Plan Review Details - Permit 00051555
Plan Review Stops For Permit 00051555
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-07-06 Cont ID  
Sent By lmartine Date 2000-07-06 Time 16:14 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-03-08 Cont ID  
Sent By dpalmer Date 2001-03-08 Time 13:38 Rev Time 0.00
Received By dpalmer Date 2001-03-08 Time 13:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-11-29 Cont ID  
Sent By dpalmer Date 2000-11-29 Time 15:38 Rev Time 0.00
Received By dpalmer Date 2000-11-29 Time 15:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-25 Cont ID  
Sent By dpalmer Date 2000-07-25 Time 08:26 Rev Time 0.00
Received By dpalmer Date 2000-07-25 Time 08:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-19 Cont ID  
Sent By dpalmer Date 2000-06-19 Time 20:03 Rev Time 0.00
Received By dpalmer Date 2000-06-19 Time 20:03 Sent To  
Notes
2001-01-08 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 `#`S ON PLANS INCLUDE ALL RECEPT. CIR.`S
 AND LIGHITNG. 215-5
  
 2)NOTE: PLEASE SHOW LIGHTING LOADS FIG-
 -URED AT 125% FOR CONTINUOUS LOAD.
 PLEASE SHOW IN CLACULATION.
  
 3)NOTE: PANEL EDP SHOWS FEED TO PANEL
 'ELP'? NOT SHOWN ON LINE DIAGRAM.
  
 EEEETE: PLEASE NOTE THAT AIC RATING OF
 PANEL 'H5B' IS SHOWN AT 14,000? PLEASE
 CALRIFY THIS AS A STANDARD RATING.
  
 5)NOTE: PLEASE CHECKLINE DIAGRAM
  
 FOR WIRE SIZING. MIGHT BE A TYPE-O FOR
 MAINS? YOU SHOW #10, PLEASE CHANGE TO
 1/0.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372
 DEWEY PALMER ELECTRICAL PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-05-16 Cont ID  
Sent By mcarsill Date 2001-05-16 Time 16:12 Rev Time 0.00
Received By mcarsill Date 2001-05-16 Time 16:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-03-29 Cont ID  
Sent By mcarsill Date 2001-03-29 Time 12:35 Rev Time 0.00
Received By mcarsill Date 2001-03-29 Time 12:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-11-28 Cont ID  
Sent By mcarsill Date 2000-11-28 Time 08:33 Rev Time 0.00
Received By mcarsill Date 2000-11-28 Time 08:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-06-08 Cont ID  
Sent By rturnque Date 2000-06-08 Time 14:18 Rev Time 0.25
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-03-15 Cont ID  
Sent By ndenmark Date 2001-03-15 Time 12:45 Rev Time 0.25
Received By ndenmark Date 2001-03-15 Time 12:45 Sent To  
Notes
2001-03-15 00:00:00AS BUILT REVISION DATED 2/28/01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-13 Cont ID  
Sent By ndenmark Date 2000-07-13 Time 09:46 Rev Time 0.10
Received By ndenmark Date 2000-07-13 Time 09:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status A Date 2000-07-13 Cont ID  
Sent By ndenmark Date 2000-06-24 Time 10:09 Rev Time 1.00
Received By ndenmark Date 2000-06-24 Time 10:09 Sent To  
Notes
2001-01-08 00:00:00ACCEPTED/CORRECTED BY REVISION7/13/00*
 1. SCU-5 SHOWS AS SOURCE OF O/A AND COND
 ITIONED AIR FOR SPACE SHOW LOCATION AND
 CONECTION TO DUCTS IN SPACE
 2. HPU-1 SHOWS 140 CFM OF OUTSIDE AIR.
 PROVIDE DETAILS OF O/A CONNECTION TO HPU
 3. SHOW EXISTING DUCT LOCATION SOURCE OF
 CONDITIONED AIR FOR DISTRIBUTION EX:
 M2.1 SHOWS 15" ROUND DUCT WHERE DOES IT
 COME FROM?
 M2.2 SHOWS 3 DUCTS 18" ROUND,17" ROUND,
 AND A 14" ROUND. WHERE DO THEY COME FROM
 4. PROVIDE DUCT AND INSULATION SPECIFI-
 CATIONS FOR AIR DISTRIBUTION COMPONENTS.
 5. PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2
  
 INSUFFICIENT INFORMATION PROVIDED FOR
 REVIEW. PROVIDE ABOVE INFORMATION AND
 RESUBMIT

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-05-11 Cont ID  
Sent By jleech Date 2001-05-11 Time 10:05 Rev Time 0.75
Received By jleech Date 2001-05-11 Time 10:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-07-26 Cont ID  
Sent By tlarge Date 2000-07-26 Time 12:25 Rev Time 2.25
Received By tlarge Date 2000-07-26 Time 12:22 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 WIDTH OF DOOR OPENING TO TOILET ROOM #
 523 SHALL BE MIN.32"CLEAR SPACE PER
 FACBC SEC.4.13.5
  
 2)PROVIDE WOOD BLOCKING IN TOILET ROOM
 #523 FOR FUTURE INSTALLATION OF GRAB
 BARS PER FACBC SEC.4.1.3(11).

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-04 Cont ID  
Sent By tlarge Date 2000-06-04 Time 09:18 Rev Time 0.75
Received By tlarge Date 2000-06-04 Time 09:18 Sent To  
Notes
2001-01-08 00:00:00PRIVATE TOILET(ROOM #523)SHALL BE
 HANDICAP ADAPTABLE PER FACBC SEC.4.1.3.
 (11).PROVIDE DETAILS FOR WOOD BLOCKING
 FOR FUTURE INSTALLATION OF GRAB BARS.
  
 WATER CLOSET SHALL BE 18"FROM FINISH
 WALL TO CENTER OF TOILET PER FACBC FIG.
 28.
  
 LOCATION OF WATER CLOSET IN TOILET ROOM
 SHALL NOT INTERFERE W/NORMAL OPERATION
 OF DOOR.SPC SEC.404.2.
  
 SINK IN BREAK ROOM SHALL COMPLY W/FACBC
 SEC.4.24.1-4.24.7.
  
 DOOR OPENING TO TOILET ROOM SHALL COMPLY
 W/FACBC SEC.4.13.5.
  
 SUBMIT SQUARE FOOTAGE OF OCCUPIED SPACE.
 NUMBERAND TYPE OF MIN.REQD.SANITARY
 FACILITIES SHALL COMPLY W/SPC TABLE 407.