Plan Review Details - Permit 00050494
Plan Review Stops For Permit 00050494
Review Stop P PLUMBING
Rev No 2 Status P Date 2000-05-17 Cont ID  
Sent By tlarge Date 2000-05-17 Time 12:11 Rev Time 0.30
Received By tlarge Date 2000-05-17 Time 12:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-15 Cont ID  
Sent By tlarge Date 2000-05-15 Time 14:29 Rev Time 1.00
Received By tlarge Date 2000-05-15 Time 14:29 Sent To  
Notes
2001-01-08 00:00:00AIR ADMITTANCE VALVE SHALL NOT BE USED
 TO RELIEVE POSITIVE PRESSURE PER SPC SEC
 905.7.5.AND MANUF.RECOMMENDATIONS.
  
 SUBMIT MANUF.SHEETS FOR SUMP BASIN AND
 PUMPS.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.,717.3.
  
 A CHECK VALVE AND GATE VALVE ARE REQD.ON
 THE EJECTOR DISCHARGE PIPING PER SPC
 SEC.717.2.
  
 SUBMIT WATER RISER FOR REVIEW.
  
 SHOW SIZE OF DRAIN FROM SHAMPOO SINKS.
 COMPLY W/SPC TABLE 714.2.
  
 THE DISCHARGE FROM THE SUMP SHALL
 CONNECT TO THE DRAINAGE SYSTEM PER SPC
 SEC.717.11.