Plan Review Details - Permit 00050701
Plan Review Stops For Permit 00050701
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-26 Cont ID  
Sent By dpalmer Date 2000-07-26 Time 20:08 Rev Time 0.00
Received By dpalmer Date 2000-07-26 Time 20:08 Sent To  
Notes
2001-01-08 00:00:00****************** PROVISO *************
  
 1)NOTE: STILL NEED TO ADDRESS SOME OF
 THE ORIGINAL NOTES.
  
 2)NOTE: ALL RECEOTS IN BATH ARE TO BE
 GFI/GFI PROTECTED PLEASE SHOW. 210-8-A-1
  
 3)NOTE: PLEASE 210-52 FOR OUTLET SPACING
  
 4)NOTE: PLEASE SEE THE REQ`MENTS OF ART
 110-26 OF NEC FOR PANEL IN KITCHEN.
  
 5)NOTE: PLEASE SEE NOTE 8 OF FIRST NOTES
  
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-22 Cont ID  
Sent By dpalmer Date 2000-05-22 Time 10:17 Rev Time 0.00
Received By dpalmer Date 2000-05-19 Time 16:41 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE:NEED TO SHOW THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) ON PANLE SCHEDULE.
 210-11-C-3/ 215-5
  
 2)NOTE: PLEASE INCLUDE THE BLDG.STEEL
 AS PART OF THE GROUNDING ELECTRODE
 AS REQ`D BY 250-50
  
 3)NOTE: PLEASE CORRECT THE WIRE SIZES
 FOR THE SERVICE CONDUCTORS. SIZE PER
 310-16.YOU SHOW #1,NEEDS TO BE INCREASED
  
  
 4)NOTE;PLEASE PROVIDE THE AIC RATING FOR
 THE EQUIPMENT MAINS. MAINS TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT. 110-9
  
 5)NOTE:PLEASE NOTE YOU SHOW THE LIGHTING
 IN THE CLOSETS AS (PC)`S PULL CHIANS?
 SEE ART 410-8 FOR CLEARENCEREQ`MENTS
 PLEASE CHANGE LIGHTING SHOWN ON PLANS.
  
 6)NOTE:PLEASE NOTE THAT THE GUARDRAIL
 SHOWN ON SECOND FLOOR GUEST SUITE IS
 CONSIDERED WALL SPACE. OUTLET SPACING
 PER 210-52 MUST BE MET. FLOOR BOXES? ETC
  
 7)NOTE: NO DOORSARE BEING SHOWN ON
 ANY OF THE BEDROOMS?/BATHS? AND ALSO
 FROM UPSTAIRS TO DOWNSTAIRS? PLEASE GIVE
 MORE DETAIL FOR ANY INTERIOR DOORS.
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS AND ON EACH
 FLOOR LEVEL AT COMMON AREA. NFPA-72
 2-2.1.1.1. NEED TO SEE WHAT DOORS IF ANY
 ARE BEING INSTALLED.
  
 8)NOTE: YOU ARE ALSO SHOWING TWO A/C
 UNITS? ARE THEY BOTH EXISTING? IF NOT
 PLEASE SHOW ONPLANS THE NEW A/C`S AND
 SHOW THE REQ`DE A/C DISCS AND REQ`D
 210 RECEPT. 440-11 AND 210-63
  
 9)NOTE: YOU ARE SHOWING A TELEPHONE
 IN THE MASTER SUITE, IS THERE GOING TO
 BE ONE IN THE GUEST SUITE?OR IN KITCHEN?
 NEED SHOW ANY CABLE TV OUTLETS THAT ARE
 GOING TO BE INSTALLED,IF ANY.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-07-25 Cont ID  
Sent By cthirben Date 2000-07-25 Time 07:44 Rev Time 0.00
Received By cthirben Date 2000-07-25 Time 07:44 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 NO MECHANICAL PLANS SUBMITTED FOR REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-06-02 Cont ID  
Sent By cthirben Date 2000-06-02 Time 13:47 Rev Time 0.00
Received By cthirben Date 2000-06-02 Time 13:53 Sent To  
Notes
2001-01-08 00:00:00*****************NOTES******************
 MECHANICAL PERMIT REQUIRED FOR A/C
 INSTALLATION AND EXHAUST FANS .
 SUBMIT A/C-MECHANICAL PLANS WITH PERMIT
 APPLICATION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-07-28 Cont ID  
Sent By tlarge Date 2000-07-28 Time 17:59 Rev Time 0.30
Received By tlarge Date 2000-07-28 Time 17:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-01 Cont ID  
Sent By tlarge Date 2000-06-01 Time 18:14 Rev Time 0.65
Received By tlarge Date 2000-06-01 Time 18:14 Sent To  
Notes
2001-01-08 00:00:00DRY VENTS NOT PERMITTED PER SPC SEC.
 906.2.1.
  
 WET VENTS SHALL RECEIVE THE DISCHARGE
 FROM FIXTURE DRAINS ONLY.WATER CLOSETS
 NOT PERMITTED ON WET VENTS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1.
  
 VEG.SINK REQUIRES VENT PER SPC SEC.901.2
  
 SANITARY RISER DOESN'T MATCH 1ST.FLOOR.
 RISER SHOWS BATHROOM ON 1ST.FLOOR AND
 FLOOR PLAN DOESN'T.CLARIFY.COUNTYWIDE
 AMENDMENTS TO SPC SE.104.2.1.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-08-02 Cont ID  
Sent By fknapp Date 2000-08-02 Time 14:36 Rev Time 4.00
Received By fknapp Date 2000-08-02 Time 13:56 Sent To  
Notes
2001-01-08 00:00:00 
  
 ************BUILDING PROVISO************
  
 SBC 104.2.2
  
 1)PROVIDE COMPLETE DETAILS OF GUARDRAILS
 WITH CONNECTIONS TO BUILDING.
  
 2)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR FRENCH
 DOORS THAT ARE BEING USED.
  
 PLEASE SUBMIT PRIOR TO INSTALLATION.
  
 3)PROVIDE MECHANICAL DRAWINGS WITH
 PERMIT APPLICATION.
  
 4)PROVIDE PRODUCT APPROVAL FOR STORM
 PANELS WITH INSTALLATION SCHEDULE AND
 KEY PLAN WITH SPECIFIC ANCHORS TO BE
 USED UNDER SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-17 Cont ID  
Sent By gjoyce Date 2000-05-17 Time 10:00 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***