Plan Review Details - Permit 00050908
Plan Review Stops For Permit 00050908
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-02-08 Cont ID  
Sent By hpiskura Date 2001-02-08 Time 13:45 Rev Time 0.00
Received By hpiskura Date 2001-01-26 Time 15:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-01-12 Cont ID  
Sent By hpiskura Date 2001-01-12 Time 14:40 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-12-20 Cont ID  
Sent By hpiskura Date 2000-12-20 Time 09:55 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00LETTER W/APPLICATION SEE ALSO COMPANION
 REVIEW 00050907

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-11-22 Cont ID  
Sent By hpiskura Date 2000-11-22 Time 11:27 Rev Time 0.00
Received By hpiskura Date 2000-11-22 Time 09:04 Sent To  
Notes
2001-01-08 00:00:00LETTER ATTACHED TO APPLICATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-10 Cont ID  
Sent By hpiskura Date 2000-10-10 Time 14:56 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-10-03 Cont ID  
Sent By dpalmer Date 2000-10-03 Time 10:34 Rev Time 0.00
Received By dpalmer Date 2000-10-03 Time 10:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-06 Cont ID  
Sent By dpalmer Date 2000-06-06 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2000-06-06 Time 08:45 Sent To  
Notes
2001-01-08 00:00:00*************UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATINGS
 OOR THE 600 AMP DISC AND 700 AMP BREAKER
 ENCLOUSURE. 110-9/215-5 NEEDS TO BE ON
 PLANS SUBMITTED.
  
 2)NOTE: PLEASE NOTE THE OUTLET SPACING
 REQ`MENT PER LOCAL CODE. 210-50
 EVERY 20` OF UNENCUMBERED WALL SPACE.
  
  
 3)NOTE:PLEASE SEE SHEET E-5 YOU SHOW
 ON MAIN THE "SAMBA" BEING SERVED BY
 TRKR #3 ? PLEASE CLARIFY.
  
 4)NOTE: PLEASE SHOW WHAT/OR WHERE
 "CHEFS PANEL" IS/ OR WHERE IT IS GOING
 TO BE.
  
 5)NOTE: PLEASE NOTE AND CHECK THE REQ`-
 -MENTS OF ART; 450-21-B FORTRANSFORMER
 ROOM? OVER 112 1/2 KVA. ALSO EXCEPT. #1
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASECALL 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-15 Cont ID  
Sent By mcarsill Date 2000-09-15 Time 09:52 Rev Time 0.00
Received By mcarsill Date 2000-09-15 Time 09:52 Sent To  
Notes
2001-01-08 00:00:001) CNAVAS AWNINGS ARE TO BE FIRE
 RETARDANT.
 2) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 3) PROVIDE EMERGENCY LIGHTING EQUIPMENT
 IN RESTROOMS.
 4) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON PLANS. CUT SHEETS REQUIRED
 ON ALL DEVICES SHOWN ON PLANS.
 5) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE HOOD, DUCT AND EXTINGUISHING SYSTEM.
 A SEPARATE PERMIT IS REQUIRED.
 6) INTERIOR FINISH IN EXITS SHALL BE
 CLASS A OR B.
 7) NO FIRE SPRINKLERS SHOWN IN OUTDOOR
 SEATING, SECTION 130.
 8) PROVIDE SEATING FOR AT LEAST TWO
 HANDICAPPED PERSONS, PER NFPA 101,
 THE LIFE SAFETY CODE, 1985 EDITION.
 9) CEILING MOUNTED DRAPERY, 301 IS TO
 BE FURTHER EXPLAINED. THIS MATERIAL
 IF APPROVED IS TO BE FIRE RETARDENT
 MATERIAL. SINCE IT IS PLANNED NEAR
 AN EXIT IT SHALL MEET CLASS A OR B
 FLAMESPREAD REQUIREMENTS.
 10) PROVIDE FIRE EXTINGUISHERS.
 APPROVED PROVISO:

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-05-18 Cont ID  
Sent By rturnque Date 2000-05-18 Time 14:20 Rev Time 0.45
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-09-21 Cont ID  
Sent By ndenmark Date 2000-09-21 Time 14:15 Rev Time 1.00
Received By ndenmark Date 2000-09-21 Time 14:15 Sent To  
Notes
2001-01-08 00:00:00REVISION SHOWING REQUIRED SEPARATION FOR
 HOODS AND DUCT ASREQUESTED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-09-06 Cont ID  
Sent By ndenmark Date 2000-09-06 Time 10:51 Rev Time 0.25
Received By ndenmark Date 2000-09-06 Time 10:51 Sent To  
Notes
2001-01-08 00:00:00FAILED: NO MECHANICAL PLANS SUBMITTED
 FOR REVIEW W/ THIS RESUB 9/6/00

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-09 Cont ID  
Sent By ndenmark Date 2000-06-09 Time 14:18 Rev Time 1.00
Received By ndenmark Date 2000-06-09 Time 14:18 Sent To  
Notes
2001-01-08 00:00:00***********DENIED***********************
  
 1) AIR BALANCE AND AIR CONDITIONING PLAN
 OK
 2) 1997 SMC 505.9.1 VERTICAL AND HORIZ-
 ONTAL DUCTS LOCATED IN BUILDINGS 2
 OR MORE STORIES SHALL BE ENCLOSED IN A
 CONTINUOUS ENCLOSURE FROM THE CEILING
 ABOVE THE HOOD TO OF THROUGH THE ROOF.
 505.9.2 REQUIRES THE ENCLOSURE TO BE
 USED EXCLUSIVELY TO ENCLOSE A SINGLE
 GREASE EXHAUST SYSTEM AND SHALL BE USED
 FOR NO OTHER PURPOSE.
 NOTE: SEPARATE PERMITS REQUIRED FOR HOOD
 WALK IN COOLER/FREEZER, AND FIRE SUPPRES
 SION FOR HOODS

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-12-19 Cont ID  
Sent By jleech Date 2000-12-19 Time 11:12 Rev Time 1.00
Received By jleech Date 2000-12-19 Time P1:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-11-16 Cont ID  
Sent By jleech Date 2000-11-16 Time 13:12 Rev Time 2.00
Received By jleech Date 2000-11-16 Time 13:12 Sent To  
Notes
2001-01-08 00:00:001.MEN'S H.C. STALL DOESNOT HAVE REQUIRED
 TURNING RADIUS.
 2.URINALS; MESSUREMENTS MUST BE INSIDE
 TO INSIDE NOT CENTER OF PARTITION.
 BOTH MESSUREMENTS ARE MINIMUM
 EXCEPTABLE WIDTH.
 3.VACUUM RELIFE VALVE ON WATER HEATER
 TO COMPLY TO MANUF. SPECIFICATIONS.
 4.PAGE P-3 WATER HEATER RISER DIAGRAM
 CHANGE FLOOR DRAIN TO FLOOR SINK.
 5.AUTOMATIC SHUTOFF VALVES SHALL HAVE
 A SHUTOFF VALVE UP STREAM AND UNIONS
 SO AUTOMATIC VALVE CAN BE REPLACED
 IF REQUIRED.
 6.GAS SHUTOFF VALVES FOR EACH PIECE OF
 EQUIPMENT SHALL BE ACCESSIBLE WITHOUT
 MOVING EQUIPMENT.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-09-14 Cont ID  
Sent By tlarge Date 2000-09-14 Time 18:35 Rev Time 4.50
Received By tlarge Date 2000-09-14 Time 18:35 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT CALCULATIONS FOR COMBUSTION AIR
 PER SGC SEC.402.4,402.4.4.
  
 2)SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP.
 EQUIPMENT SHALL BE LISTEDPER SGC SEC.
 402.1.
  
 3)SUBMIT DETAILS ON VENT FOR WATER HEAT-
 ER.COMPLY W/SGC SEC.607,608,AND VENTING
 TABLES IN SGC CHAPT.6.
  
 4)CONTROLS FOR GAS EQUIPMENT SHALL
 COMPLY W/NFPA 54 SEC.5.5.4.
  
 5)SHUT-OFF VALVES ARE REQD.ON THE BRANCH
 LINES OF THE WATER SUPPLY SYSTEM PER SPC
 SEC.610.4.2.
  
 6)RELIEF LINES FROM WATER HEATER SHALL
 DRAIN TO FLOOR SINK NOT FLOOR DRAIN PER
 SPC SEC.807.1.3.
  
 7)CONTACT R.COMPO W/CITY OF WEST PALM
 BEACH FOR APPROVAL OF THE GREASE TRAPS.
 SUBMIT COPY OF APPROVAL.COUNTYWIDE
 AMENDMENTS TO SPC SEC.101.4.7.
  
 8)CLEAR FLOOR SPACE FOR WATER CLOSET IN
 WOMEN'S RESTROOM SHALL COMPLY W/FACBC
 SEC.4.17.3.& FIG.30.
  
 9)SPECS.ON SHT.P1 CALL OUT A FLOOR
 MOUNTED WATER CLOSET AND THE PLANS SHOW
 A WALL MOUNTED WATER CLOSET.IF FLOOR
 MOUNTED THE H.C.TOILET STALL IN THE
 MEN'S RESTROOM DOESN'T COMPLY W/FACBC
 SEC.4.17.3 AND FIG.#30.
  
 10)MAX.TEMPERATURE OF WATER DISCHARGED
 TO THE SANITARY SYSTEM SHALL BE 140
 DEGREES PER SPC 717.8
  
 11)STANDARD URINAL REQS.A MIN. OF 24"
 CLEARANCE PER SPC SEC.403.4.
  
 12)WATER CLOSETS ARE NOT PERMITTED ON
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1.
  
 13)OVER 2 FIXTURES SUPPLIED BY 1/2"C.W.
 SEE SHT.P5.COUNTYWIDE AMENDMENTS TO SPC
 SEC.607.7.
  
 14)SIZE THE GAS LINES TO THE EQUIPMENT.
 COMPLY W/SGC TABLE 305.4(A).
  
 15)AUTOMATIC SHUT-OFF VALVES SHALL BE
 ACCESSIBLE AND LOCATED BELOW CEILING.
 SGC 310.1.
  
 16)THE APPLICABLE GAS CODE IN EFFECT IN
 THE CITY OF WPB IS THE 1997 STANDARD GAS
 CODE,NOT THE 1994.
  
 17)DISHWASHER SHALL NOT DISCHARGE TO THE
 GREASY WASTE SYSTEM PER LOCAL ORDINANCE.
 DISCHARGE SHALL BE TO SANITARY SYSTEM.
  
 18.)VACUUM RELIEF VALVES ARE REQD,ON ALL
 BOTTOM FED WATER HEATERS AND SHALL BE
 INSTALLED PER MANUF.RECOMMENDATIONS.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.TIMOTHY LARGE.
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-28 Cont ID  
Sent By tlarge Date 2000-08-28 Time 14:51 Rev Time 1.00
Received By tlarge Date 2000-08-28 Time 13:43 Sent To  
Notes
2001-01-08 00:00:001)CLEAR FLOOR SPACE FOR WATER CLOSETS IN
 THE ACCESSIBLE STALLS IN THE MALE AND
 FEMALE RESTROOMS SHALL COMPLY W/FACBC
 SECS.4.17.3,FIG.30.(IF WATER CLOSETS ARE
 WALL MOUNTED,56"WILL SUFFICE.THERE IS A
 PROBLEM W/CLEAR FLOOR SPACE FOR THE W.C.
 IN THE WOMEN'S R.R.)
  
 2)WHERE ARE THE M,E,P DRAWINGS? THEY ARE
 NOT WITH THE ARCHITECTURAL PLANS.A
 COMPLETE REVIEW CANNOT BE PERFORMED.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 3)COMPLY W/ALL PREVIOUS COMMENTS DATED
 5/16/00.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-27 Cont ID  
Sent By tlarge Date 2000-05-27 Time 09:59 Rev Time 1.75
Received By tlarge Date 2000-05-27 Time 09:42 Sent To  
Notes
2001-01-08 00:00:00SHT.A0-THE APPLICABLE PLUMBING CODE IS
 THE 1994 EDITION OF THE STANDARD PLBG.
 CODE.COUNTYWIDE AMENDMENT TO SPC 101.1
 AND FLA.STATUTE.
  
 PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 SUBMIT SQ.FT.AREA OF HABITABLE FLOOR
 SPACE FOR DETERMINATION OF MIN.FIXTURE
 REQS.SEE SPC SEC.407.1.3.FOR ALLOWED
 DEDUCTIBLE AREAS.
  
 WALLS IN TOILET ROOMS SHALL BE
 NONABSORBENT TO A HEIGHT OF 4' PER SBC
 SEC.1204.2.
  
 SUBMIT A COMPLETE GAS DRAWING SHOWING
 ALL GAS PIPING AS A WHOLE ALONG W/THE
 FOLLOWING ITEMS:
 A COPY OF OR REFERENCE TO THE SPECIFIC
 GAS SIZING TABLE USED TO DESIGN THE
 SYSTEM.
 2)SHOW DIMENSIONS OF ALL CUT SECTIONS OF
 PIPE,TYPE OF PIPING MATERIAL,ALL PIPE
 SIZES,TYPE OF GAS,ETC.
 3)DISTANCE TO MOST REMOTE OUTLET.
 4)DELIVERY PSI AT METER.
 5)CALCULATIONS FOR COMBUSTION AIR.
 6)TYPE,LOCATION,SIZE AND TERMINATION PT.
 OF GAS VENTS.
 7)MANUF.SHEETS FOR ALL GAS EQUIP.
 (EQUIPMENT SHALL BE LISTED.SGC SEC.402.1
  
 SUBMIT MORE INFORMATION/ISOMETRIC DRAW-
 ING ON AIR INTAKE AND EXHAUST PIPING FOR
 WATER HEATERS.(SEE SHT.P-3.)
  
 CONTROLS FOR GAS EQUIPMENT SHALL COMPLY
 W/NFPA 54 SEC.5.5.4.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 610.4.1.,610.4.2.
  
 FLOOR SINKS SHALL BE USED IN KITCHEN
 AREA IN LIEU OF FLOOR DRAINS PER SPC
 SEC.807.1.3.
  
 INDIRECT WASTES SHALL COMPLY W/SPC SEC.
 805.1,805.2.
  
 WASTES FROM BAR SINK AREAS SHALL DIS-
 CHARGE TO GREASE INTERCEPTOR PER SPC
 SEC.804.1.,1004.4.
  
 CONTACT R.COMPO W/CITY OF WEST PALM
 UTILITIES FOR CHANGES TO THE GREASY
 WASTE SYSTEM(SUBMIT APPROVAL FROM
 UTILITIES FOR EXISTING GREASE SYSTEM.
  
 CLEAR FLOOR SPACE FOR WATER CLOSET IN
 MEN'S RESTROOM SHALL COMPLY W/FACBC SEC.
 4.16.2 AND FIGURE 28.
  
 SIZE OF VENTS SHALL COMPLY W/SPC SEC.
 920.2.(SEE URINALS AND VENT FOR 6"DRAIN)
  
 URINAL IS LOCATED IN LINE OF SIGHT FROM
 VESTIBULE AREA.COMPLY W/SPC SEC.404.3.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-02-13 Cont ID  
Sent By sjohnson Date 2001-02-13 Time 08:18 Rev Time 0.00
Received By sjohnson Date   Time   Sent To  
Notes
***NONE***