Plan Review Details - Permit 00051008
Plan Review Stops For Permit 00051008
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-12-13 Cont ID  
Sent By lmartine Date 2000-12-13 Time 09:41 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-08-24 Cont ID  
Sent By lmartine Date 2000-08-24 Time 09:58 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLANS ARE READY ISSUANCE,
 PAY CITY RADON AND COUNTY IMPACT FEES,
 HAVE ZONING APPROVAL,

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-11 Cont ID  
Sent By lmartine Date 2000-08-11 Time 16:25 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:002ND REVIEW[BUILDING]
  
 SHEET RF-01 DETAIL "A",PARAPET SHALL BE
 OF NON COMBUSTIBLE MATERIAL[TABLE 600
 AND 1517.6].
  
 SUBMIT SPECIFICATION FOR EXTERIOR WALL,
 [3HR AND 2HR] REQUIRED BY TABLE 600 SBC.
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 659-8096#8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-22 Cont ID  
Sent By lmartine Date 2000-07-22 Time 13:32 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00*************BUILDING*************
  
 1]ALL EXTERIOR WALLS SHALL COMPLY WITH
 TABLE 600,SBC,REQUIREMENTS.SUBMIT
 APPROVED TESTED ASSEMBLY'S FOR 3HR WALL
 INCLUDE MIN. 18" PARAPET. NO OPENINGS
 ARE PERMITED WERE SPERATIONS OF LESS
 THAN 3' EXIST BETWEEN PROPERTY LINES OR
 OTHER BUILDINGS.
 2]SUBMIT COMPLETE CONSTRUCTION DETAILS
 FOR CONNECTION TO EXISTING BUILDING.
 3]PROVIDE ROOF DRAINAGE PLAN.
 4]A 2ND APPROVED EXIT IS REQUIRED,1004.2
 SBC.
 5]SUBMIT INTERIOR WALL SECTION.
 6]ADDITIONAL FEES OWED,COUNTY IMPACT FEE
 AND CITY RADON FEE.
  
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 659-8096#8456

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-10 Cont ID  
Sent By dpalmer Date 2000-08-10 Time 15:05 Rev Time 0.00
Received By dpalmer Date 2000-08-10 Time 15:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-05 Cont ID  
Sent By dpalmer Date 2000-07-05 Time 21:23 Rev Time 0.00
Received By dpalmer Date 2000-07-05 Time 21:23 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO ****************
  
 1)NOTE: YOU HAVE SUBMITTED THE AIC RAT-
 -ING FOR BRANCH BREAKERS. HOW-EVER THE
 AIC RATING FOR MAIN IS REQ`D ALSO. MUST
 BE RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9.
  
 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS/ CORRELATE WITH PANEL SCHE-
 -DULE.
  
 3)NOTE PLEASE SUBMIT LOAD CALCULATION
 WITH ALL CONTINUOUS LOADS FIGURED AT
 125% (LIGHTING).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-10 Cont ID  
Sent By mcarsill Date 2000-08-10 Time 09:49 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-18 Cont ID  
Sent By mcarsill Date 2000-07-11 Time 13:59 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) PROVIDE EMERGENCY LIGHTING AND EXIT
 SIGNS.
 2) PROVIDE AT LEAST TWO MEANS OF EGRESS
 FROM STORAGE BUILDING.
 3) ACCORDING TO PERSONS, THE BUILDING
 IS TO BE USED FOR STORAGE OR ORNAMENTAL
 METAL. THEY WERE EXPLAINED ABOUT EXITING
 REQUIREMENTS AND THAT OVERHEAD DOORS
 CANNOT BE USED FOR EXITING.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-07-14 Cont ID  
Sent By cthirben Date 2000-07-14 Time 11:47 Rev Time 0.00
Received By cthirben Date 2000-07-14 Time 15:03 Sent To  
Notes
2001-01-08 00:00:00PROVISO*********************************
 PROVIDE VENTILATION TO THE BATHROOM AS
 PER 1997 SMC 503.3.1..

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-07-11 Cont ID  
Sent By tlarge Date 2000-07-11 Time 08:29 Rev Time 0.33
Received By tlarge Date 2000-07-11 Time 08:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-12-13 Cont ID  
Sent By gjoyce Date 2000-05-22 Time 16:32 Rev Time 0.25
Received By nleiva Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS LEVEL 1 SITE PLAN REVIEW