Plan Review Details - Permit 00050848
Plan Review Stops For Permit 00050848
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-03-07 Cont ID  
Sent By jwitmer Date 2001-03-07 Time 15:19 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-12-20 Cont ID  
Sent By jwitmer Date 2000-12-20 Time 11:49 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING PLAN REVIEW:
 1). S.B.C.1606.2.6.2. COMPONENTS &
 CLADDING. 1606.3.1 ROOF DECKS.
 ALL WALLS AND ROOF FRAMING INCLUDING
 CLADDING AND CONNECTIONS OF THESE
 ELEMENTS. THERE IS NO INFORMATION ON HOW
 THE 2X6 FRAMING MEMBERS ARE ATTACHED TO
 THE EXISTING ROOF AND FRAMING MEMBERS.
 ADMIN. CODE 104.2.2 ADDITIONAL INFO. ON
 THE ALUM. LOUVERED SCREEN WALL,ANCHORAGE
 AND WIND LOAD DATA SHOULD BE INCORPARA-
 TED INTO THE ANCHORAGE OF THE 2X6 DECK
 SYSTEM.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-06-01 Cont ID  
Sent By hpiskura Date 2000-06-01 Time 10:23 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2001-02-06 Cont ID  
Sent By dpalmer Date 2001-02-06 Time 15:34 Rev Time 0.00
Received By dpalmer Date 2001-02-06 Time 15:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-01-02 Cont ID  
Sent By dpalmer Date 2001-01-02 Time 09:39 Rev Time 0.00
Received By dpalmer Date 2001-01-02 Time 09:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-11-16 Cont ID  
Sent By dpalmer Date 2000-11-16 Time 19:20 Rev Time 0.00
Received By dpalmer Date 2000-11-16 Time 19:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-29 Cont ID  
Sent By dpalmer Date 2000-08-29 Time 18:46 Rev Time 0.00
Received By dpalmer Date 2000-08-29 Time 18:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-08-15 Cont ID  
Sent By dpalmer Date 2000-08-15 Time 19:40 Rev Time 0.00
Received By dpalmer Date 2000-08-15 Time 19:40 Sent To  
Notes
2001-01-08 00:00:00****************************************
  
 1)NOTE: PLEASE NOTE THAT THE EXTERIOR
 LIGHTING ON BLDG. 'B' CAN NOT BE FED
 FROM THE HOUSE PANEL ON BLDG. "A"
 THE IS A SEPARATE BLDGAND MAY NOT
 HAVE POWER FROM OTHER SERVICE. IF A FIRE
 IN BLDG. "B" OCCURRED AND FIRE DEPT WAS
 TO TURN POWER OFF FOR BLDG"B". THE LIGHT
 -S WOULD STILL BE HOT.
 A SEPARATE HOUSE PANEL MAY BE INSTALLED
 AT BLDG."B".
  
 PLEASE ADDRESS THE ABOVE NOTES AND SUB-
 -MIT FOR REVIEW. THE PLANS WOULD HAVE
 PASSED WITH A PROVISO BUT WERE COMING
 BACK FOR PLUMB NOTES.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 CITY OF WEST PALM BEACH
 659-8096 EXT8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-30 Cont ID  
Sent By dpalmer Date 2000-05-30 Time 18:51 Rev Time 0.00
Received By dpalmer Date 2000-05-30 Time 18:51 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS TO CORRELATE WITH PANEL
 SCHEDULES.
  
 2)NOTE: PLEASEINCLUDE THE RISER DIA-
 -GRAM FOR BLDG. 'B'. PLEASE SHOW MAIN/
 DISC,GROUNDING,ETC. 215-5 AIC RATING FOR
 MAIN PER 110-9
  
 3)NOTE:PLEASE REMOVE COMMENT ON RISER
 DIAGRAM FOR BLDG. 'A' THAT SHOWS PANEL#7
 THIS IS TO BE ON SEPARATE RISER DIAGRAM.
  
 4)NOTE: PLEASE SEE SIZING FOR GROUNDING
 ELECTRODE CONDUCTOR PER 250-66
  
 5)NOTE: PLEASE SHOW THE HOUSE PANEL AND
 METER FOR BLDG. 'A'.ON RISER DIAGRAM FOR
 BLDG.'B'. SERVICES MUST BE BONDED.
  
 6)NOTE: PLEASE SHOW THE REQ`D GFI RECEPT
 FOR CU ON BLDG.'B'.
  
 7)NOTE: OUTSIDE LIGHTING FOR BLDG 'B'
 SHOWS GOING TO PANEL VIA TC? SHOW PANEL
 FEED FOR LIGHTING.
  
 8)NOTE:SHOW ALL OUTSIDE LIGHTING FOR BLD
 'A' BRANCH CIRCUIT #`S
  
 9)NOTE:PLEASE PLACE TWO NOTES ON PLANS,,
 ONE FOR CLEARENCES FOR A/C CU`S PER ART;
 110-26 AND SECOND NOTE ON RISER DIAGRAM
 FOR ART; 230-2-E IDENTIFICATION OF
 SERVICE MAINS.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL. 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-12-14 Cont ID  
Sent By mcarsill Date 2000-12-14 Time 10:03 Rev Time 0.00
Received By mcarsill Date 2000-12-14 Time 10:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-01 Cont ID  
Sent By mcarsill Date 2000-09-01 Time 14:01 Rev Time 0.00
Received By mcarsill Date 2000-09-01 Time 14:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-05-18 Cont ID  
Sent By rturnque Date 2000-05-18 Time 09:39 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-03-07 Cont ID  
Sent By jwitmer Date 2001-03-07 Time 15:19 Rev Time 0.15
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-07 00:00:00MECH APPROVED NCD 3/7/01

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2001-01-04 Cont ID  
Sent By ndenmark Date 2001-01-04 Time 08:27 Rev Time 0.33
Received By ndenmark Date 2001-01-04 Time 08:27 Sent To  
Notes
2001-01-08 00:00:00REFERENCE DRAWINGS SEE SEALED MECH
 DRAWINGS W/ MECH PERMIT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2000-09-05 Cont ID  
Sent By cthirben Date 2000-08-01 Time 11:30 Rev Time 1.00
Received By ndenmark Date 2000-08-01 Time 11:30 Sent To  
Notes
2001-01-08 00:00:00MECHANICAL SUBCONTRACTOR TO SUBMIT
 ENGINEERED DRAWINGS SHOWING A/C INSTALL
 INCLUDING DUCT SIZES, CFM, EQUIPMENT
 SIZING, OUTSIDE AIR CALCULATIONS AND
 AIR BALANCE INFORMATION. NO MECHANICAL P
 PERMIT TO BE ISSUED PRIOR TO SUBMISSION
 OF THIS INFORMATION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-07-31 Cont ID  
Sent By cthirben Date 2000-07-31 Time 12:33 Rev Time 1.00
Received By cthirben Date 2000-07-31 Time 12:32 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 REQUIRED INFORMATION AS PREVIOUS REVIEW
 AS DATED 07.31.00....

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-05-20 Cont ID  
Sent By cthirben Date 2000-05-20 Time 16:50 Rev Time 0.00
Received By cthirben Date 2000-07-31 Time 12:56 Sent To  
Notes
2001-01-08 00:00:00DENIED**********************************
 1. NEEDS MORE INFO ON A/C UNITS.
 2. DUCTS, GRILLES, CFM VALUE, TYPE OF
 DUCT AND SIZES.
 3. INDICATE SMOKE DETECTOR IN THE RETURN
 AIR DUCT IF REQUIRED.
 4. EXHAUST FANS REQUIRED IN BATHROOM &
 SHOW THE SIZE AND MODEL INFO.
 5. SHOW CONDENSATE LINES TO THE OUTSIDE.
 6. RETURN AIR GRILLE & SIZE TO BE SHOWN.

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-02-01 Cont ID  
Sent By jleech Date 2001-02-01 Time 16:43 Rev Time 0.75
Received By jleech Date 2001-02-01 Time 16:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-09-06 Cont ID  
Sent By tlarge Date 2000-09-06 Time 12:30 Rev Time 0.33
Received By tlarge Date 2000-09-06 Time 12:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-08-31 Cont ID  
Sent By tlarge Date 2000-08-31 Time 16:38 Rev Time 0.75
Received By tlarge Date 2000-08-31 Time 16:38 Sent To  
Notes
2001-01-08 00:00:001)DRINKING FOUNTAINS SHALL COMPLY W/
 FACBC SEC.4.1.3.(10)(A).PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING AND STOOPING.
  
 2)PAN DRAINS ARE REQUIRED FOR THE HEATER
 PANS.TERMINATION OF DRAINS SHALL
 COMPLY W/SPC SEC.507.8.3.MIN.SIZE OF PAN
 DRAIN SHALL BE MIN.1".SPC 507.8.2.
  
 3)AN ADDITIONAL LAVATORY IS REQD.IN THE
 WOMEN'S TOILET ROOM PER SPC TABLE 407.
 SEE SPACES #1,#7.
  
 4)A MIN.OF 29" IS REQD.UNDER THE H.C.
 LAVS.FACBC SEC.4.19.2.SEE SHT.TI-A3.
  
 5)WATER CLOSETS AND LAVS.IN UNITS #4 & 5
 ARE NOT PROPERLY VENTED.SPC SEC.901.2,
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-06 Cont ID  
Sent By tlarge Date 2000-08-06 Time 08:00 Rev Time 1.25
Received By tlarge Date 2000-08-06 Time 06:22 Sent To  
Notes
2001-01-08 00:00:001)DRINKING FOUNTAINS SHALL COMPLY WITH
 FACBC SEC.4.1.3.(10)(A).PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 2)WATER HEATERS CANNOT BE LOCATED IN
 CLEAR FLOOR SPACE FOR WATER CLOSET.
 FACBC SEC.4.2.3.,FIG.#28.
  
 3)AN ADDITIONAL LAVATORY IS REQD.IN THE
 WOMEN'S TOILET ROOM PER SPC TABLE 407.
 SEE SPACES #1,7.
  
 4)A MIN.OF 29"IS REQD.UNDER H.C.LAV.PER
 FACBC SEC.4.19.2.
  
 5)SPACES #4 & 5-WATER CLOSETS,DRINKING
 FOUNTAINS AND LAVATORIES NOT PROPERLY
 VENTED.COMPLY W/SPC SEC.901.2,913.1,
 913.1.2.& SPC TABLE 714.2.
  
 6)TOILET ROOM IN SPACE #7 NOT SHOWN ON
 SANITARY RISER.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 7)NOT MORE THAN 2 FIXTURES SHALL BE
 SUPPLIED BY 1/2" C.W.PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.607.7.MIN.SUPPLY
 TO EWH SHALL BE 3/4".SHOW DRINKING
 FOUNTAINS ON WATER RISERS.
  
 8)WATER HEATERS SHALL BE EQUIPPED W/HEAT
 TRAPS PER FLA.ENERGY CODE.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-20 Cont ID  
Sent By pschmitz Date 2000-05-20 Time 11:05 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW DENIED
 (1)TENANT SPACES#1,#2 COMPLY WITH SPC-94
 TAB 407 & SEC 407.1.3,FOOT NOTE 6.
 SEPERATE MALE,FEMALE FACILITIES REQIIRED
 (2) ISOMETRIC OF HOT & COLD WATER PIPING
 LOCATION OF ALL WATER HEATERS. SEC 104.2
 (3) SHOW LOCATION OF BACK FLOW PREVENTER
 SEC 104.2
 (4) WATER SUPPLY CONTROL TO EACH TENANT
 SPACE SHALL HAVE A SEPERATE SHUT OFF.
 SEC 610.
 (5) DRINKING FOUNTAINS REQUIRED IN EACH
 UNIT,TAB 407.
 END OF COMMENTS