| 2001-03-29 00:00:00 | SECOND CHECKLIST: |
| | 1-BEDROOM WINDOWS DON'T COMPLY WITH THE |
| | EGRESS REQUIREMENTS. SEC 1005.4.2 AND |
| | SEC. 1005.4.4 SBC 1997. |
| | 2-SURVEY DOESN'T MATCH FLOOR PLAN AND |
| | PLOT PLAN ON SHEET #2. |
| | -REVISE BUILDING DIMENSIONS, SETBACKS, |
| | DRIVEWAYS, BUILDING FOOTPRINT, ETC. |
| | 3-PROFESSIONAL ENGINEER OF RECORD TO |
| | DATE HIS DRAWINGS WHEN SEALING AND |
| | SIGNING DOCUMENTS FOR PUBLIC RECORDS |
| | AS REQUIRED BY CHAPTER 471 FL STATUTES |
| | 4-ROOF TRUSS DRAWINGS: |
| | -ALL TRUSS DRAWINGS TO BE REVIEWED BY |
| | THE PROFESSIONAL DESIGNER OF RECORD. |
| | -DESIGNER OF RECORD IS USING SBC 1997 |
| | DESIGN CRITERIA. TRUSSES ARE DESIGNED |
| | BASED ON ASCE 7-93. MIXING OF THE TWO |
| | CODES IS NOT ALLOWED. SEE SEC 1606.1.2 |
| | SBC 1997. REVISE AS REQUIRED. |
| | -CONNECTOR SPECIFIED FOR TRUSS T03 AT |
| | BEARING POINT #8 DOESN'T WORK. REVISE |
| | AS REQUIRED. SEE TRUSS PROFILE. |
| | -TRUSS ENGINEER TO DATE ALL DRAWINGS AT |
| | TIME OF SEALING THEM AS REQUIRED BY |
| | FLORIDA STATUTES, CHAPTER 471. |
| | SEE ALL GENERAL DETAILS. |
| | 5-PROVIDE CURRENT PRODUCT APPROVAL FOR: |
| | -AWNING WINDOWS (PRODUCT APPROVAL IS |
| | EXPIRED) |
| | -OCTAGON WINDOWS. |
| | -WINDOW MULLIONS |
| | 6-STORM PANELS: |
| | -PROVIDE KEY PLAN AND A COMPLETE |
| | INSTALLATION SCHEDULE (SEE SAMPLE). |
| | -CLEARLY INDICATE ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TYPE |
| | AND SPACING TO BE USED ACCORDING TO |
| | THE MEAN ROOF HEIGHT,DESIGN PRESSURES, |
| | PANEL SPAN, CONNECTION TYPE, EDGE |
| | DISTANCE AND STRUCTURE TO BE ATTACHED |
| | TO (MASONRY). |
| | -THERE ARE THREE DIFFERENT TYPES OF |
| | STORM SHUTTERS SUBMITTED (ROLL UP, |
| | ACCORDION AND STORM PANELS), CLARIFY |
| | WHICH ONE IS GOING TO BE USED AND |
| | PROVIDE THE KEY PLAN, INSTALLATION |
| | SCHEDULE AND ALL REQUIRED INFORMATION. |
| | 7-INFORMATION ON ROOF FRAMING PLAN ON |
| | SHEET #4 IS EXTREMELY LIGHT AND IS NOT |
| | SUITABLE FOR MICROFILMING FOR PUBLIC |
| | RECORDS. CORRECT AS REQUIRED. |
| | 8-OWES $827.34 FOR LOW VALUATION, RADON |
| | FEES AND INCREASE ON THE SQUARE |
| | FOOTAGE OF THE ADDITION. |
| | NOTE: SOME FEES MAY HAVE BEEN PAID |
| | FROM PREVIOUS CHECKLIST. PLEASE BRING |
| | COPIES OF THE PAID RECEIPTS TO |
| | VERIFY WHAT WAS PAID. |
| | 9-SPECIFY FIREBLOCKING ON WALL SECTION. |
| | SECTION 2305 SBC 1997. |
| | 10-SPECIFY SIZE OF VENTS FOR ROOF |
| | VENTILATION. SEC. 2309.7 SBC 1997. |
| | 11-PLANS WERE CHANGED FROM ORIGINAL |
| | SUBMITTAL. SEE ZONING COMMENTS |
| | ATTACHED. |