| Plan Review Stops For Permit 00050908 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-02-08 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-02-08 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2001-01-26 |
Time |
15:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-01-12 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-01-12 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-12-20 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-12-20 |
Time |
09:55 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | LETTER W/APPLICATION SEE ALSO COMPANION | | | REVIEW 00050907 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-11-22 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-11-22 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2000-11-22 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | LETTER ATTACHED TO APPLICATION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-10-10 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-10-10 |
Time |
14:56 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-10-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-03 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-03 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-06-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-06 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-06-06 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT THE AIC RATINGS | | | OOR THE 600 AMP DISC AND 700 AMP BREAKER | | | ENCLOUSURE. 110-9/215-5 NEEDS TO BE ON | | | PLANS SUBMITTED. | | | | | | 2)NOTE: PLEASE NOTE THE OUTLET SPACING | | | REQ`MENT PER LOCAL CODE. 210-50 | | | EVERY 20` OF UNENCUMBERED WALL SPACE. | | | | | | | | | 3)NOTE:PLEASE SEE SHEET E-5 YOU SHOW | | | ON MAIN THE "SAMBA" BEING SERVED BY | | | TRKR #3 ? PLEASE CLARIFY. | | | | | | 4)NOTE: PLEASE SHOW WHAT/OR WHERE | | | "CHEFS PANEL" IS/ OR WHERE IT IS GOING | | | TO BE. | | | | | | 5)NOTE: PLEASE NOTE AND CHECK THE REQ`- | | | -MENTS OF ART; 450-21-B FORTRANSFORMER | | | ROOM? OVER 112 1/2 KVA. ALSO EXCEPT. #1 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASECALL 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-09-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-15 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-15 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) CNAVAS AWNINGS ARE TO BE FIRE | | | RETARDANT. | | | 2) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 3) PROVIDE EMERGENCY LIGHTING EQUIPMENT | | | IN RESTROOMS. | | | 4) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT | | | SHOWN ON PLANS. CUT SHEETS REQUIRED | | | ON ALL DEVICES SHOWN ON PLANS. | | | 5) PROVIDE COMPLETE SHOP DRAWINGS FOR | | | THE HOOD, DUCT AND EXTINGUISHING SYSTEM. | | | A SEPARATE PERMIT IS REQUIRED. | | | 6) INTERIOR FINISH IN EXITS SHALL BE | | | CLASS A OR B. | | | 7) NO FIRE SPRINKLERS SHOWN IN OUTDOOR | | | SEATING, SECTION 130. | | | 8) PROVIDE SEATING FOR AT LEAST TWO | | | HANDICAPPED PERSONS, PER NFPA 101, | | | THE LIFE SAFETY CODE, 1985 EDITION. | | | 9) CEILING MOUNTED DRAPERY, 301 IS TO | | | BE FURTHER EXPLAINED. THIS MATERIAL | | | IF APPROVED IS TO BE FIRE RETARDENT | | | MATERIAL. SINCE IT IS PLANNED NEAR | | | AN EXIT IT SHALL MEET CLASS A OR B | | | FLAMESPREAD REQUIREMENTS. | | | 10) PROVIDE FIRE EXTINGUISHERS. | | | APPROVED PROVISO: |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-05-18 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-05-18 |
Time |
14:20 |
Rev Time |
0.45 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-21 |
Time |
14:15 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-09-21 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION SHOWING REQUIRED SEPARATION FOR | | | HOODS AND DUCT ASREQUESTED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-09-06 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-06 |
Time |
10:51 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-09-06 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | FAILED: NO MECHANICAL PLANS SUBMITTED | | | FOR REVIEW W/ THIS RESUB 9/6/00 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-09 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-06-09 |
Time |
14:18 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-06-09 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***********DENIED*********************** | | | | | | 1) AIR BALANCE AND AIR CONDITIONING PLAN | | | OK | | | 2) 1997 SMC 505.9.1 VERTICAL AND HORIZ- | | | ONTAL DUCTS LOCATED IN BUILDINGS 2 | | | OR MORE STORIES SHALL BE ENCLOSED IN A | | | CONTINUOUS ENCLOSURE FROM THE CEILING | | | ABOVE THE HOOD TO OF THROUGH THE ROOF. | | | 505.9.2 REQUIRES THE ENCLOSURE TO BE | | | USED EXCLUSIVELY TO ENCLOSE A SINGLE | | | GREASE EXHAUST SYSTEM AND SHALL BE USED | | | FOR NO OTHER PURPOSE. | | | NOTE: SEPARATE PERMITS REQUIRED FOR HOOD | | | WALK IN COOLER/FREEZER, AND FIRE SUPPRES | | | SION FOR HOODS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2000-12-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-19 |
Time |
11:12 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2000-12-19 |
Time |
P1:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2000-11-16 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-16 |
Time |
13:12 |
Rev Time |
2.00 |
| Received By |
jleech |
Date |
2000-11-16 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.MEN'S H.C. STALL DOESNOT HAVE REQUIRED | | | TURNING RADIUS. | | | 2.URINALS; MESSUREMENTS MUST BE INSIDE | | | TO INSIDE NOT CENTER OF PARTITION. | | | BOTH MESSUREMENTS ARE MINIMUM | | | EXCEPTABLE WIDTH. | | | 3.VACUUM RELIFE VALVE ON WATER HEATER | | | TO COMPLY TO MANUF. SPECIFICATIONS. | | | 4.PAGE P-3 WATER HEATER RISER DIAGRAM | | | CHANGE FLOOR DRAIN TO FLOOR SINK. | | | 5.AUTOMATIC SHUTOFF VALVES SHALL HAVE | | | A SHUTOFF VALVE UP STREAM AND UNIONS | | | SO AUTOMATIC VALVE CAN BE REPLACED | | | IF REQUIRED. | | | 6.GAS SHUTOFF VALVES FOR EACH PIECE OF | | | EQUIPMENT SHALL BE ACCESSIBLE WITHOUT | | | MOVING EQUIPMENT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-09-14 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-14 |
Time |
18:35 |
Rev Time |
4.50 |
| Received By |
tlarge |
Date |
2000-09-14 |
Time |
18:35 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SUBMIT CALCULATIONS FOR COMBUSTION AIR | | | PER SGC SEC.402.4,402.4.4. | | | | | | 2)SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP. | | | EQUIPMENT SHALL BE LISTEDPER SGC SEC. | | | 402.1. | | | | | | 3)SUBMIT DETAILS ON VENT FOR WATER HEAT- | | | ER.COMPLY W/SGC SEC.607,608,AND VENTING | | | TABLES IN SGC CHAPT.6. | | | | | | 4)CONTROLS FOR GAS EQUIPMENT SHALL | | | COMPLY W/NFPA 54 SEC.5.5.4. | | | | | | 5)SHUT-OFF VALVES ARE REQD.ON THE BRANCH | | | LINES OF THE WATER SUPPLY SYSTEM PER SPC | | | SEC.610.4.2. | | | | | | 6)RELIEF LINES FROM WATER HEATER SHALL | | | DRAIN TO FLOOR SINK NOT FLOOR DRAIN PER | | | SPC SEC.807.1.3. | | | | | | 7)CONTACT R.COMPO W/CITY OF WEST PALM | | | BEACH FOR APPROVAL OF THE GREASE TRAPS. | | | SUBMIT COPY OF APPROVAL.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.101.4.7. | | | | | | 8)CLEAR FLOOR SPACE FOR WATER CLOSET IN | | | WOMEN'S RESTROOM SHALL COMPLY W/FACBC | | | SEC.4.17.3.& FIG.30. | | | | | | 9)SPECS.ON SHT.P1 CALL OUT A FLOOR | | | MOUNTED WATER CLOSET AND THE PLANS SHOW | | | A WALL MOUNTED WATER CLOSET.IF FLOOR | | | MOUNTED THE H.C.TOILET STALL IN THE | | | MEN'S RESTROOM DOESN'T COMPLY W/FACBC | | | SEC.4.17.3 AND FIG.#30. | | | | | | 10)MAX.TEMPERATURE OF WATER DISCHARGED | | | TO THE SANITARY SYSTEM SHALL BE 140 | | | DEGREES PER SPC 717.8 | | | | | | 11)STANDARD URINAL REQS.A MIN. OF 24" | | | CLEARANCE PER SPC SEC.403.4. | | | | | | 12)WATER CLOSETS ARE NOT PERMITTED ON | | | WET VENTS PER COUNTYWIDE AMENDMENTS TO | | | SPC SEC.911.1.1. | | | | | | 13)OVER 2 FIXTURES SUPPLIED BY 1/2"C.W. | | | SEE SHT.P5.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.607.7. | | | | | | 14)SIZE THE GAS LINES TO THE EQUIPMENT. | | | COMPLY W/SGC TABLE 305.4(A). | | | | | | 15)AUTOMATIC SHUT-OFF VALVES SHALL BE | | | ACCESSIBLE AND LOCATED BELOW CEILING. | | | SGC 310.1. | | | | | | 16)THE APPLICABLE GAS CODE IN EFFECT IN | | | THE CITY OF WPB IS THE 1997 STANDARD GAS | | | CODE,NOT THE 1994. | | | | | | 17)DISHWASHER SHALL NOT DISCHARGE TO THE | | | GREASY WASTE SYSTEM PER LOCAL ORDINANCE. | | | DISCHARGE SHALL BE TO SANITARY SYSTEM. | | | | | | 18.)VACUUM RELIEF VALVES ARE REQD,ON ALL | | | BOTTOM FED WATER HEATERS AND SHALL BE | | | INSTALLED PER MANUF.RECOMMENDATIONS. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS.TIMOTHY LARGE. | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-08-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-28 |
Time |
14:51 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
2000-08-28 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)CLEAR FLOOR SPACE FOR WATER CLOSETS IN | | | THE ACCESSIBLE STALLS IN THE MALE AND | | | FEMALE RESTROOMS SHALL COMPLY W/FACBC | | | SECS.4.17.3,FIG.30.(IF WATER CLOSETS ARE | | | WALL MOUNTED,56"WILL SUFFICE.THERE IS A | | | PROBLEM W/CLEAR FLOOR SPACE FOR THE W.C. | | | IN THE WOMEN'S R.R.) | | | | | | 2)WHERE ARE THE M,E,P DRAWINGS? THEY ARE | | | NOT WITH THE ARCHITECTURAL PLANS.A | | | COMPLETE REVIEW CANNOT BE PERFORMED. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | 3)COMPLY W/ALL PREVIOUS COMMENTS DATED | | | 5/16/00. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-05-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-05-27 |
Time |
09:59 |
Rev Time |
1.75 |
| Received By |
tlarge |
Date |
2000-05-27 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHT.A0-THE APPLICABLE PLUMBING CODE IS | | | THE 1994 EDITION OF THE STANDARD PLBG. | | | CODE.COUNTYWIDE AMENDMENT TO SPC 101.1 | | | AND FLA.STATUTE. | | | | | | PLANS SHALL BE ROUTED TO DEPT.OF | | | BUSINESS REGULATION FOR REVIEW AND | | | APPROVAL.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.101.4.7. | | | | | | SUBMIT SQ.FT.AREA OF HABITABLE FLOOR | | | SPACE FOR DETERMINATION OF MIN.FIXTURE | | | REQS.SEE SPC SEC.407.1.3.FOR ALLOWED | | | DEDUCTIBLE AREAS. | | | | | | WALLS IN TOILET ROOMS SHALL BE | | | NONABSORBENT TO A HEIGHT OF 4' PER SBC | | | SEC.1204.2. | | | | | | SUBMIT A COMPLETE GAS DRAWING SHOWING | | | ALL GAS PIPING AS A WHOLE ALONG W/THE | | | FOLLOWING ITEMS: | | | A COPY OF OR REFERENCE TO THE SPECIFIC | | | GAS SIZING TABLE USED TO DESIGN THE | | | SYSTEM. | | | 2)SHOW DIMENSIONS OF ALL CUT SECTIONS OF | | | PIPE,TYPE OF PIPING MATERIAL,ALL PIPE | | | SIZES,TYPE OF GAS,ETC. | | | 3)DISTANCE TO MOST REMOTE OUTLET. | | | 4)DELIVERY PSI AT METER. | | | 5)CALCULATIONS FOR COMBUSTION AIR. | | | 6)TYPE,LOCATION,SIZE AND TERMINATION PT. | | | OF GAS VENTS. | | | 7)MANUF.SHEETS FOR ALL GAS EQUIP. | | | (EQUIPMENT SHALL BE LISTED.SGC SEC.402.1 | | | | | | SUBMIT MORE INFORMATION/ISOMETRIC DRAW- | | | ING ON AIR INTAKE AND EXHAUST PIPING FOR | | | WATER HEATERS.(SEE SHT.P-3.) | | | | | | CONTROLS FOR GAS EQUIPMENT SHALL COMPLY | | | W/NFPA 54 SEC.5.5.4. | | | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | | 610.4.1.,610.4.2. | | | | | | FLOOR SINKS SHALL BE USED IN KITCHEN | | | AREA IN LIEU OF FLOOR DRAINS PER SPC | | | SEC.807.1.3. | | | | | | INDIRECT WASTES SHALL COMPLY W/SPC SEC. | | | 805.1,805.2. | | | | | | WASTES FROM BAR SINK AREAS SHALL DIS- | | | CHARGE TO GREASE INTERCEPTOR PER SPC | | | SEC.804.1.,1004.4. | | | | | | CONTACT R.COMPO W/CITY OF WEST PALM | | | UTILITIES FOR CHANGES TO THE GREASY | | | WASTE SYSTEM(SUBMIT APPROVAL FROM | | | UTILITIES FOR EXISTING GREASE SYSTEM. | | | | | | CLEAR FLOOR SPACE FOR WATER CLOSET IN | | | MEN'S RESTROOM SHALL COMPLY W/FACBC SEC. | | | 4.16.2 AND FIGURE 28. | | | | | | SIZE OF VENTS SHALL COMPLY W/SPC SEC. | | | 920.2.(SEE URINALS AND VENT FOR 6"DRAIN) | | | | | | URINAL IS LOCATED IN LINE OF SIGHT FROM | | | VESTIBULE AREA.COMPLY W/SPC SEC.404.3. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-02-13 |
|
|
Cont ID |
|
| Sent By |
sjohnson |
Date |
2001-02-13 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
sjohnson |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|