Plan Review Details - Permit 00051429
| Plan Review Stops For Permit 00051429 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-08-08 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-26 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-06-26 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | ****BUILDING REVIEW COMMENTS*** | | | | | | 1]SUBMIT CONSTRUCTION DETAILS FOR NEW | | | COUNTER AND FITTING ROOM PARTITIONS. | | | 2]SPECIFY NEW DOORS AND HARDWARE AT | | | STOCK ROOM WALLS,"C". | | | 3]PROVIDE DETAILS FOR SQUARING ROUND | | | COLUMN AT ENTRY. | | | 4]EXPLAIN NOTES,METAL STUDS FOR SOFFIT | | | FRAMING BY TENANT? | | | 5]SUBMIT PROPERLY SCALED DRAWINGS. | | | 6]SUBMIT OVERHEAD DOOR SPECS.AS SHOP | | | DRAWINGS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-10-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-16 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-16 |
Time |
16:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1900-05-30 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
1900-05-30 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | SEE BACK OF APPLICATION. | | | APPR. BY DEWEY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-08-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-02 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISH ON WALLS AND | | | CEILINGS SHALL BE CLASS A OR B. | | | 2) EXITING THROUGH STOCKROOM PERMITTED | | | IF THE FOLLOWING CONDITIONS EXIST, | | | NOT MORE THAN 50 PERCENT OF EXIT ACCESS | | | IS PROVIDED THROUGH STOCKROOM, AN AISLE | | | OF AT LEAST 44" WIDE TO BE PRESENT | | | THROUGH STOCKROOM, THE 44" AISLE IS TO | | | BE MAINTAINED, AND THE STOCKROOM | | | CANNOT BE LOCKED. | | | 3) IF FIRE SPRINKLER RELOCATION REQUIRED | | | THEN A SEPARATE PLAN AND PERMIT IS | | | REQUIRED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-06-08 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-06-08 |
Time |
15:14 |
Rev Time |
0.15 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVIDE FIRE SPRINKLER DRAWINGS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-06-03 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-06-03 |
Time |
13:49 |
Rev Time |
0.75 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: 1 DRINKING FOUNTIAN REQUIRED | | | SPC TAB 407. |
|
|
|