Plan Review Details - Permit 00051083
Plan Review Stops For Permit 00051083
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-14 Cont ID  
Sent By dpalmer Date 2000-09-14 Time 12:50 Rev Time 0.00
Received By dpalmer Date 2000-09-14 Time 12:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-06-06 Cont ID  
Sent By dpalmer Date 2000-06-06 Time 18:08 Rev Time 0.00
Received By dpalmer Date 2000-06-06 Time 18:08 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO ***************
  
 1)NOTE:PLEASE SUBMIT LOAD CALCULATIONS
 FOR EXISTING SERVICE/HOUSE. PLEASE SHOW
 EXISTING SERVICE SIZE. PER 220-3-C-1 OF
 THE NEC.
  
 2)NOTE: PLEASE SUBMIT A PANEL SCHEDULE.
 ALSO PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) FOR RECEPT. MUST BE
 20AMP AND #12 PER 210-11-C-3
  
 3)NOTE: PLEASE SEE NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS OF NEW CONST-
 -RUCTION.
  
 4)NOTE:PLEASE NOTE THE MISSING OUTLET
 REQ`D FOR REAR OF DWELLING 210-52E
  
 PLEASE SUBMIT ALL THE ABOVE INFORMAITON
 FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT -
 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-06-07 Cont ID  
Sent By cthirben Date 2000-06-07 Time 12:34 Rev Time 0.20
Received By cthirben Date 2000-06-07 Time 12:32 Sent To  
Notes
2001-01-08 00:00:00****************NOTES ******************
 NO MECHANICAL OR A/C PLANS SUBMITTED FOR
 REVIEW. REQUIRES PERMIT FOR MECHANICAL.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-06-05 Cont ID  
Sent By tlarge Date 2000-06-05 Time 17:35 Rev Time 0.30
Received By tlarge Date 2000-06-05 Time 17:35 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2001-05-11 Cont ID  
Sent By jgomez Date 2001-05-11 Time 17:20 Rev Time 0.25
Received By jgomez Date 2001-05-11 Time 17:20 Sent To  
Notes
2001-05-11 00:00:00TRUSS DRAWINGS.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2001-04-18 Cont ID  
Sent By jgomez Date 2001-04-18 Time 18:34 Rev Time 1.00
Received By jgomez Date 2001-04-18 Time 18:34 Sent To  
Notes
2001-04-18 00:00:00TRUSS DRAWINGS CHECKLIST:
  
 1-ENGINEER OF RECORD TO REVIEW ALL TRUSS
 DRAWINGS PRIOR TO SUBMITTAL TO THIS
 OFFICE (USE THE REVIEW STAMP).
 2-TRUSS LAYOUT TO BE SIGNED, SEALED AND
 DATED BY THE TRUSS ENGINEER. ALSO,
 PROVIDE ENGINEER'S INFORMATION AS
 REQUESTED BY CHAPTER 471 OF FLORIDA
 STATUTES WHEN SUBMITTING DOCUMENTS FOR
 PUBLIC RECORDS.
 3-SIMPSON STRONG-TIE LETTER SUBMITTED IS
 TOO OLD AND NEED TO BE SIGNED, SEALED
 AND DATED. CHAPTER 471 FL. STATUTES.
 4-UPDATE ALL GENERAL DETAILS PROVIDED.
 SIGN,SEAL, DATE PER CHAPTER 471 FL. ST
 5-CLARIFY WHY THERE ARE GENERAL DETAILS
 COPIES WITH THE SEALS OF DIFFERENT
 ENGINEERS. CHAPTER 471 FL. STATUTES.
 6-ENGINEER OF RECORD DESIGNED BUILDING
 BASED ON SBC 1997 FOR 110MPH. TRUSSES
 ARE DESIGNED BASED ON ASCE 7-93 FOR
 110MPH. MIXING OF PROVISIONS FROM ASCE
 AND SBC SHALL NOT BE PERMITTED. SEE
 SEC. 1606.1.2.1 OF SBC 97.
 -ENGINEERED TRUSSES SHALL BE DESIGNED
 USING SBC 1997 AND SHALL STATE THIS
 SPECIFIC CODE EDITION.
 -CLARIFY WHY TRUSS GE1 WAS DESIGNED
 USING SBC WHILE THE OTHERS ARE ASCE.
 7-TRUSSES V30, V26, V22, HV18 AND HV14
 ARE DESIGNED TO BEAR ON 3 SUPPORTS.
 PROVIDE DETAIL OR SPECIFICATIONS
 SHOWING HOW THE LOAD IS TRANSFERED
 THRU THE MIDDLE SUPPORT IF THERE IS NO
 MIDDLE SUPPORT SHOWN ON ROOF PLAN.
 ALSO, SPECIFY CONNECTORS TO RESIST THE
 CALCULATED UPLIFT LOADS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-09-26 Cont ID  
Sent By jgomez Date 2000-09-26 Time 12:17 Rev Time 1.00
Received By jgomez Date 2000-09-26 Time 12:17 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-BEDROOM EGRESS WINDOWS TO HAVE 20" MIN
 CLEAR OPENING IN WIDTH, 24" MINIMUM
 CLEAR OPENING IN HEIGHT AND 5 SQUARE
 FEET MINIMUM CLEAR OPENING. SECTION
 1005.4 SBC 1997.
 2-STORM PANELS: CLEARLY INDICATE ON
 DRAWINGS WHICH ANCHOR AND SPACING IS
 GOING TO BE USED FOR THIS PROJECT FOR
 INSPECTOR'S INSPECTION.
 3-PROVIDE VENTILATION FOR FOR NEW
 BATHROOM AND EXISTING BATHROOM WHERE
 WINDOW WAS CLOSED.
 4-PROVIDE PRODUCT APPROVALS FOR:
 -EXTERIOR SWING DOOR (INCLUDE DRAWINGS)
 -ROOF SHINGLES FOR 110 MPH WIND LOAD.
 -SINGLE HUNG WINDOWS WITH COMPLETE AND
 LEGIBLE DRAWINGS.
 5-PROVIDE DENSITY LETTER AFTER SOIL IS
 COMPACTED.
 6-NEED TO APPLY FOR SEPARATE PERMITS FOR
 MECHANICAL, ELECTRICAL, PLUMBING AND
 ROOFING WORK. SUBCONTRACTORS DIDN'T
 APPLY FOR IT AT TIME OF BUILDING
 PERMIT APPLICATION.
  
  
  
  
  
  
 NOTES:
 -PROVIDE ALL REQUESTED INFORMATION PRIOR
 TO CONSTRUCTION OR INSTALLATION TO
 AVOID UNNECESSARY DELAYS.
 -IF YOU HAVE ANY QUESTIONS PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT 659-8096
 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-09-15 Cont ID  
Sent By jgomez Date 2000-09-13 Time 21:16 Rev Time 2.00
Received By jgomez Date 2000-09-13 Time 21:16 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 PLEASE, GET DRAWINGS STAMPED AND BRING
 PAID RECEIPT.
 2-PROVIDE EGRESS AT BEDROOM. SECTION
 1005.4.4 SBC 1997. WINDOWS SPECIFIED
 DON'T PROVIDE THE MINIMUM EGRESS SIZE.
 3-PROVIDE COPY OF NOTICE OF COMMENCEMNT.
 4-ADDITION IS GOING TO BE ADJACENT TO
 EXISTING GARAGE. AMOUNT OF OPENINGS
 ALLOWED ARE RESTRICTED BY TABLE 600 OF
 SBC 1997. PLEASE, REVISEDRAWINGS AS
 REQUIRED TO COMPLY WITH TABLE 600.
 5-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE (SEE ATTACHED SAMPLE) AND KEY
 PLAN SHOWING LOCATION OF OPENINGS TO
 BE PROTECTED.
 -STORM PANEL DRAWINGS: HIGHLIGHT
 SPECIFIC MOUNTING CONDITIONS AND
 ANCHOR TYPE AND SPACING TO BE USED.
 6-PROVIDE VENTILATION FOR BATHROOM.
 SECTION 1203.4.2 SBC 1997.
 -NOTE 1:SAME THING APPLIES TO EXISTING
 BEDROOM AND BATHROOM WHERE EXISTING
 WINDOWS ARE BLOCKED BY THE ADDITION.
 -NOTE 2: PROVIDE EGRESS WINDOW FOR
 EXISTING BEDROOM WHERE WINDOW IS BEING
 BLOCKED BY THE NEW ADDITION.
 EGRESS WINDOW SECTION 1005.4.4 SBC/97.
 7-PROVIDE PRODUCT APPROVALS FOR: SINGLE
 HUNG WINDOWS (INCLUDING COMPLETE AND
 LEGIBLE DRAWINGS),EXTERIOR SWING DOOR,
 ROOF SHINGLES FOR A WIND VELOCITY OF
 110 MPH.
 8-CONTRACTOR NEEDS TO UPDATE THE LICENSE
 AND INSURANCE.
  
  
  
 NOTE:
 -IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT 659-8096
 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-20 Cont ID  
Sent By jgomez Date 2000-06-20 Time 14:16 Rev Time 2.50
Received By jgomez Date 2000-06-20 Time 14:16 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 2-PROVIDE EGRESS AT BEDROOM. SEE SECTION
 1005.4 SBC 1997.
 3-PROVIDE COMPLETE BEAM AND LINTEL
 SCHEDULE WITH COMPLETE SPECS. ALSO,
 SPECIFY CONSTRUCTION OF WINDOW SILLS
 TO RECEIVE STORM PANELS.
 SECTION 104.2.2 CITY AMENDMENTS.
 4-NOTICE OF COMMENCEMENT NEEDS TO BE
 RECORDED WITH PALM BEACH COUNTY.
 5-PROVIDE SAFETY GLASS WHERE REQUIRED.
 SEE PLANS FOR COMMENTS. SECTION 2405.2
 SBC 1997.
 6-SEE PROVISO AND COMMENTS BY OTHER PLAN
 REVIEWERS.
 7-PROVIDE UPLIFT CALCULATIONS FOR ROOF
 TRUSSES. SEC 104.2.2 CITY AMENDMENTS.
 8-SPECIFY FIREBLOCKING WHERE REQUIRED.
 SECTION 2305 SBC 1997.
 9-ENGINEER TO CERTIFY THAT EXISTING ROOF
 TRUSSES AND CONNECTORS ARE ADEQUATE TO
 RECEIVE THE NEW ROOF LOADS AND
 REACTIONS. SEC 104.2.2 CITY AMENDMENTS
 10-PROVIDE CURRENT SIGNED, SEALED AND
 DATED SURVEY SHOWING THE ADDITION.
 11-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION,AS PER
 CITY SAMPLE ATTACHED, AND KEY PLAN.
 -HIGHLIGHT SPECIFIC MOUNTING CONDITIONS
 AND ANCHOR SPACING ACCORDING TO THE
 DESIGN PRESSURES, PANEL SPAN, EDGE
 DISTANCE AND STRUCTURE TO BE ATTACHED
 12-CLARIFY IF THIS ADDITION IS GOING TO
 BE AIR CONDITIONED. IF SO, PROVIDE
 THE REQUIRED ENERGY CALCULATIONS.
 -IF NOT AIR CONDITIONING IS INSTALLED,
 THEN PROVIDE ADEQUATE VENTILATION AS
 PER SECTION 1203.4.2 SBC 1997.
 -PROVIDE LIGHT AND VENTILATION FOR
 BEDROOM AS PER SECTION 1203.1.2 SBC/97
 -PROVIDE A/C DRAWINGS FOR REVIEW.
 13-PROVIDE PRODUCT APPROVALS FOR:
 AWNING WINDOWS, EXTERIOR SWING DOOR,
 SLIDING GLASS DOORS, ROOF SHINGLES FOR
 A WIND VELOCITY OF 110 MPH.
 14-CLARIFY WHAT TYPE OF WINDOWS ARE
 GOING TO BE USED IN THIS HOUSE. AWNING
 WINDOWS OR SINGLE HUNG WINDOWS.
 15-PROVIDE COMPLETE ENGINEERED TRUSS
 DRAWINGS REVIEWED BY THE ENGINEER OF
 RECORD OF THIS ADDITION.
 16-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM:
 -MEAN ROOF HEIGHT IS INCORRECT.
 MEAN ROOF HEIGHT IS TAKEN FROM FINISH
 GRADE TO THE AVERAGE POINT OF THE
 HIGHEST ROOF.
 -COMPLETE BASIC VELOCITY PRESSURE. SEE
 TABLE 1606.2A SBC 1997.
 17-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS. SEC 1606 SBC 1997.
 18-OWES $51.29FOR RADON FEES AND
 BUILDING VALUATION. THIS IS TO BE PAID
 TO THE CITY OF WEST PALM BEACH. SEE
 ATTACHED PAYMENT RECEIPT.
  
  
  
 NOTE:
 PLEASE RETURN REVIEWED SETS IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-23 Cont ID  
Sent By gjoyce Date 2000-05-23 Time 11:05 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***