Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-22 Cont ID  
Sent By dpalmer Date 2001-03-22 Time 21:37 Rev Time 0.00
Received By dpalmer Date 2001-03-22 Time 21:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-25 Cont ID  
Sent By dpalmer Date 2000-05-25 Time 20:13 Rev Time 0.00
Received By dpalmer Date 2000-05-25 Time 20:13 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING
 OF MAIN/PANEL. MIANS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9
  
 2)NOTE:PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) AS PER 210-11-C-3
 MUST BE 20 AMP AND #12.
  
 3)NOTE: PLEASE INCLUDE THE BLDG.STELL
 OF BOTH NEW ADDITIONS AS PART OF THE
 GROUNDING ELECTRODE SYSTEM AS REQ`D BY
 250-50 OF THE NEC/215-5
  
 4)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS IN DWELL-
 -INGS. THE MAJORITY OF THE STRUCTURE
 IS BEING WORKED ON (50)%. SD`S WILL BE
 REQ`D IN EXISTING BEDROOM ALSO. ALL
 MUST BE 120V AND WIRED IN SERIES. AS PER
 NFPA-72 2-2.1.1.1.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-02 Cont ID  
Sent By pkrauss Date 2001-04-02 Time 09:51 Rev Time 0.35
Received By pkrauss Date 2001-04-02 Time 09:51 Sent To  
Notes
2001-04-02 00:00:00NOTE ON PLAN - 1997 SMC 503.3.1, WINDOW
 HAVE HAVE 3 SQ FT MINIMUM OPEN SPACE OR
 MECHANICAL EXHAUST IS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-06-05 Cont ID  
Sent By cthirben Date 2000-06-05 Time 08:42 Rev Time 1.00
Received By cthirben Date 2000-06-05 Time 08:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-20 Cont ID  
Sent By jleech Date 2001-03-20 Time 17:15 Rev Time 0.33
Received By jleech Date 2001-03-20 Time 17:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-03 Cont ID  
Sent By pschmitz Date 2000-06-03 Time 12:59 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1)WATER CLOSET IN GARAGE TO COMPLY WITH
 SPC SEC 404.3 PRIVACY SCREEN, ALSO
 SEC 404.1 LIGHT & VENTILATION.
 (2)WATER CLOSETS IN BOTH BATH ROOMS NOT
 VENTED,SPC SEC 913.2 "MAJOR OVER MINOR".
 ALSO MASTER BATH TUB & LAV WASTE,
 STRAIGHT TEE BRANCH PROHIBITED SEC 307.3
 (3)SHOW HOT & COLD WATER RISER & PIPE
 SIZES,SEC 104.2 DRAWINGS.
 END OF COMMENTS

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-03-29 Cont ID  
Sent By jgomez Date 2001-03-29 Time 17:33 Rev Time 3.00
Received By jgomez Date 2001-03-29 Time 17:32 Sent To  
Notes
2001-03-29 00:00:00SECOND CHECKLIST:
 1-BEDROOM WINDOWS DON'T COMPLY WITH THE
 EGRESS REQUIREMENTS. SEC 1005.4.2 AND
 SEC. 1005.4.4 SBC 1997.
 2-SURVEY DOESN'T MATCH FLOOR PLAN AND
 PLOT PLAN ON SHEET #2.
 -REVISE BUILDING DIMENSIONS, SETBACKS,
 DRIVEWAYS, BUILDING FOOTPRINT, ETC.
 3-PROFESSIONAL ENGINEER OF RECORD TO
 DATE HIS DRAWINGS WHEN SEALING AND
 SIGNING DOCUMENTS FOR PUBLIC RECORDS
 AS REQUIRED BY CHAPTER 471 FL STATUTES
 4-ROOF TRUSS DRAWINGS:
 -ALL TRUSS DRAWINGS TO BE REVIEWED BY
 THE PROFESSIONAL DESIGNER OF RECORD.
 -DESIGNER OF RECORD IS USING SBC 1997
 DESIGN CRITERIA. TRUSSES ARE DESIGNED
 BASED ON ASCE 7-93. MIXING OF THE TWO
 CODES IS NOT ALLOWED. SEE SEC 1606.1.2
 SBC 1997. REVISE AS REQUIRED.
 -CONNECTOR SPECIFIED FOR TRUSS T03 AT
 BEARING POINT #8 DOESN'T WORK. REVISE
 AS REQUIRED. SEE TRUSS PROFILE.
 -TRUSS ENGINEER TO DATE ALL DRAWINGS AT
 TIME OF SEALING THEM AS REQUIRED BY
 FLORIDA STATUTES, CHAPTER 471.
 SEE ALL GENERAL DETAILS.
 5-PROVIDE CURRENT PRODUCT APPROVAL FOR:
 -AWNING WINDOWS (PRODUCT APPROVAL IS
 EXPIRED)
 -OCTAGON WINDOWS.
 -WINDOW MULLIONS
 6-STORM PANELS:
 -PROVIDE KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE (SEE SAMPLE).
 -CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE
 AND SPACING TO BE USED ACCORDING TO
 THE MEAN ROOF HEIGHT,DESIGN PRESSURES,
 PANEL SPAN, CONNECTION TYPE, EDGE
 DISTANCE AND STRUCTURE TO BE ATTACHED
 TO (MASONRY).
 -THERE ARE THREE DIFFERENT TYPES OF
 STORM SHUTTERS SUBMITTED (ROLL UP,
 ACCORDION AND STORM PANELS), CLARIFY
 WHICH ONE IS GOING TO BE USED AND
 PROVIDE THE KEY PLAN, INSTALLATION
 SCHEDULE AND ALL REQUIRED INFORMATION.
 7-INFORMATION ON ROOF FRAMING PLAN ON
 SHEET #4 IS EXTREMELY LIGHT AND IS NOT
 SUITABLE FOR MICROFILMING FOR PUBLIC
 RECORDS. CORRECT AS REQUIRED.
 8-OWES $827.34 FOR LOW VALUATION, RADON
 FEES AND INCREASE ON THE SQUARE
 FOOTAGE OF THE ADDITION.
 NOTE: SOME FEES MAY HAVE BEEN PAID
 FROM PREVIOUS CHECKLIST. PLEASE BRING
 COPIES OF THE PAID RECEIPTS TO
 VERIFY WHAT WAS PAID.
 9-SPECIFY FIREBLOCKING ON WALL SECTION.
 SECTION 2305 SBC 1997.
 10-SPECIFY SIZE OF VENTS FOR ROOF
 VENTILATION. SEC. 2309.7 SBC 1997.
 11-PLANS WERE CHANGED FROM ORIGINAL
 SUBMITTAL. SEE ZONING COMMENTS
 ATTACHED.
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-30 Cont ID  
Sent By jgomez Date 2000-06-30 Time 16:09 Rev Time 2.50
Received By jgomez Date 2000-06-30 Time 16:09 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-BEDROOM WINDOWS DON'T COMPLY WITH
 EGRESS REQUIREMENTS, SECTION 1005.4
 SBC 1997.
 3-ENGINEER TO CLEARLY INCLUDE HIS NAME,
 LICENSE NUMBER, ADDRESS.
 -ENGINEER TO PROVIDE DATE WHEN DRAWINGS
 ARE SEALED.
 4-PROVIDE SURVEY SHOWING NEW BUILDING
 LAYOUT. SIGNED, SEALED AND DATED.
 5-PROVIDE ATTIC ACCESS IN FAMILY ROOM
 WING. SECTION 2309.6 SBC 1997.
 6-PROVIDE SOIL TEST REPORT.
 7-PROVIDE ENGINEERED ROOF TRUSS DWGS.
 REVIEWED BY THE PROFESSIONAL DESIGNER
 OF RECORD.
 -SPECIFY ATTACHMENT OF NEW ROOF TRUSSES
 OVER EXISTING ROOF. NOTE: TAKE INTO
 CONSIDERATION EAST WING WHERE EXISTING
 ROOF TRUSSES AND NEW ROOF TRUSSES SEEM
 TO BE RUNNING PERPENDICULAR TO EACH
 OTHER.
 -PROVIDE COMPLETE CONSTRUCTION DETAIL
 AND SPECIFICATIONS FOR INSTALLATION OF
 GIRDER TRUSS TO RECEIVE EXISTING ROOF
 TRUSSES AT FAMILY ROOM WING. PROVIDE
 SHORING SPECIFICATIONS.
 SECTION 104.2.2 CITY AMENDMENTS.
 8-PROVIDE BUCK DETAIL FOR OPENINGS OVER
 12'-0" WIDE. SEE WINDOW/DOOR BUCK
 INSTALLATION TABLE ON DRAWING #6.
 9-COMPLETELY FILL ALL THE INFORMATION
 ON THE DESIGN CERTIFICATION FOR BLDG
 CODE COMPLIANCE FORM AND ENGINEER TO
 DATE DOCUMENT AT TIME OF IMPRESSING
 HIS SEAL. FLORIDA STATUTES CHAPTER 471
 10-OWNER/AGENT TO SIGN AND DATE THE
 ENERGY CALCULATIONS TO CERTIFY
 COMPLIANCE WITH FLORIDA ENERGY CODE.
 11-PROVIDE CURRENT PRODUCT APPROVALS FOR
 SLIDING, AWNING, SLIDING AND OCTAGON
 WINDOWS, FRENCH DOORS, ROOF TILE.
 12-STORM PANELS:
 -PROVIDE PRODUCT APPROVAL WITH LEGIBLE
 DRAWINGS.
 -PROVIDE A COMPLETE INSTALLATION SCHED,
 AS PER CITY SAMPLE ATTACHED, AND KEY
 PLAN.
 -CLEARLY INDICATE ON PRODUCT APPROVAL
 DRAWINGS THE SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE AND SPACING
 TO BE USED IN THIS HOUSE ACCORDING TO
 THE MEAN ROOF HEIGHT, DESIGN PRESURES,
 EDGE DISTANCE, STORM PANEL SPAN AND
 STRUCTURE TO BE ATTACHED TO (CONCRETE,
 MASONRY OR WOOD).
 13-OWES $379.63 FOR LOW VALUATION AND
 RADON FEES. SEE ATTACHED RECEIPT.
  
  
 NOTES:
 1-SEE COMMENTS BY OTHER TRADES.
 2-PLEASE RETURN REVIEWED SETS IN ORDER
 TO EXPEDITE THE REVIEW PROCESS.

Review Stop Z ZONING
Rev No 2 Status F Date 2001-03-29 Cont ID  
Sent By sgraham Date 2001-03-29 Time 15:33 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-03-29 00:00:00DO NOT MEET REAR SETBACK/SITE PLAN &
 SURVEY DO NOT MATCH

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-24 Cont ID  
Sent By gjoyce Date 2000-05-24 Time 09:37 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***