Plan Review Details - Permit 00051429
Plan Review Stops For Permit 00051429
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-08-08 Cont ID  
Sent By lmartine Date 2000-08-08 Time 10:48 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-06-26 Cont ID  
Sent By lmartine Date 2000-06-26 Time 15:12 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 ****BUILDING REVIEW COMMENTS***
  
 1]SUBMIT CONSTRUCTION DETAILS FOR NEW
 COUNTER AND FITTING ROOM PARTITIONS.
 2]SPECIFY NEW DOORS AND HARDWARE AT
 STOCK ROOM WALLS,"C".
 3]PROVIDE DETAILS FOR SQUARING ROUND
 COLUMN AT ENTRY.
 4]EXPLAIN NOTES,METAL STUDS FOR SOFFIT
 FRAMING BY TENANT?
 5]SUBMIT PROPERLY SCALED DRAWINGS.
 6]SUBMIT OVERHEAD DOOR SPECS.AS SHOP
 DRAWINGS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-10-16 Cont ID  
Sent By dpalmer Date 2000-10-16 Time 16:49 Rev Time 0.00
Received By dpalmer Date 2000-10-16 Time 16:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1900-05-30 Cont ID  
Sent By lmartine Date 1900-05-30 Time 16:15 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 SEE BACK OF APPLICATION.
 APPR. BY DEWEY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-02 Cont ID  
Sent By mcarsill Date 2000-08-02 Time 15:39 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISH ON WALLS AND
 CEILINGS SHALL BE CLASS A OR B.
 2) EXITING THROUGH STOCKROOM PERMITTED
 IF THE FOLLOWING CONDITIONS EXIST,
 NOT MORE THAN 50 PERCENT OF EXIT ACCESS
 IS PROVIDED THROUGH STOCKROOM, AN AISLE
 OF AT LEAST 44" WIDE TO BE PRESENT
 THROUGH STOCKROOM, THE 44" AISLE IS TO
 BE MAINTAINED, AND THE STOCKROOM
 CANNOT BE LOCKED.
 3) IF FIRE SPRINKLER RELOCATION REQUIRED
 THEN A SEPARATE PLAN AND PERMIT IS
 REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-06-08 Cont ID  
Sent By rturnque Date 2000-06-08 Time 15:14 Rev Time 0.15
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE FIRE SPRINKLER DRAWINGS

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-06-03 Cont ID  
Sent By pschmitz Date 2000-06-03 Time 13:49 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO: 1 DRINKING FOUNTIAN REQUIRED
 SPC TAB 407.