| 2001-01-08 00:00:00 | AIR ADMITTANCE VALVE SHALL NOT BE USED | | | TO RELIEVE POSITIVE PRESSURE PER SPC SEC | | | 905.7.5.AND MANUF.RECOMMENDATIONS. | | | | | | SUBMIT MANUF.SHEETS FOR SUMP BASIN AND | | | PUMPS.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1.,717.3. | | | | | | A CHECK VALVE AND GATE VALVE ARE REQD.ON | | | THE EJECTOR DISCHARGE PIPING PER SPC | | | SEC.717.2. | | | | | | SUBMIT WATER RISER FOR REVIEW. | | | | | | SHOW SIZE OF DRAIN FROM SHAMPOO SINKS. | | | COMPLY W/SPC TABLE 714.2. | | | | | | THE DISCHARGE FROM THE SUMP SHALL | | | CONNECT TO THE DRAINAGE SYSTEM PER SPC | | | SEC.717.11. |
|
|
|