Review Stop P PLUMBING
Rev No 2 Status P Date 2000-05-26 Cont ID  
Sent By tlarge Date 2000-05-26 Time 14:27 Rev Time 0.30
Received By tlarge Date 2000-05-26 Time 14:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-19 Cont ID  
Sent By tlarge Date 2000-05-19 Time 06:17 Rev Time 0.50
Received By tlarge Date 2000-05-19 Time 06:17 Sent To  
Notes
2001-01-08 00:00:00SUBMIT APPLICABLE SIZING CHART USED TO
 SIZE THE SYSTEM.SGC SEC.305.4.
  
 SUBMIT EHD NUMBER OF CSST TUBING FOR
 EACH SIZED BEING INSTALLED.SGC SEC.305.4
  
 SHOW PIPE CONNECTION TO METER,PIPE SIZE
 AND MATERIAL.SGC SEC.305.4.
  
 DISTANCE TO MOST REMOTE OUTLET SHALL BE
 SHOWN.SGC 305.4.
  
 SUBMIT DELIVERY PRESSURE TO SYSTEM.SGC
 305.4.
  
 INDICATE DISTANCE OF METER FROM HOUSE.
 COMPLY W/SGC 305.2.