Plan Review Details - Permit 00050040
Plan Review Stops For Permit 00050040
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-05 Cont ID  
Sent By dpalmer Date 2000-07-05 Time 19:55 Rev Time 0.00
Received By dpalmer Date 2000-07-05 Time 19:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-24 Cont ID  
Sent By dpalmer Date 2000-05-24 Time 19:56 Rev Time 0.00
Received By dpalmer Date 2000-05-24 Time 19:56 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE:PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. AS REQ`D BY 210-8-A-6
  
 2)NOTE:BLDG.STEEL TO BE PART OF THE
 GROUNDING ELECTRODE SYSTEM AS PER 250-50
 SHOW ON PLANS .
  
 3)NOTE:RISER DIAGRAM NOTE NOTES FUSED
 DISC? NOT SHOWN? PLEASE SUBMIT CORRECT
 RISER DIAGRAM. MAIN MUST BE RATED FOR TH
 AVIALABLE FAULT CURRENT. 110-9
  
 4)NOTE: PLEASE NOTE THE MISSING OUTLETS
 REQ`D BY 210-52 FRONT FOYER ARE AND AD-
 -JOINING AREA.
 5)NOTE: PLEASE SHOW ON PANEL SCHEDULE
 THE REQ`D DEDICATED BATH(S) CIRCUIT(S)
 PER 210-11-C-3 MUST BE 20A AND #12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REIVEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-05-05 Cont ID  
Sent By cthirben Date 2000-05-05 Time 11:42 Rev Time 0.00
Received By cthirben Date 2000-05-05 Time 11:42 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 INDICATEON PLANS EXHAUST FANS AND DRYER
 VENT.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-05-05 Cont ID  
Sent By tlarge Date 2000-05-05 Time 06:14 Rev Time 0.33
Received By tlarge Date 2000-05-05 Time 06:04 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-07-14 Cont ID  
Sent By jgomez Date 2000-07-14 Time 12:50 Rev Time 1.50
Received By jgomez Date 2000-07-14 Time 12:50 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE SAFETY GLASS AT BEDROOM #2.
 SECTION 2405.2 SBC 1997.
 2-PROVIDE PRODUCT APPROVAL FOR BUTT
 GLAZING ASSEMBLY AT MASTER BATH.
 3-PRODUCT APPROVAL FOR SLIDING GLASS
 DOORS IS NOT GOOD. SEE SIZES SHOWN
 ON PLANS AND PRODUCT APPROVAL.
 4-PROVIDE COMPLETE INSTALLATION DETAIL/
 SPECS FOR AHU IN ATTIC. INCLUDE ALL
 HANGERS. SEC 104.2.2 CITY AMENDMENTS.
 5-PROVIDE COPIES OF SOIL TEST REPORT
 DONE AS PER SEC 1804.2.7.3 OF CITY
 AMENDMENTS.
 6-PROVIDE PRODUCT APPROVAL FOR INSWING
 DOUBLE ENTRY DOORS.
 7-PROVIDE STRUCTURAL BUCK DETAIL WITH A
 2X BUCK IF REQUIRED IN THE DOORS
 PRODUCT APPROVAL.
 8-PROVIDE PRODUCT APPROVAL FOR:
 -WINDOW MULLIONS, FRENCH DOOR AT MASTER
 SUITE, FIXED WINDOW OF THE SIZE SHOWN
 AT THE LIVING ROOM ABOVE THE SLIDING
 GLASS DOORS.
 9-REVISE SIZE OF CEILING FANS. SEE TABLE
 6-6 OF FLORIDA ENERGY EFFICIENCY CODE
 FOR BUILDING CONSTRUCTION. 1997 ED.
 10-SEE COMMNETS ON PLANS, INCLUDING THE
 OTHER TRADES.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-07-07 Cont ID  
Sent By jgomez Date 2000-07-07 Time 12:45 Rev Time 2.50
Received By jgomez Date 2000-07-07 Time 12:45 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-IMPACT FEES WERE NOT PAID.
 2-PROVIDE SAFETY GLAZING AT BEDROOM #2.
 SECTION 2405.2 SBC 1997.
 3-PROVIDE PRODUCT APPROVAL FOR BUTT
 GLAZING ASSEMBLY AT MASTER BATH.
 4-PRODUCT APPROVAL FOR SLIDING GLASS
 DOORS IS NO GOOD. SIZE OF DOORS SHOWN
 ON LIVING ROOM IS NOT COVERED IN THIS
 PRODUCT APPROVAL. RESUBMIT.
 5-PROVIDE COMPLETE INSTALLATION DETAIL/
 SPECIFICATIONS FOR AHU IN ATTIC.
 INCLUDE ALL FASTENERS.
 6-PROVIDE COPIES OF SOIL TEST REPORT
 DONE AS PER SEC 1804.2.7.3 OF CITY
 AMENDMENTS.
 7-INSWING PRODUCT APPROVAL SUBMITTED IS
 FOR SINGLE DOOR ONLY. PROVIDE PRODUCT
 APPROVAL FOR INSWING DOUBLE DOORS.
 8-PROVIDE STRUCTURAL BUCK DETAIL WITH
 2X BUCK IF REQUIRED IN THE PRODUCT
 APPROVAL REQUIREMENTS.
 9-PROVIDE PRODUCT APPROVAL FOR:
 WINDOW MULLIONS, FRENCH DOOR AT MASTER
 SUITE, FIXED WINDOW OF THE SIZE SHOWN
 AT THE LIVING ROOM ABOVE THE SLIDING
 GLASS DOORS.
 10-REVISE SIZE OF CEILING FANS. SEE
 TABLE 6-6 OF FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING CONSTRUCTION.
 11-SEE COMMENTS ON PLANS, INCLUDING THE
 COMMENTS BY THE OTHER TRADES.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-14 Cont ID  
Sent By tmoore Date 2000-06-14 Time 15:47 Rev Time 8.00
Received By tmoore Date   Time   Sent To  
Notes
2001-01-08 00:00:00SBC 104.2.2
 1) PROVIDE 2 CURRENT COPIES OF SBCCI
 OR METRO DADE PRODUCT APPROVALS FOR ;
 ALL EXTERIOR SWING DOOR ASSEMBLIES
 AND FIREPLACE UNIT
  
 2) PROVIDE ENGINEERING FOR ALL BUTT GLAS
 OPENINGS.
  
 3) PROVIDE NAME AND SIGNITURE OF PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 4) PROVIDE SAFETY GLASS AS REQUIRED.
 1997 SBC 2405.2
  
 *************NOTE***************
  
 5) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH CO. THE PERMIT PLAN STAMPED
 BY THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-04 Cont ID  
Sent By gjoyce Date 2000-05-04 Time 08:30 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***