Plan Review Details - Permit 00050965
Plan Review Stops For Permit 00050965
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-06-26 Cont ID  
Sent By fknapp Date 2000-06-26 Time 09:51 Rev Time 1.00
Received By fknapp Date 2000-06-26 Time 09:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-27 Cont ID  
Sent By dpalmer Date 2000-07-27 Time 06:50 Rev Time 0.00
Received By dpalmer Date 2000-07-27 Time 06:49 Sent To  
Notes
2001-01-08 00:00:00***********PROVISO *******************
  
 1)NOTE: PLEASE SEE FIRST SET OF NOTES!
 PLEASE COMPLETE LOAD CALCULATIONS!!!!
 PLEASE SHOW THE CONTINUOUS LOADS AT 125%
  
 2)NOTE: PLEASE SEE RISER, STILL NEED TO
 SHOW WIRE SIZE FROM PANEL 'H' TO XFORMER
 I KNOW THE WIRE SIZE IS SHOWN ON PANEL
 SCHEDULE.
  
 3)NOTE: ALSO SIZE GROUND FOR TRANSFORMER
 PER 250-66. GROUNDING ELECTRODE.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-18 Cont ID  
Sent By dpalmer Date 2000-05-18 Time 21:24 Rev Time 0.00
Received By dpalmer Date 2000-05-18 Time 21:24 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: NEED TO PROVIDE MORE DETAIL ON
 LOAD CALCULATIONS. GIVE BREAK DOWN AND
 COMPLETE WHAT IS BEING SHOWN. PLEASE
 SHOW ALL LOADS THAT ARE CONTINUOUS AT
 125%. LIGHTING?
  
 2)NOTE: PLEASE SHOW WIRE SIZE FROM
 PANEL 'H' TO TRANSFORMER.
  
 3)NOTE: PLEASE PROVIDE AIC RATINGS FOR
 ALL EQUIPMENT, MAINS, PANELS, BREAKERS.
 PER 110-9 AND 215-5
  
 4)NOTE: PLEASE SHOW GROUNDING FOR TRANS-
 -FORMER.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-08 Cont ID  
Sent By mcarsill Date 2000-08-08 Time 08:47 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-06-06 Cont ID  
Sent By rturnque Date 2000-06-06 Time 11:20 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE FIRE SPRINKLER DRAWINGS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-05-24 Cont ID  
Sent By ndenmark Date 2000-05-24 Time 07:48 Rev Time 0.33
Received By ndenmark Date 2000-05-24 Time 07:48 Sent To  
Notes
2001-01-08 00:00:00NOTE:
 NO COMBUSTIBLES ALLOWED IN RETURN AIR
 PLENUM

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-07-29 Cont ID  
Sent By tlarge Date 2000-07-29 Time 10:00 Rev Time 0.50
Received By tlarge Date 2000-07-29 Time 09:58 Sent To  
Notes
2001-01-08 00:00:00PROVISO:SINK IN BREAK ROOM SHALL COMPLY
 W/FACBC SEC.4.24.1.-4.24.7.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-20 Cont ID  
Sent By pschmitz Date 2000-05-20 Time 12:24 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW DENIED
 (1) BREAK RM SINK TO COMPLY WITH FACBC
 SEC 4.24.1-4.24.7 THIS AREA NOT DEFINED
 AS WORK AREA,PER DCA.34"FF TO COUNTER
 TOP.
 END OF COMMENTS