Plan Review Details - Permit 00050756
Plan Review Stops For Permit 00050756
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-06-12 Cont ID  
Sent By dpalmer Date 2000-06-12 Time 15:03 Rev Time 0.00
Received By dpalmer Date 2000-06-12 Time 15:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-18 Cont ID  
Sent By dpalmer Date 2000-05-18 Time 19:19 Rev Time 0.00
Received By dpalmer Date 2000-05-18 Time 19:18 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATINGS OF
 THE MAIN AND BRKRS. AS REQ`D BY 215-5
 AND 110-9. AIC RATINGS CAN BE FIGURED
 FROM FAULT CURRENT CALCULATIONS.
  
 2)NOTE: UPSTAIRS OUTLET SPACING TO MEET
 CODE. 210-52 AND ALL OUTLET SPACING TO
 BE BROUGHT UP TO CODE. MORE THAN 50%
 OF THE ELECTRICAL WORK IS BEING DONE.
  
 3)NOTE: AS REQ`D BY 210-8-A-6 ALL OUTLET
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED. PLEASE SHOW ON PLANS.
  
 4)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AND ON
 EACH LEVEL OF THE DWELLING.THEY ALL MUST
 BE WIRED INLINEAND 120V W/BATT BACK
 UP.
  
  
 5)NOTE PLEASE SHOW THE EQUIPMENT GROUND-
 ING CONDUCTORS REQ`D FOR CONDUITS TO A/C
 UNITS.
  
 6)NOTE; PLEASE INCLUDE COLD WATER PIPE
 AS PART OF THE GROUNDING ELECTRODE SYS-E
 -TEM. 250-50
  
 7)NOTE: AS REQ`D BY 210-11-C-3 PLEASE
 SHOW THE REQ`D DEDICATED BATH(S)CIRCUITS
 MUST BE #12 AND 20 AMPS.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-06-14 Cont ID  
Sent By cthirben Date 2000-06-14 Time 12:46 Rev Time 1.00
Received By cthirben Date 2000-06-14 Time 12:43 Sent To  
Notes
2001-01-08 00:00:00PROVISO*********************************
 INDICATE EXHAUST FANS IN BATHROOMS, THE
 SIZE AND LOCATION
 CONCRETE SLAB LOCATION AND CONDENSATE
 LINES SIZE AND LOCATION
 DRYER VENT SIZE AND LOCATION TO BE
 PROVIDED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-06-13 Cont ID  
Sent By cthirben Date 2000-06-13 Time 15:46 Rev Time 1.00
Received By cthirben Date 2000-06-13 Time 15:46 Sent To  
Notes
2001-01-08 00:00:00DENIED
 AHU'S TOO SMALL FOR SUPPLY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-05-19 Cont ID  
Sent By cthirben Date 2000-05-19 Time 11:45 Rev Time 0.00
Received By cthirben Date 2000-05-19 Time 11:48 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
 NO MECHANICAL PLANS SUBBITED FOR REVIEW.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-05-19 Cont ID  
Sent By tlarge Date 2000-05-19 Time 09:12 Rev Time 0.65
Received By tlarge Date 2000-05-19 Time 09:12 Sent To  
Notes
2001-01-08 00:00:00PROVISO:GAS WATER HEATER SHALL COMPLY W/
 SGC SEC.402.7 AND BE PROTECTED FROM
 PHYSICAL DAMAGE.GAS DRAWING SHALL BE
 SUBMITTED PRIOR TO INSPECTION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-06-14 Cont ID  
Sent By lsmith Date 2000-06-14 Time 14:47 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER TONY MARCELLO 6/13/2000

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-17 Cont ID  
Sent By gjoyce Date 2000-05-17 Time 13:14 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***