Plan Review Details - Permit 00051545
Plan Review Stops For Permit 00051545
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-06-22 Cont ID  
Sent By dpalmer Date 2000-06-22 Time 09:00 Rev Time 0.00
Received By dpalmer Date 2000-06-22 Time 08:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-06 Cont ID  
Sent By dpalmer Date 2000-06-06 Time 17:28 Rev Time 0.00
Received By dpalmer Date 2000-06-06 Time 17:27 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATING OF
 EQUIPMENT MAIN. MAINS/PANELS MUST BE
 RATEDFOR THE AVAILABLE FAULT CURRENT.
 110-9/215-5 THIS IS REQ`D ON ALL PLANS
 SUBMITTED FOR NEW CONSTRUCTION.!!
  
 2)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AND
 ONE IN COMMON AREA.WIRED INLINE ,120V
 W/ BATTERY BACK-UP. NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE INCLUDE THE BLDG.STEEL
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM. THIS IS REQ`D PER 250-50/215-5
  
 4)NOTE: PLEASE NOTE THE REQ`D MEANS OF
 EGRESS LIGHTING FOR MASTER BEDROOM.
 210-70 HOWEVER YOU WANT TO SET IT UP.
  
  
 5)NOTE; PLEASE SHOW PANEL AS BEING
 MAIN BRKR.
  
 6)NOTE:PLEASE SUBMIT A PANEL SCHEDULE
 AND PLEASE INCLUDE THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S). MUST BE #12 AND 20A
 PER 210-11-C-3
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATIONN
 FOR REVIEW.IF THER ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-06-22 Cont ID  
Sent By cthirben Date 2000-06-22 Time 09:36 Rev Time 1.00
Received By cthirben Date 2000-06-22 Time 09:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-06-08 Cont ID  
Sent By cthirben Date 2000-06-08 Time 09:44 Rev Time 0.50
Received By cthirben Date 2000-06-08 Time 09:43 Sent To  
Notes
2001-01-08 00:00:00DENIED**********************************
 NO MECHANICAL SUBMITTED FOR REVIEW.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-06-07 Cont ID  
Sent By tlarge Date 2000-06-07 Time 20:10 Rev Time 0.33
Received By tlarge Date 2000-06-07 Time 20:10 Sent To  
Notes
2001-01-08 00:00:00PROVISO:SUBMIT SIGNED AND SEALED
 SANITARY RISER THAT CORRELATES W/FLOOR
 PLAN PRIOR TO PLUMBING INSPECTION.
  
 SHOWER SHALL BE A MIN.OF 30"WIDE AND A
 MIN.OF 1024 SQ.IN.IN FLOOR AREA PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.
 409.8.2.1.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-08-08 Cont ID  
Sent By lsmith Date 2000-08-08 Time 09:32 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00CHANGE FROM TIE BEAM TO BOND BEAM
 ENGINEERED LETTER DATED 7/17/00

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-06-15 Cont ID  
Sent By lmartine Date 2000-06-15 Time 07:13 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-02 Cont ID  
Sent By gjoyce Date 2000-06-02 Time 11:47 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***