Plan Review Details - Permit 00050057
Plan Review Stops For Permit 00050057
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-03-09 Cont ID  
Sent By lmartine Date 2001-03-09 Time 06:44 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-03-09 00:00:00APPROVE WD-65 BY FOLD DOORS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-02-22 Cont ID  
Sent By lmartine Date 2001-02-22 Time 15:53 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-02-21 Cont ID  
Sent By hpiskura Date 2001-02-21 Time 15:05 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-02-21 00:00:00REVISION DATED 1/24/01 HOOOD PLATFORM.
 NEEDS DOWN TOWN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-08-01 Cont ID  
Sent By lmartine Date 2000-08-01 Time 09:32 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00***PROVISO***
  
 1]SUBMIT CORRECTED ENERGY EFFICIENCY
 CALCULATIONS.
 2]IF STORM SHUTTERS ARE PROPOSED FOR
 IMPACT PROTECTION,PLEASE SUBMIT TEST
 REPORT WITH ENGINEERING FOR APPROVAL.
 ALSO SUBMIT INSTALLATION AND STORAGE
 PLAN.
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 561-659-8096#8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-06-20 Cont ID  
Sent By lmartine Date 2000-06-20 Time 15:24 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00***PLAN REVIEW COMMENTS***
  
 1]SIGNED AND SEALED SURVEYS ARE REQUIRED
 2]PROVIDE CITY'S APPROVAL FOR CONSTR.
 ON CITY PROPERTY.
 3]SUBMIT TEST REPORTS FOR ALL INTERIOR
 FINISHES MUST COMPLY WITH 803,'97SBC.
 4]PROVIDE TEST REPORTS FOR WIND AND
 IMPACT COMPLIANCE ON ALL EXTERIOR DOOR
 AND WINDOW SYSTEMS.
 5]DOORS #24 AND 25 MUST BE APPROVED TYPE
 DOORS,SEE 1012SBC.
 6]DOORS #6,20,25,AND26 MUST BE 20 MIN.
 RATED IF PART OF THE EXIT ACCESS.
 7]DOORS 15 AND 16 MUST COMPLY WITH '97
 FAC,4.13.6[MANUVERING CLEARENCES FROM
 PULL SIDE].
 8]ENTRY CANOPY'S SHALL COMPLY WITH APPEN
 "F",102.2.8
 9]TYPE 2 CONSTRUCTION REQUIRES ANY WOOD
 USED,SHALL BE OF FIRE RETARDANT TREAT-
 ED.
 10]SPECIFY WHICH CODE WAS USED FOR THE
 DESIGN CALCULATION,EACH PAGE SHALL BE
 SIGNED AND SEALED.
 11]SUBMIT ENERGY EFFICIENCY CALCULATIONS
 12]PROVIDE ACCESSIBLE SEATING FOR DINING
 PATIO"C".
 13]SUBMIT FIRE SPRINKLER LAYOUT.
  
 REVIEWED BY
 LUIS MARTINEZ
 561-659-8096#8456

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2001-03-01 Cont ID  
Sent By dpalmer Date 2001-03-01 Time 18:05 Rev Time 0.00
Received By dpalmer Date 2001-03-01 Time 18:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2001-02-27 Cont ID  
Sent By dpalmer Date 2001-02-27 Time 11:49 Rev Time 0.00
Received By dpalmer Date 2001-02-27 Time 11:49 Sent To  
Notes
2001-02-27 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT UNDER F.A.C.
 SECTION(S) 481.221 AND 471.025 ALL CHANG
 ES ON PLANS ARE TO BE DONE BY THE ARCH/
 ENGINEER OF RECORD. PLANS ARE TO BE
 SEALED/ SIGNED AND DATED.
  
 PLEASE REDRAW AND SUBMIT THE ABOVE INFOR
 MATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2001-02-22 Cont ID  
Sent By dpalmer Date 2001-02-22 Time 07:34 Rev Time 0.00
Received By dpalmer Date 2001-02-22 Time 07:34 Sent To  
Notes
2001-02-22 00:00:00****************** UNSAT ************
  
 1)NOTE: PLEASE SUBMIT SIGNED AND SEALED
 PLANS PER F.A.C SECT 481.221.
  
 2)NOTE: PLEASE PROVIDE INFORMATION ON
 LOCATIONS OF TRANSFORMERS.
  
 3)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS THAT CORRELATE WITH PANEL
 SCHEDULE.
  
 4)NOTE: PLEASE PROVIDE INFORMATION ON
 THE CONTROL OF ALL FIXTURES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-02 Cont ID  
Sent By jleahy Date 2000-08-02 Time 12:45 Rev Time 1.45
Received By jleahy Date 2000-08-02 Time 12:44 Sent To  
Notes
2001-01-08 00:00:00TRANSFORMER TO MEET 450-21BJLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-07-27 Cont ID  
Sent By dpalmer Date 2000-07-27 Time 12:52 Rev Time 0.00
Received By dpalmer Date 2000-07-27 Time 12:52 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT*****************
  
 1)NOTE: UNSAT FOR PHASE TWO (II)
 PLEASE SEE AND ADDRESS FIRST SET OF
 NOTES GIVEN BY JAKE LEAHY.
  
 2)NOTE: PLEASE PROVIDE CONDUIT LAYOUT
 PLAN, SHOWING CONDUIT SIZES FOR PHASE
 I ONLY.
  
 3)NOTE: PLEASE SUBMIT SPECS ON 1400 AMP
 OCP SHOWN AT 1600AMP MAIN. 1400 AMP
 FUSES ARE NOT STANDARD AND IF YOU HAVE
 A MANUFACTURE`S LISTING, THEN PLEASE
 SUBMIT. SEE ART;240-6
  
  
 IF WIRE SIZES, AND CONDUIT SIZES CHANGE
 DUE TO MAIN OCP THEN THERE WOULD BE A
 PROBLEM ISSUING ANY PERMIT FOR PHASE I
 ELECTRICAL.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-25 Cont ID  
Sent By jleahy Date 2000-05-25 Time 13:09 Rev Time 1.30
Received By jleahy Date 2000-05-25 Time 13:03 Sent To  
Notes
2001-01-08 00:00:001-PG. E-5 MAIN FEEDER TO MDP IS TOO SMAL
 WIRE HAS TO MATCH BREAKER AND BE BASED
 ON 75C RATING NOT 90C 110-14(C2)
  
 2-PG. E-5 GROUNDING ELECTRODE CONDUCTOR
 IS TOO SMALL SHOULD BE A LEAST A 4/0
 250-66
  
 3-PG. E-5 NO AIC RATINGS SHOWN FOR ANY
 PANELS, MAINS, BREAKERS, OR OTHER EQUP
 110-9,10

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-08-14 Cont ID  
Sent By mgonzale Date 2000-08-14 Time 14:20 Rev Time 2.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISOS
 1. ANY WORK ALONG SIDEWALK MUST BE
 CONTAINED ON SITE.ANY DAMAGE TO EXIST.
 SIDEWALK MUST BE RESTORE TO EQUAL OR
 BETTER CONDITIONS.
 2. DUMPSTER MUST BE ACCESSIBLE AT ALL
 TIMES. SEE DUMPSTER MINIMUM DIMENSIONS
 ON DETAIL ATTACHED.
 3. PROVIDE TWO COPIES OF PLANS SHOWING
 WATER, SEWER AND DRAINAGE FOR PUBLIC
 UTILITIES APPROVAL.
 ATTENTION: MANNY GONZALEZ
 PROJECT SPECIALIST
 1000 45TH ST, SUITE 15
 WEST PALM BEACH, FL 33407
 561-659-8040 FAX 561-659-8039.
 PLEASE ALSO SUBMIT SHOP DRAWINGS
 TO THE SAME LOCATION.WE MUST RETAIN
 TWO COPIES, 1 FOR THE UTILITY FILE AND
 1 FOR OUR PUBLIC UTILITY INSPECTORS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-03-05 Cont ID  
Sent By mcarsill Date 2001-03-05 Time 08:49 Rev Time 0.00
Received By mcarsill Date 2001-03-05 Time 08:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-01-26 Cont ID  
Sent By mcarsill Date 2001-01-26 Time 09:02 Rev Time 0.00
Received By mcarsill Date 2001-01-26 Time 09:02 Sent To  
Notes
2001-01-26 00:00:001) DEEP FAT FRYERS ARE TO BE EQUIPPED
 WITH HIGH LIMIT CONTROLS.
 2) IT APPEARS THAT MORE CLEAN-OUTS MAY
 BE NEEDED TO PROPERLY INSPECT AND CLEAN
 THE EXHAUST DUCTS.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-04 Cont ID  
Sent By rturnque Date 2000-08-04 Time 14:46 Rev Time 1.00
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE PANICK HARDWARE ON ALL DESIGNATE
 D EXIT DOORS.
 PROVIDE SHOP DRAWINGS FOR HOOD AND
 EXTINGUISHING SYSTEM.
 PROVIDE SHOP DRAWINGS FOR FIRE ALARM
 SYSTEM.
 SUBMIT SEATING DIAGRAM TO THE FIRE DEPT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-05-09 Cont ID  
Sent By rturnque Date 2000-05-09 Time 15:02 Rev Time 0.55
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE FIRE SPRINKLER DRAWINGS.
 PROVIDE PANICK HARDWARE ON ALL EXIT
 DOORS.
 PROVIDE SHOP DRAWINGS FOR HOOD
 EXTINGUISHING SYSTEM, FIRE ALARM SYSTEM
 AND FIRE SPRINKLER SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-16 Cont ID  
Sent By cthirben Date 2000-08-16 Time 10:03 Rev Time 0.00
Received By cthirben Date 2000-08-16 Time 10:56 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 *FAN SHUTDOWN FOR A SYSTEM UNDER
 2000 CFM SERVING AN AREA USED AS AN
 EGRESS AS PER 1997 SMC 406.2....
 *ADDITIONAL PERMIT REQUIRED FOR HOOD,
 FIRE SUPPRESSION SYSTEM, FUEL AND WALK-
 IN COOLER/FREEZER.
  
 ***EXHAUST DUCT INSIDE RATED SHAFT SHALL
 MAINTAIN A MINIMUM CLEARANCE OF 6" AS
 PER 1997 SMC 505.9.1 AND NOT AS STATED
 ON SHEET M7 OF THE PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-05-24 Cont ID  
Sent By cthirben Date 2000-05-24 Time 08:06 Rev Time 0.00
Received By cthirben Date 2000-05-24 Time 09:18 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 1. FAN SHUTDOWN FOR AGGREGATE AREA OF
 2000 CFM OR MORE, OR UNDER 2000 CFM
 BUT SERVING AN AREA USED FOR EGRESS
 1997 SMC 406.2
 2. ADDITIONAL PERMIT REQUIRED FOR HOOD,
 FIRE SUPPRESSIONAND GAS.

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-01-18 Cont ID  
Sent By jleech Date 2001-01-18 Time 17:07 Rev Time 0.75
Received By jleech Date 2001-01-18 Time 17:07 Sent To  
Notes
2001-01-18 00:00:00GAS REVISIONS

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-08-15 Cont ID  
Sent By tlarge Date 2000-08-15 Time 17:21 Rev Time 2.00
Received By pschmitz Date 2000-08-15 Time 17:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-08-14 Cont ID  
Sent By tlarge Date 2000-08-14 Time 15:47 Rev Time 0.00
Received By pschmitz Date 2000-08-14 Time 11:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-01 Cont ID  
Sent By tlarge Date 2000-08-01 Time 18:26 Rev Time 3.00
Received By pschmitz Date 2000-08-01 Time 12:49 Sent To  
Notes
2001-01-08 00:00:001)INDICATE TYPE OF PIPING FOR GAS SYSTEM
 TO ENSURE COMPLIANCE W/SGC.(JOB SPECS.
 ARE NOT WITH PLANS.)
  
 2)SHT.A2.0-RESTROOM FIXTURE CALCULATIONS
 ARE NOT IN COMPLIANCE W/SPC TABLE 407
 FOR THE TYPE OF OCCUPANCIES AND OCCUPANT
 LOAD.RESTAURANT LOAD TO BE BASED ON
 NUMBER OF SEATS NOTED ON SHEET A5.1.
 (154)AN ADDITIONAL WATER CLOSET IS REQD.
 IN EACH TOILET ROOM.
  
 3)ADDITIONAL INFORMATION REQD.FOR POWER
 VENT FOR GAS WATER HEATER.SEE SHT.M1,
 NOTE #4.
  
 4)SHT.M1-SUBMITTED COMBUSTION AIR CALC-
 ULATIONS ARE DEFICIENT AS DESIGNED.
 COMPLY W/SGC SEC.402.4.4.4(3),NFPA 5.3.5
  
 5)SHT.M2-KIT.EQUIP.#P-11A SHALL
 DISCHARGE TO GREASY WASTE.SPC 1004.4.
  
 6)DISHWASHER SHALL DISCHARGE TO THE
 SANITARY SYSTEM PER CITY OF WPB ORDIN-
 ANCE.
  
 7)COMBINATION WASTE AND VENT SYSTEM IS
 NOT SIZED TO SPC SEC.921.4.1-921.4.2.
 SYSTEM SHALL DISCHARGE TO THE GREASY
 WASTE SYSTEM,NOT THE SANITARY.SPC SEC.
 1004.4.
  
 8)SUBMIT APPROVAL FORM FROM CITY OF WPB
 UTILITIES DEPT.FOR GREASE TRAP.COUNTY
 WIDE AMENDMENTS TO SPC SEC.101.4.7.
 CONTACT R.COMPO AT 561-835-7423.
  
 9)WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC SEC.610.4.1.,610.4.2.
  
 10)DISPOSAL OF CONDENSATE SHALL COMPLY
 W/SMC SEC.304.8.3.(SEE SHT.M3,COL.A6)
  
 11)DRESSING ROOM BENCH SHALL BE LOCATED
 ALONG THE LONGER DIMENSION WALL PER
 FACBC SEC.4.35.4.
  
 12)URINALS SHALL BE SCREENED FOR PRIVACY
 PER SPC SEC.404.3.
  
 13)SEE ATTACHED DRAWING FOR GREASE TRAP.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT 561-659-8096,EXT.8377.
 TIMOTHY LARGE,PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-26 Cont ID  
Sent By tlarge Date 2000-05-26 Time 16:20 Rev Time 2.75
Received By tlarge Date 2000-05-26 Time 16:20 Sent To  
Notes
2001-01-08 00:00:00JOB SPECIFICATION 15000-SEC.1.04-THE
 PLUMBING CODE IN EFFECT IS THE 1994
 EDITION OF THE STANDARD PLUMBING CODE.
 REVISE THE SPECS.TO REFLECT THIS STAN-
 DARD.
  
 SUBMIT OCCUPANT LOAD OF EACH AREA PER
 SPC TABLE 407 FOR DETERMINATION OF MIN.
 REQUIRED SANITARY FACILITIES.SEE SEC.
 407.1.3. FOR ALLOWED DEDUCTIBLE AREAS.
  
 DELETE REFERENCE TO THE UNIFORM BUILDING
 CODES NOTED THROUGHOUT THE PLANS.THE
 STANDARD BUILDING CODES ARE THE ADOPTED
 STANDARDS.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.1.
  
 SUBMIT A COMPLETE SANITARY AND WATER
 ISOMETRIC FOR REVIEW.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 SUBMIT A GAS ISOMETRIC FOR REVIEW.SHOW
 DISTANCE TO MOST REMOTE OUTLET,PIPE
 SIZES,TYPE OF PIPING,TYPE OF GAS,BTU
 LOAD OF EACH APPLIANCE,TOTAL BTU LOAD ON
 THE SYSTEM,TYPE OF VENT,ETC.SGC SEC.302.
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR.
 COMPLY W/SGC SEC.402.4.
  
 DRAINS FROM THE BAR AREA SHALL DISCHARGE
 THROUGH THE GREASE INTERCEPTOR PER SPC
 SEC.1004.4.
  
 DRAINS IN BAR AND KITCHEN AREAS SHALL
 DISCHARGE TO THE BUILDING DRAINAGE SYS-
 TEM THROUGH AN INDIRECT WASTE PER SPC
 SEC.804.INSTALLATION OF INDIRECT WASTES
 SHALL COMPLY W/SPC SEC.805.1,806,807.
  
 CAPACITY OF GREASE TRAP SHALL BE
 APPROVED BY CITY OF WPB UTILITIES.SUBMIT
 APPROVAL FORM FROM CITY OF WPB.CONTACT
 R.COMPO AT(561)835-7423.
  
 TWO WAY CLEANOUTS ARE REQD.ON THE INLET
 AND OUTLET TO THE GREASE TRAP PER SPC
 SEC.710.4.
  
 SUPPLY MANUF.INSTALLATION INSTRUCTIONS
 FOR POWER VENT INSTALLATION.COMPLY W/
 SGC SEC.610.3.
  
 BOTTOM FED WATER HEATERS SHALL BE
 EQUIPPED W/VACUUM RELIEF VALVE PER SPC
 SEC.507.1.2.
  
 NUMBER OF SANITARY FACILITIES SHALL
 COMPLY W/FLA.STATUTE 553.141(1)(2)(3).