Plan Review Details - Permit 00051136
Plan Review Stops For Permit 00051136
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-08-08 Cont ID  
Sent By lmartine Date 2000-08-08 Time 16:40 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-03 Cont ID  
Sent By hpiskura Date 2000-07-03 Time 13:47 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-28 Cont ID  
Sent By dpalmer Date 2000-07-28 Time 06:29 Rev Time 0.00
Received By dpalmer Date 2000-07-28 Time 06:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-13 Cont ID  
Sent By dpalmer Date 2000-06-13 Time 20:23 Rev Time 0.00
Received By dpalmer Date 2000-06-13 Time 20:23 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING FOR
 NEW MAIN. MAINS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT.110-9/215-5
  
  
  
  
  
 3)NOTE: MUST BOND COLD WATER AT ADDITION
 PER 250-50 PLEASE SHOW ON RISER DIAGRAM.
  
 4)NOTE: PLEASE SHOW LOAD CALCULATIONS
 FOR SERVICE. ALL CONTINUOUS LOADS AT
 125%(LIGHTING) ETC. PLEASE SHOW LOAD
 FOR TRACK LIGHTING PER 220-12B, SQ FT
 PER 220.
  
 5)NOTE;PER 250-50 BLDG STEEL MUST BE
 BONDED AT ADDITION.
  
 6)NOTE:PLEASE PROVIDE DISTANCE FROM
 MAIN TO PANEL 'B' IN ADDITION. LENGTH
 OF CONDUCTORS.
  
 PLEASE SUBMIT ALL THE ABOVE INFOMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-08-01 Cont ID  
Sent By lmartine Date 2000-08-01 Time 11:23 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISOS,6/13/00
 SEE BACK OF APPLICATION,LM

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-06-08 Cont ID  
Sent By rturnque Date 2000-06-08 Time 14:04 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-25 Cont ID  
Sent By cthirben Date 2000-07-25 Time 10:40 Rev Time 1.00
Received By cthirben Date 2000-07-25 Time 10:40 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 REVIEW NOTES DATED 06.24.00 IS SUBMITTED
 ON PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-24 Cont ID  
Sent By cthirben Date 2000-06-24 Time 12:19 Rev Time 1.00
Received By cthirben Date 2000-06-24 Time 12:19 Sent To  
Notes
2001-01-08 00:00:00DENIED:******************************
 1. PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2..
 2. SPECIFY DUCT MATERIAL TO BE USED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-03-07 Cont ID  
Sent By jleech Date 2001-03-07 Time 17:55 Rev Time 0.75
Received By jleech Date 2001-03-07 Time 17:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-10 Cont ID  
Sent By tlarge Date 2000-08-10 Time 16:58 Rev Time 1.50
Received By tlarge Date 2000-08-10 Time 12:19 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 SUBMIT REVISED SANITARY RISER PRIOR TO
 PLBG.INSPECTION.SYSTEM SHALL COMPLY W/
 SPC SEC.921.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-09 Cont ID  
Sent By tlarge Date 2000-06-09 Time 18:25 Rev Time 1.00
Received By tlarge Date 2000-06-09 Time 18:24 Sent To  
Notes
2001-01-08 00:00:00NOTE ON PLANS THE AVERAGE DAILY
 ATTENDANCE OF STUDENTS UTILIZING THIS
 FACILITY FOR FIXTURE REQS.PER SPC TABLE
 407.
  
 A MIN.OF TWO TOILET ROOMSWILL BE REQD.
 PER SPC TABLE 407 OF SPC.
  
 NOTE MOUNTING HEIGHTS OF ALL HANDICAP
 FIXTURES AND APUTENANCES ON PLANS.(E.G.-
 T.P.DISPENSER,GRAB BARS,WATER CLOSET,
 CLEAR FLOOR SPACE UNDER LAV.,ETC.)COMPLY
 W/FACBC 1997 ED.SEE SHT.A-3.
  
 SHT.P-2.-OVER 2 FIXTURES SUPPLIED BY
 1/2" C.W.LINE PER COUNTYWIDE AMENDMENTS
 SEC.607.7.

Review Stop Z ZONING
Rev No 2 Status P Date 2000-08-10 Cont ID  
Sent By gjoyce Date 2000-08-10 Time 08:16 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2000-06-01 Cont ID  
Sent By hpiskura Date 2000-07-03 Time 13:47 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEED LEVEL 1 SITE PLAN REVIEW