Plan Review Details - Permit 00050892
Plan Review Stops For Permit 00050892
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-06-27 Cont ID  
Sent By hpiskura Date 2000-06-27 Time 10:33 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00LETTER ATTACHED TOPLANS

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-06-06 Cont ID  
Sent By rturnque Date 2000-06-06 Time 10:45 Rev Time 0.50
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00DEAD END CORRIDORS SHALL NOT EXCEED 20'.
 PROVIDE 1 HOUR PROTECTION SURROUNDING
 STAIR ENCLOSURE.
 PROVIDE EXIT LIGHT AND EMERGENCY LIGHT
 ILLUMINATION.
 PROVIDE STAIR TREAD AND RISER DETAILS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-26 Cont ID  
Sent By tlarge Date 2000-05-26 Time 17:57 Rev Time 0.75
Received By tlarge Date 2000-05-26 Time 17:57 Sent To  
Notes
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD BASED ON HABITABLE
 FLOOR SPACE PER SPC 407.1.3.COMPLY W/SPC
 TABLE 407 FOR MINIMUM REQD.SANITARY
 FACILITIES.
  
 SINK IN EMPLOYEE LOUNGE SHALL BE
 ACCESSIBLE PER FACBC SEC.4.24.1.-4.24.7.
  
 SHOWER SHALL BE ACCESSIBLE PER FACBC
 SEC.4.1.2(6).
  
 A DRINKING FOUNTAIN IS REQD.PER TABLE
 407 OF SPC.FOUNTAIN SHALL COMPLY W/
 FACBC SEC.4.1.3.(10)(A).PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 INDICATE WALL FINISH IN TOILET ROOM PER
 SBC 1204.2.
  
 SHT.A-9-WATER CLOSET SHALL BE 18" FROM
 WALL,NOT 20" AS SHOWN.SEE FIGURE 28 OF
 FACBC.
  
 CLEARLY SHOW SCUPPER SIZE.COMPLY W/SPC
 SEC.1109.1,1109.2,1109.3.
  
 SUBMIT COMPLETE SANITARY,STORM,AND WATER
 ISOMETRICS FOR REVIEW.SPC 104.2.1.
 SHOW SQ.FOOTAGE DRAINED BY EACH ROOF
 DRAIN.
  
 SUBMIT CIVIL DRAWINGS FOR ANY NEW SITE
 UTILITIES TO BE INSTALLED.

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***