Plan Review Details - Permit 00051379
Plan Review Stops For Permit 00051379
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-28 Cont ID  
Sent By lmartine Date 2000-09-28 Time 13:28 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 REVISION SUBMITTED ON 9/28/00 IS
 NOT APPROVED.CONTRACTOR SHALL APPLY FOR
 SEPERATE PERMIT FOR INTERIOR BUILDOUT.
 THIS PERMIT FOR RESTROOMS ONLY.
 ENERGY EFFIC. REPORT REQUIRED.
  
 REVIEWED BY:
 LUIS MARTINEZ
 659-8096
 EXT-8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-06-26 Cont ID  
Sent By lmartine Date 2000-06-26 Time 17:06 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-05-30 Cont ID  
Sent By dpalmer Date 2000-05-30 Time 20:35 Rev Time 0.00
Received By dpalmer Date 2000-05-30 Time 20:35 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE:OUTLET SPACING TO MEET LOCAL CODE
 PER 210-50 EVERY 12`.
  
 2)NOTE: PLEASE HAVE ALL BRANCH CIRCUIT
 `#`S ON PLANS.
  
 3)NOTE: PLEASE SHOW MEANS OF EGRESS
 LIGHTING REQ`D PER 210-70(REAR DOOR) OR
 IS THERE OTHER LIGHITNG?
 4)NOTE: PLEASE SHOW SHOW WINDOW LIGHTING
 REQ`D BY 210-62
  
 5)NOTE: PLEASE NOTE THAT EGRESS LIGHTING
 SWITCHING IS REQ`D FOR REAR ENTRANCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT
 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-06-14 Cont ID  
Sent By rturnque Date 2000-06-14 Time 10:53 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-06-06 Cont ID  
Sent By ndenmark Date 2000-06-06 Time 14:50 Rev Time 0.33
Received By ndenmark Date 2000-06-06 Time 14:50 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 DUCT SMOKE DETECTOR TO BE TIED TO BUILD-
 ING FIRE ALARM OR HORN ANDSTROBE FOR
 NOTIFICATION PER NFPA 90A

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-31 Cont ID  
Sent By tlarge Date 2000-08-31 Time 12:41 Rev Time 0.30
Received By tlarge Date 2000-08-31 Time 12:41 Sent To  
Notes
2001-01-08 00:00:00CLARIFICATION ON LOCATION OF FIXTURES IN
 TOILET ROOMS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-23 Cont ID  
Sent By pschmitz Date 2000-08-23 Time 10:37 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-06-04 Cont ID  
Sent By tlarge Date 2000-06-04 Time 07:21 Rev Time 0.65
Received By tlarge Date 2000-06-04 Time 07:21 Sent To  
Notes
***NONE***