| 2001-01-08 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE:NEED TO SHOW THE REQ`D DEDICATED |
| | BATH(S) CIRCUIT(S) ON PANLE SCHEDULE. |
| | 210-11-C-3/ 215-5 |
| | |
| | 2)NOTE: PLEASE INCLUDE THE BLDG.STEEL |
| | AS PART OF THE GROUNDING ELECTRODE |
| | AS REQ`D BY 250-50 |
| | |
| | 3)NOTE: PLEASE CORRECT THE WIRE SIZES |
| | FOR THE SERVICE CONDUCTORS. SIZE PER |
| | 310-16.YOU SHOW #1,NEEDS TO BE INCREASED |
| | |
| | |
| | 4)NOTE;PLEASE PROVIDE THE AIC RATING FOR |
| | THE EQUIPMENT MAINS. MAINS TO BE RATED |
| | FOR THE AVAILABLE FAULT CURRENT. 110-9 |
| | |
| | 5)NOTE:PLEASE NOTE YOU SHOW THE LIGHTING |
| | IN THE CLOSETS AS (PC)`S PULL CHIANS? |
| | SEE ART 410-8 FOR CLEARENCEREQ`MENTS |
| | PLEASE CHANGE LIGHTING SHOWN ON PLANS. |
| | |
| | 6)NOTE:PLEASE NOTE THAT THE GUARDRAIL |
| | SHOWN ON SECOND FLOOR GUEST SUITE IS |
| | CONSIDERED WALL SPACE. OUTLET SPACING |
| | PER 210-52 MUST BE MET. FLOOR BOXES? ETC |
| | |
| | 7)NOTE: NO DOORSARE BEING SHOWN ON |
| | ANY OF THE BEDROOMS?/BATHS? AND ALSO |
| | FROM UPSTAIRS TO DOWNSTAIRS? PLEASE GIVE |
| | MORE DETAIL FOR ANY INTERIOR DOORS. |
| | SMOKE DETECTORS ARE REQ`D INSIDE AND |
| | OUTSIDE ALL SLEEPING ROOMS AND ON EACH |
| | FLOOR LEVEL AT COMMON AREA. NFPA-72 |
| | 2-2.1.1.1. NEED TO SEE WHAT DOORS IF ANY |
| | ARE BEING INSTALLED. |
| | |
| | 8)NOTE: YOU ARE ALSO SHOWING TWO A/C |
| | UNITS? ARE THEY BOTH EXISTING? IF NOT |
| | PLEASE SHOW ONPLANS THE NEW A/C`S AND |
| | SHOW THE REQ`DE A/C DISCS AND REQ`D |
| | 210 RECEPT. 440-11 AND 210-63 |
| | |
| | 9)NOTE: YOU ARE SHOWING A TELEPHONE |
| | IN THE MASTER SUITE, IS THERE GOING TO |
| | BE ONE IN THE GUEST SUITE?OR IN KITCHEN? |
| | NEED SHOW ANY CABLE TV OUTLETS THAT ARE |
| | GOING TO BE INSTALLED,IF ANY. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL 659-8096 EXT 8372 |