Plan Review Details - Permit 00051021
Plan Review Stops For Permit 00051021
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-06-12 Cont ID  
Sent By lmartine Date 2000-06-12 Time 16:23 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 BUILDINGCOMMENTS
 ---------- ---------
  
 1]SUBMIT TEST REPORTS FOR ALL EXTERIOR
 OPENINGS TO BE REPLACED.
 2]TABLE 1004 SBC REQUIRES ONE EXIT DOOR
 MINIMUM 32"CLEAR PER UNIT.
 3]PROVIDE THE DETAILS FOR ADA COMPLIANCE
 ACCORDING TO FAIR HOUSING ACT.
  
  
 REVIEWER:LUIS MARTINEZ
 561-659-8096#8456

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-05 Cont ID  
Sent By dpalmer Date 2000-06-05 Time 20:01 Rev Time 0.00
Received By dpalmer Date 2000-06-05 Time 20:01 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: YOU ARE SHOWING ON PANEL SCHED-
 -ULES GFI RECEPT. CIRCUIT? IS THIS THE
 REQ`D DEDICATED BATH RECEPT CIRCUIT?
 IF SO PLEASE LIST ON PANEL SCHEDULE AS
 BATH RECEPT. 210-11-C-3/215-5
  
 2)NOTE:PLEASE NOTE ON PANEL SCHEDULES
 FOR UNITS B AND E YOU ARE SHOWING TWO
 CIRCUITS,,,4 AND 6. ONE IS BEING SHOWN
 AS SMALL APPLIANCE AND THE OTHER REC.
 PLEASE INDICATE BOTH CIRCUITS AS SMALL
 APPLIANCE AS REQ`D BY 210-11-C-1
  
 3)NOTE: PLEASE SHOW ON PLANS ALL THE
 REQ`MENTS UNDER THE FAIR HOUSING ACT
 REG.24 CFR 100.205 CHAPTER 5
 ALL THE HEIGHT REQ`MENTS FOR DEVICES
 MUST BE SHOWN.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-06-14 Cont ID  
Sent By rturnque Date 2000-06-14 Time 10:47 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-06-13 Cont ID  
Sent By ndenmark Date 2000-06-13 Time 15:06 Rev Time 0.50
Received By ndenmark Date 2000-06-13 Time 15:06 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 MECHANICAL EQUIPMENT TO BE MOUNTED ON
 SOLID CONCRETE PADS MINIMUM 3" ABOVE
 FINISHED GRADE
 ENERGY EFFICIENCY CODE FOR FLORIDA REQ-
 UIRES DUCT IN ATTIC TO BE MINIMUM R-6

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-30 Cont ID  
Sent By tlarge Date 2000-05-30 Time 15:25 Rev Time 6.00
Received By tlarge Date 2000-05-30 Time 15:25 Sent To  
Notes
2001-01-08 00:00:00SUBMIT THE FOLLOWING INFORMATION FOR
 THE GAS INSTALLATION:
 1)SUBMIT A COPY OF/OR REFERENCE THE
 APPLICABLE GAS SIZING TABLE USED IN THE
 SIZING OF THE GAS SYSTEM.SGC 305.4.
  
 2)SHOW ALL CUT SECTIONS OF PIPE,TYPE OF
 PIPING MATERIAL,PIPE SIZES,TYPE OF GAS,
  
 3)DISTANCE TO MOST REMOTE OUTLET.
  
 4)DELIVERY PSI
  
 5)CALCULATIONS FOR COMBUSTION AIR PER
 NFPA 54 SEC.5.3.5 AND SGC SEC.402.4.
  
 6)DELIVERY PSI.
  
 7)TYPE LOCATION AND SIZE OF GAS VENTS.
  
 8)MANUF.SHEETS FOR ALL GAS EQUIPMENT.
  
 2)ONE MAIN VENT THRU ROOF IS REQD.PER
 SPC SEC.904.3.1.
  
 3)RISER S/1-WATER CLOSETS NOT PERMITTED
 ON WET VENTS PER COUNTYWIDE AMENDMENTS
 SEC.911.1.1.
  
 4)RISER S/1-DRY VENTS ARE NOT PERMITTED
 PER SPC SEC.906.2.1.
  
 5)RISER S/2-ONE MAIN VENT THRU ROOF IS
 REQD.PER SPC SEC.904.3.1.
  
 6)SHT.P100-GAS LINE FOR UNIT 1634 SHOWS
 A 3/4"LINE SUPPLYING A 1 1/2" LINE.
 COMPLY W/SGC SEC.305.4.
  
 7)SIZE THE WATER RISERS.
  
 8)WATER HEATERS SHALL BE READILY ACESS-
 IBLE PER SPC SEC.501.7.
  
 9)THE APPLICABLE PLUMBING CODE IS THE
 1994 EDITION,NOT THE 1995.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved