Plan Review Details - Permit 00050235
Plan Review Stops For Permit 00050235
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-10-24 Cont ID  
Sent By dpalmer Date 2000-10-24 Time 14:14 Rev Time 0.00
Received By dpalmer Date 2000-10-24 Time 14:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-10-10 Cont ID  
Sent By dpalmer Date 2000-10-10 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2000-10-10 Time 11:32 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST TWO
 REVIEWS.
  
 2)NOTE: PLEASE SEE PANELS "B" AND "C"
 STILL SHOW (3) AIR HANDLER UNIT #1.
 ALSO WIRE SIZED AT 10AWG W/ 50A, 10KW
 LOAD.?
  
 3)NOTE: PLEASE SEE BRKR FEED TO PANEL
 "C". SHOWN AT 2P30? 1/0 CONDUCTOR SIZE.?
  
 4)NOTE: PLEASE NOTE THAT AIC RATINGS FOR
 PANELS HAVE NOT BEEN SUBMITTED.
 PER110-9 AND 215-5
  
 5)NOTE: PANEL SCHEDULES FOR PANEL "A"
 SHOWS MLO?? WHERES MAIN?
 S
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-09-11 Cont ID  
Sent By dpalmer Date 2000-09-11 Time 11:07 Rev Time 0.00
Received By dpalmer Date 2000-09-11 Time 11:07 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
  
 1)NOTE: PLEASE NOTE THAT ALL THE NOTES
 ON THE FIRST REVIEW WERE NOT ADDRESSED.
 PLEASE SEE THE LIST ATTACHED AND MAKE
 CORRECTIONS.
  
 2)NOTE: PLEASE SEE PLANS AND SHOW WHERE
 PANEL "C" IS BEING FED FROM.??
 PLEASE SHOW CONDUIT/WIRE/BRKR/ ETC.
  
 PLEASE SUBMIT ALL THE INFORMATION FROM
 BOTH REVIEWS. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT8372

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2000-10-10 Cont ID  
Sent By dpalmer Date 2000-05-30 Time 21:46 Rev Time 0.00
Received By dpalmer Date 2000-05-30 Time 21:46 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ***************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING OF
 THE EQUIPMENT MAINS. MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT AS REQ`D BY
 110-9 AND 215-5.
  
 2)NOTE; PLEASE NOTE THAT ON THE PANEL
 SCHEDULES YOU ARE SHOWING GAS WATER
 HEATER AND GAS DRYER AND YET YOU ARE
 SHOWING A HIGH ELECTRIC LOAD. ?? PLEASE
 CALRIFY.IF GAS PLEASE CORRECT LOAD.
  
 3) NOTE: PLEASE NOTE AS REQ`D BY 210-11-
 -C-3 . PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) . MUST BE 20 AMP AND
 #12 AWG.
  
 4)NOTE: PLEASE CORRECT LOAD SHOWN FOR
 ELECTRIC COOK TOP? 2000VA 2P50?
  
 5)NOTE: YOU SHOW TWO AHU-1 PLEASE CORREC
 -T. AND NOTE THAT YOU ARE SHOWING 10000W
 ON #10 AWG.2P50.
  
 6)NOTE:MISSING OUTLET SECOND FLOOR 2`OF
 WALL 210-52
  
 7)NOTE: PLEASE NOTE SD MISSING SD OUT-
 -SIDE BEDROOM. UPSTAIRS AND NEED TO
 MOVE SD DOWNSTAIRS TO BE IN THE VICINITY
 OF STAIRS. NFPA-72 2-2.1.1.1
  
 8)NOTE:PLEASE INCLUDE AND SHOW THE COLD
 WATER PIPE AND BLDG.STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM AND SHOW ON
 RISER DIAGRAM. 250-50 /215-5
  
 9)NOTE:PLEASE LABEL AND SHOW ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED AS REQ`D BY 210-8-A-6.
  
 10)NOTE: PLEASE NOTE MISSING OUTLET REQ`
 FOR COUNTER OUTLET SPACING PER 210-52-
 C-1.
  
 11)NOTE:MISSING SMOKE DETECTOR OUTSIDE
 BEDROOM DOWNSTAIRS.
  
 12)NOTE: MISSING MEANS OF EGRESS LIGHT-
 -ING OUTSIDE GARAGE DOOR. 210-70
  
 13)NOTE:MISSING GFI REC FOR A/C CU`S
  
 14)NOTE: PLEASE SHOW PANEL LOCATIONS ON
 FLOOR PLAN., 215-5
  
 15)NOTE:MISSING OUTLETS FOR 2` OF WALL
 FOYER/DEN
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ROUGH/ELEC FOR SLAB.
 THIS INFORMATION MUST BE PROVIDED.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-13 Cont ID  
Sent By ndenmark Date 2000-09-13 Time 09:27 Rev Time 0.25
Received By ndenmark Date 2000-09-13 Time 09:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-05-15 Cont ID  
Sent By cthirben Date 2000-05-15 Time 08:04 Rev Time 1.00
Received By cthirben Date 2000-05-15 Time 08:04 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 NOTES: INDICATE ON PLANS.
 1. CFM'S VALUE OF EXHAUST FANS
 2. DRYER VENT SIZE AND LOCATION
 3. RETURN AIR FOR AHU # 1

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-09-05 Cont ID  
Sent By jleech Date 2001-09-05 Time 16:39 Rev Time 0.33
Received By jleech Date 2001-09-05 Time 16:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-08-23 Cont ID  
Sent By jleech Date 2001-08-23 Time 16:23 Rev Time 0.50
Received By jleech Date 2001-08-23 Time 16:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-08 Cont ID  
Sent By tlarge Date 2000-09-08 Time 09:27 Rev Time 0.50
Received By tlarge Date 2000-09-08 Time 09:27 Sent To  
Notes
2001-01-08 00:00:00*******************PROVISO**************
 SEPARATE PERMIT REQD.FOR GAS.
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR
 FOR DRYER.SGC SEC.402.4.
  
 WATER HEATER IN GARAGE SHALL COMPLY W/
 SGC 402.7.
  
 SUBMIT REVISED SANITARY RISER PRIOR TO
 PLBG.INSPECTION.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
  
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-05-08 Cont ID  
Sent By tlarge Date 2000-05-08 Time 08:12 Rev Time 0.50
Received By tlarge Date 2000-05-08 Time 08:12 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-10-20 Cont ID  
Sent By fknapp Date 2000-10-20 Time 10:33 Rev Time 3.00
Received By fknapp Date 2000-10-20 Time 10:33 Sent To  
Notes
2001-01-08 00:00:00 
  
 *************BUILDING PROVISO***********
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 ARCH WINDOWS
 OCTAGON WINDOWS
  
 PLEASE SUBMIT PRIOR TO INSTALLATION.
  
 2)PROVIDE STORM PANEL INFORMATION UNDER
 SEPARATE PERMIT.
  
 3)PROVIDE ENGINEER REPORTS AND APPROVAL
 OF PILE INSTALLATION PRIOR TO CONCRETE
 SLAB BEING POURED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-10-13 Cont ID  
Sent By fknapp Date 2000-10-13 Time 11:42 Rev Time 2.00
Received By fknapp Date 2000-10-13 Time 11:42 Sent To  
Notes
2001-01-08 00:00:00 
  
 ************BUILDING UNSAT**************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 INSWING DOOR WITH SIDELITES
 ARCH TRANSOMS
 OCTAGON WINDOWS
 MULLIONS
  
 2)PROVIDE INSTALLATION SCHEDULE AND
 KEY PLAN FOR STORM PANELS.
  
 3)PROVIDE OWNER/AGENT SIGNATURE ON
 ENERGY CALCULATIONS.
  
 4)PROVIDE FRAMING DETAILS FOR DECORATIVE
 CHIMNEY.
  
 5)PROVIDE ENGINEER REPORTS AND APPROVAL
 OF PILE INSTALLATION PRIOR TO CONCRETE
 BEING POURED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-09-07 Cont ID  
Sent By fknapp Date 2000-09-07 Time 11:46 Rev Time 4.00
Received By fknapp Date 2000-09-07 Time 08:32 Sent To  
Notes
2001-01-08 00:00:00 
  
  
 **********BUILDING UNSAT****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 INSWING DOOR WITH SIDELITES
 FIX GLASS
 ARCH TRANSOMS
 OCTAGON WINDOWS
 MULLIONS AND ROOF COVERING
  
 2)PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN WITH SPECIFIC ANCHORS TO BE USE
 FOR STORM PANELS.
  
 3)PROVIDE ENERGY CALCULATIONS WITH
 MANUEL J FORM.
  
 4)PROVIDE SOIL TEST.
  
 5)PROVIDE SHEET A-2 FOR BOTH SETS OF
 PLANS.
  
 6)SPECIFY USE OF CHIMNEY, NO FIRE PLACE
 SHOWM ON PLANS.
  
 7)PROVIDE ENGINEER REPORTS AND APPROVAL
 OF PILE INSTALLATION PRIOR TO CONCRETE
 BEING POURED.
  
 8)PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE WITH FLOOR ELEVATION AT 7'5"
 OR BETTER.
  
 9)NEED ZONNING APPROVAL.
  
 10)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-04 Cont ID  
Sent By gjoyce Date 2000-05-04 Time 14:25 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00MUST GET CONCURRENY FROM TIM