Plan Review Details - Permit 00050635
Plan Review Stops For Permit 00050635
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-05-11 Cont ID  
Sent By cthirben Date 2000-05-11 Time 12:34 Rev Time 1.00
Received By cthirben Date 2000-05-11 Time 12:27 Sent To  
Notes
2001-01-08 00:00:00***************************PROVISO******
 1. SMOKE DETECTOR,AUDIBLE ALARM AND
 STROBE TO BE TIED IN TO ALARM SYSTEM.
 FOR AHU #1 PER NFPA 90A 4.4.4.3.
 2. AHU-2 AUTOMAATIC SHUTDOWN REQUIRED
 PER SMC 1997 406.2, DUE TO AN EGRESS.