Plan Review Details - Permit 00050562
Plan Review Stops For Permit 00050562
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-06-16 Cont ID  
Sent By dpalmer Date 2000-06-16 Time 08:13 Rev Time 0.00
Received By dpalmer Date 2000-06-16 Time 08:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-22 Cont ID  
Sent By dpalmer Date 2000-05-22 Time 16:25 Rev Time 0.00
Received By dpalmer Date 2000-05-22 Time 16:25 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SHOW ALL EXISTING ELEC-
 -TRIC IN EXISTING ROOMS. SEEING THAT
 MORE THAN 50% OF THE ELECTRICAL WORK
 IS BEING DONE, ELECTRICAL NEEDS TO BE
 BROUGHT UP TO CODE.
  
 2)NOTE; PLEASE INDICATE ON PLANS ALL
 EXISTING ELECTRIC THAT IS INSTALLED IN
 THE EXISTING ROOMS.
  
 3)NOTE: SMOKE DETECTORS WILL BE REQ`D
 INSDIE AND OUTSIDE ALL SLEEPING ROOMS.
 AS PER NFPA -72 2-2.1.1.1
  
 4)NOTE; MISSSING MEANS OF EGRESS LIGHT-
 ING OUTSIDE EXISTING FAMILY ROOM.210-70
  
 5)NOTE:PLEASE NOTE THE MISSING GFI OUT-
 -LET REQ`D FOR A/C UNIT. PER 210-63
  
 6)NOTE:PLEASE NOTE THAT ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED. PLEASE SHOW.MISSING
 ONE.
  
 7)NOTE;AS REQ`D BY 220-3-C-1 NEED TO
 SUBMIT COMPLETE LOAD CALCULATION FOR
 EXISTING AND ALL NEW LOADS. 215-5
 PLEASE SHOW EXISTING SERVICE SIZE TO
 INCLUDE RISER DIAGRAM WITH ALL WIRE
 SIZES,CONDUITS, GROUNDING SYSTEM.
 IF NEW SERVICE PLEASE INDICATE ON PLANS.
  
  
 8)NOTE: PLEASE PROVIDE NEW PANEL SSCHED-
 -ULE FOR NEW CIRCUITS. PLEASE INCLUDE
 THE REQ`D DEDICATED BATH(S) CIRCUIT(S)
 AS PER 210-11-C-3. NEEDS TO BE #12 AND
 20 AMP.
  
 9)NOTE: YOU ARE SHOWING ALL THE NEW
 TELEPHONE OUTLETS,WHAT ABOUT TV? IF YOU
 ARE GOING TO HAVE CABLE TV OUTLETS THEN
 PLEASE SHOE ON PLANS.
  
 10)NOTE: PLEASE NOTE THAT ALL EXISTING
 AND NEW OUTLET SPACING WILL HAVE TO BE
 BROUGHT UP TO CODE AND MEET 210-52.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS
 PLEASECALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-06-20 Cont ID  
Sent By cthirben Date 2000-06-20 Time 09:44 Rev Time 1.00
Received By cthirben Date 2000-06-20 Time 09:44 Sent To  
Notes
2001-01-08 00:00:00PROVISO*********************************
 INSTALL EXHAUST FAN IN BATHROOMS AS PER
 1997 SMC 503.3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-06-14 Cont ID  
Sent By cthirben Date 2000-06-14 Time 07:22 Rev Time 1.00
Received By cthirben Date 2000-06-14 Time 07:17 Sent To  
Notes
2001-01-08 00:00:00NOTES***********************************
 1. PROVIDE CFM VALUE FOR EACH SUPPLY
 DROP.
 2. REQUIRED TO INSTALL EXHAUST FAN IN
 NEW BATHROOM OR HAVE A WINDOW AS PER
 1997 SMC 503.3.
 3. INFORMATION ON A/C REQUIRED FOR
 REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-02 Cont ID  
Sent By cthirben Date 2000-06-02 Time 14:16 Rev Time 1.00
Received By cthirben Date 2000-06-02 Time 14:14 Sent To  
Notes
2001-01-08 00:00:00******************NOTES*****************
 NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 PERMIT REQUIRED FOR A/C OR MECHANICAL
 INSTALLATION, WITH ENERGY CALCULATIONS.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-09-19 Cont ID  
Sent By tlarge Date 2000-09-19 Time 11:54 Rev Time 0.15
Received By tlarge Date 2000-09-19 Time 11:54 Sent To  
Notes
2001-01-08 00:00:00ORIGINAL RISER WAS SIGNED AND SEALED-
 REVISION MUST ALSO BE SIGNED AND SEALED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-06-14 Cont ID  
Sent By tlarge Date 2000-06-14 Time 21:01 Rev Time 0.30
Received By tlarge Date 2000-06-14 Time 21:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-01 Cont ID  
Sent By tlarge Date 2000-06-01 Time 18:55 Rev Time 0.65
Received By tlarge Date 2000-06-01 Time 18:54 Sent To  
Notes
2001-01-08 00:00:00FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED.SPC SEC.913.2
  
 WATER CLOSETS NOT PERMITTED ON WET VENTS
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.
  
 LAYOUT OF FIXTURES ON SANITARY RISER
 SHALL CORRELATE W/FLOOR PLAN.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 SHOWER SHALL BE A MIN.OF 30"WIDE AND NO
 LESS THAN 1024 SQ.IN.PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.409.8.2.1.
  
 SHOW ALL NEW PLUMBING ON SANITARY RISER.
 (PLANS NOTE "NEW KITCHEN".)

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-06-19 Cont ID  
Sent By fknapp Date 2000-06-19 Time 11:40 Rev Time 2.00
Received By fknapp Date 2000-06-19 Time 08:42 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 FRONT DOOR UNIT WITH SIDELITES
 MULLIONS
 ARCH WINDOWS
 STORM PANELS WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS TO BE USED FOR ALL NON IMPACT
 RESISTANT GLASS
  
  
 *****************NOTE*******************
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED,IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-13 Cont ID  
Sent By lsmith Date 2000-06-13 Time 11:05 Rev Time 0.10
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER TONY MARCELLO 6/12/00

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-17 Cont ID  
Sent By gjoyce Date 2000-05-17 Time 09:35 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***