Plan Review Details - Permit 00051520
Plan Review Stops For Permit 00051520
Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-10-31 Cont ID  
Sent By dpalmer Date 2000-10-31 Time 17:29 Rev Time 0.00
Received By dpalmer Date 2000-10-31 Time 17:29 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 MAINS/PANELS PER 110-9 AND 215-5
  
 2)NOTE: MISSING SD`S INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS. NFPA-72 2-2.1.1.1
 AND ON EACH LEVEL.
  
 3)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) PER 210-11-C-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-06-30 Cont ID  
Sent By dpalmer Date 2000-06-30 Time 16:37 Rev Time 0.00
Received By dpalmer Date 2000-06-30 Time 16:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-12 Cont ID  
Sent By dpalmer Date 2000-06-12 Time 18:54 Rev Time 0.00
Received By dpalmer Date 2000-06-12 Time 18:54 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 MAIN. MAINS ARE TO BE RATED FOR THE
 AVAILABLE FAULT CURRENT. 110-9 215-5
  
 2)NOTE: PLEASE LIST ON PANEL SCHEDULE
 THE REQ`D DEDICATED BATH(S) CIRCUIT(S)
 PER 210-52-C-3/ 215-5
  
 3)NOTE:PLEASE NOTE THAT IN YOUR NOTES
 YOU REF.THE 96 NEC. AS OF 3/1/00 WE ARE
 UNDER "99" NEC.
  
 4)NOTE: PLEASE INCLUDE THE BLDG. STEEL
 ON RISER. IT IS SHOWN BUT PLEASE INK IT
 IN.215-5
  
 5)NOTE:PLEASE SEE MISSING OUTLET IN BED-
 -ROOM #4. 210-52
  
 6)NOTE:PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTESPACE AS GFI/GFIPROTECT-
 -ED. 210-8-A-6
  
 7)NOTE: SMOKE DETECTOR REQ`D IN COMMON
 AREA ON FIRST LEVEL IN MULTI-LEVEL DWELL
 -ING. NFPA-72
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-10-28 Cont ID  
Sent By jleech Date 2000-10-28 Time 12:47 Rev Time 0.50
Received By jleech Date 2000-10-28 Time 12:47 Sent To  
Notes
2001-01-08 00:00:00MODEL CHANGE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-06-12 Cont ID  
Sent By cthirben Date 2000-06-12 Time 07:57 Rev Time 1.00
Received By cthirben Date 2000-06-12 Time 07:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-10-27 Cont ID  
Sent By tlarge Date 2000-10-27 Time 07:49 Rev Time 0.33
Received By tlarge Date 2000-10-27 Time 07:49 Sent To  
Notes
2001-01-08 00:00:00PROVISO:SUBMIT REVISED SANITARYRISER
 PRIOR TO INSP.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-06-03 Cont ID  
Sent By tlarge Date 2000-06-03 Time 05:04 Rev Time 0.33
Received By tlarge Date 2000-06-03 Time 05:04 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-06-23 Cont ID  
Sent By jcaloger Date 2000-06-23 Time 13:00 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2000-10-18 Cont ID  
Sent By gjoyce Date 2000-10-18 Time 16:03 Rev Time 15.00
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-30 Cont ID  
Sent By gjoyce Date 2000-05-30 Time 08:18 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***