Plan Review Details - Permit 00050421
Plan Review Stops For Permit 00050421
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-06-03 Cont ID  
Sent By lmartine Date 2000-06-03 Time 08:05 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-15 Cont ID  
Sent By dpalmer Date 2000-08-15 Time 20:19 Rev Time 0.00
Received By dpalmer Date 2000-08-15 Time 20:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-05-09 Cont ID  
Sent By dpalmer Date 2000-05-09 Time 20:24 Rev Time 0.00
Received By dpalmer Date 2000-05-09 Time 20:24 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO **************
  
 1)NOTE:PLEASE SHOW LOCATION OF PANELS
 ON FLOOR POWER SHEET.215-55
  
 2)NOTE: PLEASE SUBMIT THE AIC RATING OF
 THE MAIN FOR 850. PER 110-9/215-5
 YOU SHOW PANEL RATING, BUT NOT THE
 RATING FOR THE MAIN DISCONNECT.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT-
 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-07-05 Cont ID  
Sent By rturnque Date 2000-07-05 Time 14:52 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-06-02 Cont ID  
Sent By rturnque Date 2000-06-02 Time 13:46 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE FIRE SPRINKLER DRAWINGS.

Review Stop FS  
Rev No 1 Status P Date 2000-06-19 Cont ID  
Sent By wlehnhar Date 2000-07-05 Time 09:41 Rev Time 0.50
Received By wlehnhar Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER RETT TURNQUEST ( NEED SEPARATE
 PERMIT FOR FS LS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-05-24 Cont ID  
Sent By ndenmark Date 2000-05-24 Time 14:07 Rev Time 0.33
Received By ndenmark Date 2000-05-24 Time 14:07 Sent To  
Notes
***NONE***