Plan Review Details - Permit 00051291
Plan Review Stops For Permit 00051291
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-10-16 Cont ID  
Sent By dpalmer Date 2000-10-16 Time 10:02 Rev Time 0.00
Received By dpalmer Date 2000-10-16 Time 10:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-11 Cont ID  
Sent By dpalmer Date 2000-09-11 Time 17:38 Rev Time 0.00
Received By dpalmer Date 2000-09-11 Time 17:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-06-19 Cont ID  
Sent By dpalmer Date 2000-06-19 Time 11:46 Rev Time 0.00
Received By dpalmer Date 2000-06-19 Time 11:46 Sent To  
Notes
2001-01-08 00:00:00STILL DIDN`T ADDRESS ALL OF THE ORIG.
 NOTES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-23 Cont ID  
Sent By dpalmer Date 2000-05-23 Time 20:01 Rev Time 0.00
Received By dpalmer Date 2000-05-23 Time 20:01 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 SHOWING THE REQ`D DEDICATED BATH(S)
 CIRCUIT(S) PER 210-11-C-3. MUST BE #12
 AWG, AND 20 AMP.REVISED PANEL SCHEDULES
 BEFORE FINAL ELECTRICAL INSPECTION.
 2)NOTE: PLEASE NOTE THAT THE USE IS
 RESIDENTIAL. SO OUTLET SPACING NEEDS TO
 MEET CODE. 210-522`,6`,12` RULE. NOTE
 MISSING OUTLETS FOR 2` OF WALL. ETC.
  
 3)NOTE: PLEASESHOW THE REQ`D MEANS OF
 EGRESS LIGHTING FOR THE TWO DOORS SHOWN.
 PER 210-70. IF THERE IS EXISTING LIGHT-
 ING, PLEASE SHOW.
  
 4)NOTE: ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE GFI/GFI PROTECTED
 PER 210-8-A-6
  
 5)NOTE: YOU ARE SHOWING FRONT OFFICE/DEN
 THESE ARE ROOMS THAT ARE ADAPTABLE TO
 SLEEPING ROOMS. PLEASE INCLUDE SMOKE
 DETECTORS INSIDE AND OUTSIDE. PLEASE
 SHOW THE USE OF THE FIRST FLOOR AS TO
 WHERE FRONT STEPS ARE GOING? SMOKE
 DETECTOR WILL BE REQ`D ON LOWER LANDING.
 NFPA-72 2-2.1.1.1
  
 6)NOTE: IF FRONT APT IS SEPARATE TENAT
 SPACE? THEN THE PANEL IN REAR APT. MAY
 NOT BE IN THERE. PANELS MUST BE INSTALL-
 -ED IN THAT SPACE.
  
 7)NOTE: PLEASE SHOW FIRST FLOOR OCCP.
 8)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR EXISTING PANLES/SERVICE. 215-5
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-10-13 Cont ID  
Sent By mcarsill Date 2000-10-13 Time 16:07 Rev Time 0.00
Received By mcarsill Date 2000-10-13 Time 16:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-01 Cont ID  
Sent By mcarsill Date 2000-09-01 Time 10:05 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-06-29 Cont ID  
Sent By rturnque Date 2000-06-29 Time 10:43 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE 1HR. PROTECTION SURROUNDING
 SINGLE MEANS OF EGRESS FROM 2ND FLOOR
 OFFICE AREA. PROVIDE 45 MINUTE,SELF
 CLOSING,FIRE DOORS TO ALL DOORS OPENINGS
 OF SINGLE MEANS OF EGRESS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-10-13 Cont ID  
Sent By tlarge Date 2000-10-13 Time 19:03 Rev Time 0.30
Received By tlarge Date 2000-10-13 Time 18:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-01 Cont ID  
Sent By tlarge Date 2000-09-01 Time 17:11 Rev Time 0.25
Received By tlarge Date 2000-09-01 Time 17:11 Sent To  
Notes
2001-01-08 00:00:00REPLACE FIXTURES/CONNECT TO EXIST.PLBG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-06-12 Cont ID  
Sent By tlarge Date 2000-06-12 Time 07:25 Rev Time 0.30
Received By tlarge Date 2000-06-12 Time 07:25 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-10-17 Cont ID  
Sent By jgomez Date 2000-10-17 Time 12:20 Rev Time 1.00
Received By jgomez Date 2000-10-17 Time 12:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-09-13 Cont ID  
Sent By jgomez Date 2000-09-13 Time 17:54 Rev Time 3.00
Received By jgomez Date 2000-09-13 Time 17:54 Sent To  
Notes
2001-01-08 00:00:00SECOND CHECKLIST:
 1-SPECIFY THE STAIR PROTECTION AS PER
 SECTION 1006 SBC 1997.
 2-SPECIFY STAIRWAY FIRE RATING.
 TABLE 705.1.2 SBC 1997.
 3-OFFICE/STORAGE AT NORTH CORNER IS
 ANOTHER USE. NEED TENANT SEPARATION.
 -PROVIDE TENANT SEPARATION BETWEEN THE
 TWO USES. SECTION 704 SBC 1997.
 -OFFICE TO HAVE RESTROOM.
  
  
  
  
 4-SAFETY GLASS. SECTION 2405.2 SBC 1997.
 DOORS WHERE NOT ERASED. ALTERNATIVELY,
 YOU MAY USE BY PASS DOORS AT CLOSETS.
 5-DOORS BY THE STAIRWAY NEED TO BE FIRE
 RATED AND SELF-CLOSING. TABLE 705.1.2
 SBC 1997.
 6-PROVIDE A COMPLETE WINDOW AND DOOR
 SCHEDULE IN ORDER TO ACCURATELY REVIEW
 COMPLIANCE WITH TABLE 600 SBC 1997 AND
 EGRESS REQUIREMENTS.
 -IN ADDITION PROVIDE BUILD'G DIMENSIONS
 AND INTERIOR HEIGHTS TO DETERMINE THE
 TOTAL BUILDING WALL AREA & PERCENTAGE
 OF OPENINGS ALLOWED AT NORTH ELEVATION
 BY TABLE 600 SBC 1997.
 7-CLARIFY WHY THERE IS AN OPENING FROM
 THE COMMERCIAL SPACE TO THE EGRESS
 STAIRWAY ENCLOSURE.
  
  
  
  
  
  
 * IF YOU HAVE ANY QUESTIONS PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT
 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-27 Cont ID  
Sent By jgomez Date 2000-06-27 Time 19:57 Rev Time 4.00
Received By jgomez Date 2000-06-27 Time 19:57 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-PROVIDE SAFETY GLASS AS REQUIRED. SEE
 PLANS FOR COMMENTS. SEC 2405.2 SBC/97.
 3-PROVIDE A COMPLETE WINDOW AND DOOR
 SCHEDULE (NEW AND EXISTING).
 NOTE: KEEP IN CONSIDERATION EGRESS
 REQUIREMENTS FOR RESIDENTIAL AND FOR
 MIXED USE. (RESIDENTIAL AND BUSINESS).
 4-PROVIDE COMPLETE DETAILS AND SPECS
 SHOW'G THE FIRE RESISTANCE SEPARATIONS
 REQUIRED AT FLOOR ASSEMBLY AND TENANT
 WALL SEPARATIONS (OFFICE/APARTMENT)
 SECTION 704 SBC 1997.
 5-SPECIFY THE STAIR PROTECTION AS PER
 SECTION 1006 SBC 1997.
 -PROVIDE DETAILS AND SPECIFICATIONS FOR
 COMPLIANCE WITH SECTION 1007.5 FOR
 HANDRAILS.
 6-PROVIDE COMPLETE HVAC DRAWINGS AND
 ENERGY CALCULATIONS AND MANUAL J CALCS
 AS REQUIRED.
 7-PROVIDE COMPLETE INFORMATION TO ALLOW
 CALCULATION OF PERCENTAGE OF OPENINGS
 ALLOWED AT NORTH ELEVATION AS PER
 TABLE 600 SBC 1997.
 8-WHERE IS THE RESTROOM FOR INDEPENDENT
 OFFICE.
 9-CLEARLY SPECIFY ALL SCOPE OF WORK TO
 BE DONE IN ORDER TO DETERMINE A MORE
 ACCURATE VALUATION OF THE PROJECT OR
 PROVIDE COPY OF CONSTRUCTION CONTRACT.
 10-PROVIDE SMOKE DETECTOR AT FIRST FLOOR
 SECTION 905.2.2 SBC 1997.
 NOTE:
 PLEASE RETURN REVIEWED SET AFTER ALL
 CORRECTIONS ARE DONE TO EXPEDITE THE
 REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT JULIO GOMEZ, BUILDING PLAN
 REVIEWER, AT 659-8096 X 8232.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-08 Cont ID  
Sent By gjoyce Date 2000-05-24 Time 10:47 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS SURVEY & DWELLING COUNT