Plan Review Details - Permit 00051268
Plan Review Stops For Permit 00051268
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-06-28 Cont ID  
Sent By hpiskura Date 2000-06-28 Time 10:26 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-05-30 Cont ID  
Sent By dpalmer Date 2000-05-30 Time 21:20 Rev Time 0.00
Received By dpalmer Date 2000-05-30 Time 21:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-23 Cont ID  
Sent By mcarsill Date 2000-08-23 Time 10:07 Rev Time 0.00
Received By mcarsill Date 2000-08-23 Time 10:07 Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISH ON WALLS AND CEILINGS
 SHALL BE CLASS A OR B.
 2) PROVIDE COMPLETE SHOP DRAWINGS FOR
 FIRE ALARM DEVICES SHOWN ON PLANS.CUT
 SHEETS NEEDED ON DEVICES PLANNED FOR
 USE. A SEPARATE PLAN AND PERMIT REQUIRED
 3) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED THROUGHOUT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-07-21 Cont ID  
Sent By hpiskura Date 2000-07-21 Time 08:26 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00APP'D ON MIT APP HHP

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-08-17 Cont ID  
Sent By cthirben Date 2000-08-17 Time 13:46 Rev Time 1.00
Received By cthirben Date 2000-08-17 Time 13:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-20 Cont ID  
Sent By ndenmark Date 2000-07-20 Time 14:53 Rev Time 0.50
Received By ndenmark Date 2000-07-20 Time 14:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status A Date 2000-07-20 Cont ID  
Sent By ndenmark Date 2000-06-09 Time 15:39 Rev Time 1.00
Received By ndenmark Date 2000-06-09 Time 15:39 Sent To  
Notes
2001-01-08 00:00:00ACCEPTED BY REVISION 7/20/00 ***********
  
  
 FLORIDA ENERGY CODE REQUIRES ALL AIR
 DISTRIBUTION COMPONENTS TO BE INSULATED
 PER 410.1.ABCD2.1 INCLUDES TOP SIDES OF
 DIFFUSERS
 ASHRAE 62-89 TABLE 2 PROVIDES REQUIRE-
 MENTS FOR OUTSIDE AIR. THIS SPACE DOES
 NOT MEET CRITERIA FOR REDUCING QUANTITY
 OF OUTSIDE AIR BY CO2 SENSOR
 6.1.3 2. STATES WHERE OCCUPANCY DIFFERS
 FROM TABLE 2, ETC. THERE IS A SPECIFIC
 TABLE APPLICATION FOR THIS FACILITY TYPE
 PROVIDE ASHRAE 62-89 TABLE 2 QUANTITY OF
 OUTSIDE AIR FOR SPACE
 NOTE: NFPA 90A REQUIRES NOTIFICATION OF
 ACTIVIATION OF DUCT SMOKE DETECTOR BY
 VISUAL AND AUDIBLE SIGNAL. THIS IS NOT
 REQUIRED TO BE TIED TO THE MALL FIRE
 ALARM SYSTEM

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-20 Cont ID  
Sent By tlarge Date 2000-08-20 Time 12:18 Rev Time 0.30
Received By tlarge Date 2000-08-20 Time 12:08 Sent To  
Notes
2001-01-08 00:00:00PLUMBING NOT AFFECTED THIS REVISION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-07-20 Cont ID  
Sent By pschmitz Date 2000-07-20 Time 13:54 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-04 Cont ID  
Sent By tlarge Date 2000-06-04 Time 06:28 Rev Time 2.00
Received By tlarge Date 2000-06-04 Time 06:27 Sent To  
Notes
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD BASED ON SQUARE
 FEET OF HABITABLE FLOOR SPACE.SEE SPC
 SEC.407.1.3.FOR ALLOWED DEDUCTIBLE AREAS
  
 SHT.A6.1-TOILET PAPER DISPENSER SHALL BE
 MOUNTED A MIN.19"TO CENTER PER FACBC
 FIG.29(B).
  
 SHT.A6.1-URINAL SHALL BE MOUNTED A MAX.
 OF 17"A.F.F.TO THE RIM PER FACBC SEC.
 4.18.2.
  
 SHT.A6.1-A MIN.OF 29"IS REQD.UNDER THE
 LAV.PER FACBC SEC.4.19.2.
  
 SHT.A6.2-FITTING ROOMS SHALL COMPLY W/
 FACBC SECS.4.1.3(21), 4.35.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 SUPPLY FIXED LADDERFOR ACCESS OR
 RELOCATE TO FLOOR.SPC 501.7.
  
 VENTS FOR FLOOR DRAINS SHALL COMPLY W/
 SPC SEC.906.2.2.
  
 MIN.SIZE DRAIN UNDERGROUND SHALL BE 2"
 PER SPC SEC.714.4.