| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-FLOOD ZONE "AO". NEED TO PROVIDE AN |
| | ELEVATION CERTIFICATE. |
| | 2-ENERGY CALCULATIONS: |
| | -REVISE CEILING AREA AS REQUIRED PER |
| | SECTION 604.1.A.1 OF FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILDING |
| | CONSTRUCTION, 1997 EDITION. |
| | 3-SEE COMMENTS ON PLANS REVISE/UPDATE |
| | AS REQUIRED FOR FUTURE SUBMITTALS. |
| | 4-COMPLETELY SPECIFY CEILING CONSTRUCT'N |
| | AT FRONT AND BACK PORCHES. INCLUDING |
| | FASTENERS TYPE AND SPACING. SECTION |
| | 2504 SBC 1997. |
| | 5-PROVIDE COMPLETE AND LEGIBLE PRODUCT |
| | APPROVALS FOR: GLASS BLOCK, SLIDING |
| | GLASS DOORS, ENTRY DOOR AND CIRCLE TOP |
| | WINDOWS. |
| | 6-STORM PANELS: |
| | -PROVIDE INSTALLATION SCHEDULE. PLEASE, |
| | USE CITY SAMPLE AND FILL IN ALL THE |
| | INFORMATION AS SHOWN ON SAMPLE TO |
| | ASSURE PROPER INSTALLATION. |
| | -MARK ANCHOR INSTALLATION SCHEDULE |
| | ACCORDING TO THE MEAN ROOF HEIGHT, |
| | DESIGN PRESSURES, EDGE DISTANCE, STORM |
| | SPAN, CONNECTION TYPE AND STRUCTURE TO |
| | BE ATTACHED TO. |
| | NOTE: BE AWARE THAT WINDOW SILLS ARE |
| | BE AWARE THAT WINDOW SILLS ARE MASONRY |
| | UNITS. THEREFORE, STRUCTURE TO RECEIVE |
| | STORM PANELS IS CONCRETE BLOCK NOT |
| | 3,000 PSI CONCRETE. |
| | 7-PROVIDE SOIL TEST REPORT AS PER SEC. |
| | 1804.2.7 OF CITY AMENDMENTS. |
| | 8-FOR FUTURE SUBMITTALS, PLEASE CLEARLY |
| | INDICATE THE STRUCTURAL DETAILS THAT |
| | ARE RELATED TO THE SPECIFIC HOUSE AND |
| | THE OPTION THAT IS GOING TO BE BUILT |
| | IN ORDER TO EXPEDITE THE REVIEW |
| | PROCESS. |