| Plan Review Stops For Permit 00051311 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2000-11-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-11-17 |
Time |
11:08 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-11-14 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-11-14 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 3RD CKLST W/ APPLICATION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-10-25 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-10-25 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2000-10-24 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | LETTER W APPLICATION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-10 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-07-10 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-22 |
Time |
20:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-22 |
Time |
20:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2001-10-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-11 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-11 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2001-10-11 00:00:00 | LETTER SUBMITTALS ONLY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2001-10-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-05 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-05 |
Time |
10:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-10-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-05 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-05 |
Time |
07:28 |
Sent To |
|
|
| Notes |
| 2001-10-05 00:00:00 | REV FOR TWO SHEETS ONLY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-10-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-01 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-01 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2001-10-01 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT NOT ALL SHEETS | | | SIGNED. 471.025 | | | PLEASE ALSO NOTE THAT THERE ARE THREE | | | DIFFERENT SIGNATURES ON PLANS FOR | | | ELECTRICAL ENGINEER. PLEASE CALRIFY! | | | PLEASE HAVE ENGINEER OF RECORD SIGN | | | HIS SEALED DOCUMENTS.471.025 | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-10-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-31 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-31 |
Time |
13:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-06-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-23 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-06-23 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | ***************** UNSAT **************** | | | | | | LOAD CALCULATIONS AT THE BOTTOMOF EACH | | | PANEL NOT COMPLETED INCLUDING MAINS. | | | SEE PERMIT #00051322 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-10-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-01 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-01 |
Time |
15:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-09-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-28 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-28 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESSES | | | TO COMPLY WITH CITY CODE REQUIREMENTS. | | | 2) PLEASE CONTACT THE FIRE PREVENTION | | | BUREAU AT 835-2910 TO REQUEST KNOX-BOX | | | APPLICATION(S) FOR THE BUILDINGS. | | | 3) ELEVATORS TO COMPLY WITH ANSI A17.1 | | | AND THE UNIFORM FIRE CODE FOR ELEVATORS | | | 4A-47. | | | 4) INTERIOR FINISHES IN EXITS TO BE | | | CLASS A OR B. INTERIOR FINISHES IN | | | OFFICES TO BE CLASS A, B, OR C. | | | 5) PLEASE PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN | | | ON DRAWINGS. CUT SHEETS REQUIRED ON | | | ALL DEVICES PLANNED FOR USE. | | | 6) FIRE ALARM SYSTEM AND FIRE SPRINKLER | | | SYSTEM TO BE MONITORED BY A UL LISTED | | | CENTRAL STATION APPROVED BY THE FIRE | | | RESCUE DEPARTMENT. | | | 7) EXIT DOORS 113 AND 116 WHEN OPENED | | | ARE NOT TO INTERFERE WITH ONE ANOTHER. | | | 8) EXIT DOORS WHEN OPENED ARE NOT TO | | | PROJECT MORE THAN SEVEN INCHES INTO | | | A REQUIRED EXIT CORRIDOR. | | | 9) ALL STAIRS TO COMPLY WITH NEW STAIRS | | | PER NFPA 101, THE LIFE SAFETY CODE, | | | 1985 EDITION. | | | APPROVED PROVISO: |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-06-15 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-06-15 |
Time |
11:47 |
Rev Time |
1.30 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVIDE FIRE SPRINKLER DRAWINGS. | | | FIRE ALARM SYSTEM SHALL BE CLASS "A" OR | | | ADDRESSABLE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-09-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-27 |
Time |
08:30 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-09-27 |
Time |
07:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-06-26 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-06-26 |
Time |
14:53 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-06-26 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | MODEL COUNTYWIDE AMENDMENTS AS ADOPTED | | | BY THE CITY OF WEST PALM BEACH REQUIRES | | | EQUIPMENT MOUNTED ON ROOF STANDS TO HAVE | | | A MINIMUM OF 18" CLEARANCE BETWEEN ROOF | | | SURFACE AND THE BOTTOM OF THE SUPPORT | | | STRUCTURE OF THE STAND |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2001-10-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-10 |
Time |
09:28 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-10-10 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2001-09-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-27 |
Time |
11:59 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-09-27 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2001-09-27 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | PAGE P6-1 WATER HAMMER ARRESTORS TO BE | | | INSTALLED PER MANUFACTURE INSTALLATION | | | INSTRUCTIONS AND WH-PDI 201 AND NOT AT | | | THE TOP OF THE DROPS AS SHOWN ON DOMES- | | | TIC WATER ISOMETRIC. PLEASE SHOW PROPER | | | LOCATION ON PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-11-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-14 |
Time |
08:51 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2000-11-14 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-09-26 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-26 |
Time |
18:45 |
Rev Time |
3.50 |
| Received By |
tlarge |
Date |
2000-09-26 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SITE PLAN-SHT.5-WATER SERVICE IS SHOWN | | | AS 2 1/2" INCH AND ALSO AS 3".CLARIFY. | | | | | | 2)PLEASE NOTE THE OCCUPANT LOAD ON THE | | | PLANS PER SPC TABLE 407.SEE SPC SEC. | | | 407.1.3.FOR ALLOWED DEDUCTIBLE AREAS. | | | SHOW THE CALCULATIONS ON THE PLAN. | | | | | | 3)SHT.A-4-IDENTIFY THE HANDICAP URINAL | | | ON THE PLANS.THE STALL DOOR CANNOT | | | SWING INTO THE CLEAR FLOOR SPACE FOR THE | | | URINAL PER FACBC SEC.4.17.5. | | | | | | 4)SHT.A-8-PLEASE CLARIFY SECONDARY | | | DRAINAGE CALCULATIONS.SEE APPENDIX "A" | | | IN THE SPC FOR SCUPPER SIZING. | | | | | | 5)DELETE REFERENCE TO SFBC AT SAND/OIL | | | INTERCEPTOR.SHT.P0-1. | | | | | | 6)SHT.P5-1-MAX.NUMBER OF FIXTURE UNITS | | | ON 3" HORIZONTAL BRANCH CONNECTED TO THE | | | BUILDING DRAIN SHALL NOT EXCEED 20 F.U'S | | | PER TABLE 714.1.(SEE U/G BRANCH FOR LAV. | | | WASTE STACKS.) | | | | | | 7)THE SQ.FOOTAGE DRAINED BY THE ROOF | | | DRAINS SHOWN ON SHT.P2.1 DOESN'T | | | CORRELATE W/SHT.P5-1. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-06-12 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-12 |
Time |
16:43 |
Rev Time |
3.00 |
| Received By |
tlarge |
Date |
2000-06-12 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT COPY OF JOB SPECIFICATIONS FOR | | | REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | AN ADDITIONAL LAVATORY IS REQD.IN THE | | | WOMEN'S RESTROOM PER TABLE 407.(REQD.IN | | | ON ALL FLOORS.) | | | | | | SUBMIT STORM DRAINAGE AND CONDENSATE | | | ISOMETRICS FOR REVIEW.COUNTYWIDE AMEND- | | | MENTS SEC.104.2.1. | | | | | | SHOW HEIGHT DIMENSION FOR SCUPPER ON | | | DETAIL #12 AND SUBMIT DETAILS FOR OVER- | | | FLOW DRAINAGE FOR HIGH ROOF AREA.COMPLY | | | W/SPC SEC.1109.1,1109.2,1109.3. | | | | | | SHT.A-15-SHOW MOUNTING HEIGHT OF ALL | | | HANDICAP ACCESSIBLE FIXTURES AND | | | APPURTENANCES.SHOW CLEAR FLOOR SPACE | | | UNDER FIXTURES TO FINISH FLOOR.COMPLY W/ | | | FACBC OCT.1997 EDITION. | | | | | | SHT.P-4-LOCATION OF VTR'S SHALL COMPLY | | | COMPLY W/SPC SEC.905.5. | | | | | | SHT.P-5-SIZE THE SOIL STACKS FOR W.C.'S | | | IN THE WOMEN'S R.R.COMPLY W/SPC TABLE | | | 714.2. | | | | | | SIZE THE HORIZ.BRANCH FOR THE LAVS. | | | COMPLY W/SPC TABLE 714.1.(DOUBLE LAVS.) | | | SHOW SLOPE OF PIPE. | | | | | | SHT.P6-1-3/4"WATER LINE TO MOP SINKS | | | SUPPLIED BY 1/2" LINE.SPC 607.1,607.4. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2001-10-05 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-10-05 |
Time |
11:36 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2001-10-01 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-10-01 |
Time |
10:39 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2001-09-26 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-09-26 |
Time |
13:16 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-26 00:00:00 | DENIED BY ZONING-8-REQUIRED HC SPACES | | | ONE SPACE HAS PERSON EXITING BEHIND THE | | | CAR, THIS IS NOT ALLOED |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-11-20 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-07-10 |
Time |
13:57 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|