Plan Review Details - Permit 00041269
Plan Review Stops For Permit 00041269
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hpiskura Date 2000-05-23 Time 07:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-06-09 Cont ID  
Sent By jleahy Date 2000-06-09 Time 09:13 Rev Time 4.00
Received By jleahy Date 2000-06-09 Time 09:13 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-06-13 Cont ID  
Sent By mgonzale Date 2000-06-13 Time 14:59 Rev Time 1.00
Received By dlauderm Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLANS APPROVED, AND STAMPED THRU OUR
 OFFICE.PERMIT FEE AND SUBMITTAL
 NEEDS TO BE MADE THRU B&Z.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-05-11 Cont ID  
Sent By mgonzale Date 2000-05-11 Time 15:18 Rev Time 2.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED WITH THE FOLLOWING PROVISOS
  
 1. REAR ALLEY BETWEEN PHASE 1 PROPERTY
 AND PHASE 2 PROPERTY SHALL HAVE NEW
 SURFACE WHEN PROJECT IS COMPLETED
  
 2. A CATCH BASIN IS REQUIRED ALONG
 EVERNIA STREET AT DRIVEWAY (THIS
 AREA MAY NEED A CONFLICT STRUCTURE)
  
 3. RESTRIPE PARKING ALONG NARCISUS AVE
  
 4. RADIUS ARE REQUIRED IN THE ALLEYWAY
 ENTRANCES.ANY PAVERS ALONG ALLEYWAY
 WILL NOT BE REPLACED IN CASE OF A SEWER
 BREAK OR ANY MAINTENANCE ALONG ALLEYWAY.
  
 5. AREAS ADJACENT TO THIS PROPERTY
 EITHER DISTURBED OR DAMAGED MUST BE
 MILLED AND PAVED.
  
 6. WORK ALONG OLIVE SHOULD BE COORDINATE
 D WITH FLORIDA DEPARTMENT OF TRANSPORTAT
 ION. SIDEWALK ALONG EVERNIA SHOULD HAVE
 A RADIOUS THAT WILL MATCH NEW FDOT OLIVE
 IMPROVEMENTS.
  
 7. BOTH BACKFLOWS SHOULD BE AT PROPERTY
 LINE.
  
 SEE MARKED PLANS AND IF YOU HAVE ANY
 QUESTIONS PLEASE FEEL FREE TO CONTACT
 PROJECT COORDINATOR, DEAN LAUDERMILK
 1000 45TH ST. SUITE 9
 WEST PALM BEACH, FL 33409
 (561) 659-8040 EXT 2307
 FAX (561) 659-8039
  
 AFTER REVISING THESE COMMENTS PLEASE
 PROVIDE 2 COPIES OF PLANS TO
 PUBLIC UTILITIES ENGINEERING
 1000 45TH ST. SUITE 9
 WEST PALM BEACH, FL 33409
 MANNY GONZALEZ, PROJECT SPECIALIST
  
 YOU MAY ALSO SUBMIT SHOP DRAWINGS
 FOR APPROVAL TO MANNY GONZALEZ
 (2 SETS, ONE FOR THE FILE AND ONE
 FOR OUR UTILITY INSPECTOR)

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By mcarsill Date 2000-07-27 Time 12:14 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:00ON JULY 27, 2000, WRITER CALLED JAMES
 CUDDY OF AMERICAN LAND. WRITER ADVISED
 HIM THAT SEVERAL COMMENTS FROM THE
 PLAN CHECK REVIEW PERFORMED BY FIRE
 RESCUE HAVE NOT BEEN COMMENTED ON. IT
 APPEARS THAT THE ITEMS ON THE PLAN
 COMMENT LETTER FROM MR. LORDI HAVE BEEN
 DONE BUT ADDITIONAL ITEMS NEED TO BE
 ADDRESSED. WRITER GAVE MR. CUDDY THE FAX
 NUMBER FOR ADDITIONAL RESPONSES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-06-07 Cont ID  
Sent By rturnque Date 2000-06-07 Time 10:28 Rev Time 2.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) KNOX-BOX NEEDED FOR FIRE RESCUE
 ACCESS.
 2) NO HYDRAULIC CALCULATIONS SHOWN FOR
 FIRE SPRINKLER SYSTEM DRAWINGS.
 3) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL VERTICAL SHAFTS,ELECTRICAL,
 MECHANICAL, AND STORAGE ROOMS.
 4) STANDPIPE SYSTEMS TO COVER ALL AREAS
 OF THE BUILDINGS WITH 100 FEET OF HOSE
 WITH 30 FEET OF NOZZLE SPRAY.
 5) EMERGENCY LIGHTING NEEDED IN FIRE
 PUMP ROOM.
 6) LOFTS NEED SMOKE DETECTORS ON EACH
 LEVEL.
 7) PROVIDE COMPLETE SHOP DRAWINGS ON THE
 FIRE ALARM SYSTEM. CUT SHEETS NEEDED ON
 ALL DEVICES PLANNED. SYSTEM TO BE CLASS
 A OR ADDRESSABLE. SYSTEM TO BE MONITORED
 BY A UL LISTED CENTRAL STATION.
 8) ADDRESS NOT SHOWN ON ELEVATION
 DRAWINGS.
 9) CANVAS AWNINGS TO BE FIRE RATED.
 10) FIRE SEPARATION BETWEEN GARAGE AND
 BUILDING TO BE AT LEAST 2 HOUR FIRE
 RATED.
 11) OPENINGS IN THIS TWO HOUR SEPARATION
 SHALL BE AT LEAST 1 1/2 RATED.
 12) GARAGE MECHANICAL VENTILATION TO
 PROVIDE AT LEAST SIX AIR CHANGES PER
 HOUR.
 13) PARKING GARAGE TO COMPLY WITH NFPA
 88A.
 14) KITCHEN EXHAUST SHAFTS TO MEET
 APPLICABLE FIRE RATINGS.
 15) STAIRS TO COMPLY WITH NEW STAIRS AS
 PER THE LIFE SAFETY CODE, 1985 EDITION.
 16) DOORS OPENING INTO CORRIDORS SHALL
 NOT ENTER MORE THAN SEVEN INCHES. CHECK
 ELECTRICAL CLOSETS.
 17) FIRE DAMPERS TO COMPLY WITH UL 555.
 18) KITCHEN HOOD, DUCT AND EXTINGUISHING
 SYSTEMS TO COMPLY WITH NFPA 96 AND 17A.
 19) ELEVATORS TO COMPLY WITH STANDARD
 BUILDING CODE 1997 EDITION SECTION
 3003.4, STRETCHER REQUIREMENTS.
 20) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, 1985 EDITION.
 21) ANY ASSEMBLY OCCUPANCY SPACE TO
 HAVE PROVISIONS FOR AT LEAST TWO
 PERSONS.
 22) PANIC HARDWARE ON RATED DOORS TO
 BE FIRE EXIT PANIC HARDWARE.
 23) ELEVATOR RECALL REQUIRED, SEE NOTE
 24) EXPLAIN NOTE ABOUT ASTRAGALS FOR
 DOUBLE RATED FIRE DOORS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-07-24 Cont ID  
Sent By ndenmark Date 2000-07-24 Time 13:28 Rev Time 5.00
Received By ndenmark Date 2000-07-24 Time 13:28 Sent To  
Notes
2001-01-08 00:00:00************DENIED********************
  
 1. ACCEPTANCE TEST FOR STAIRWAY PRESSUR-
 IZATIONPER NFPA 92A REQUIRED BY CERT-
 IFIED TEST AND BALANCE CONTRACTOR IN
 PRESSANCE OF CITY INSPECTORS
 2. ROOM W/ HP-1 IS RATED. ALL PENETRA-
 TIONS TO BE PROTECTED PER 1997 SMC 610
 1997 SMC 610.6 REQUIRES LOCATION AND
 INSTALLATION DETAILS TO BE SHOWN AND
 PROPERLY IDENTIFIED ON PLANS
 3.SHOW COMPLIANCE W/ SBC 412.5
 NOTE: OVERFLOW PROTECTION REQUIRED FOR
 ALL VERTICAL AND HORIZONTAL AHU AND HP
 PER 1997 SMC 304.8.6
 KITCHEN EXHAUST DUCT TO BE ACCESS-
 IBLE PER 1996 NFPA 96 4-3.4.3 EACH FLOOR
 IF NOT ACCESSIBLE THRU THE TOP BY PERSON
 NEL FOR CLEANING

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-08 Cont ID  
Sent By ndenmark Date 2000-06-08 Time 06:46 Rev Time 4.00
Received By ndenmark Date 2000-06-08 Time 06:46 Sent To  
Notes
2001-01-08 00:00:001) PROVIDE SEQUENCE OF OPERATION FOR
 STAIRWAY PRESSURIZATION. NOTE:
 ACCEPTANCE TEST PER NFPA 92A REQUIRED
 BY CERTIFIED TEST AND BALANCE COMPANY IN
 PRESSENCE OF CITY INSPECTORS
 2) M101 SHOW RETURN AIR PATH FOR HP-1
 20 MIN. RATED DOOR, NO FIRE DAMPER SHOWN
 AT DUCT LEAVING ROOM WITH HP-1
 3) M101 DUCT PENETRATING VALET ROOM WALL
 TO HAVE FIRE DAMPER AT PENETRATION IF
 WALL IS RATED (DOOR IS RATED TO ROOM)
 4) SHOW AIR BALANCE SCHEDULE AND AIR
 EXCHANGE CALCULATIONS FOR GARAGE AS
 REQUIRED BY CODE
 5) M102 NO FIRE DAMPER SHOWN AT DUCT
 PENETRATION OF ELEVATOR VESTIBULE AREA
 6) M107 ALL CHWSR RISERS IN GARAGE TO
 PROTECTED FROM DAMAGE
 7) PROVIDE SPECS FOR DRYER BOOSTER FANS
 8) DRYER EXHAUST DUCT TO BE RUN AS
 STRAIGHT AS POSSIBLE TO LIMIT 90 AND 45
 DEGREE BENDS
 9) SEVERAL BATH EXHAUST FANS (EF-A) HAVE
 NO DUCT SHOWN ATTACHED 1997 SMC 501.3
 REQUIRES ALL EXHAUSTED AIR TO BE DIS-
 CHARGED OUTDOORS
 10) NO DUCT RUNS SHOWN FOR LOFT DRYERS,
 PROVIDE INFORMATION ON PLAN
 11) PROVIDE RATING/SPECS ON HOSES FOR
 HEAT PUMPS
 12) OVERFLOW PROTECTION REQUIRED FOR ALL
 AHU AND HP (VERTICAL OR HORIZONTAL) PER
 1997 SMC 304.8.6
 13) PROVIDE INFORMATION WHERE AUX DRAIN
 TERMINATES (NOT FOUND ON PLUMBING PLANS)
 1997 SMC REQUIRES AUX DRAIN LINE TO TERM
 INATE IN A CONSPICUOUS LOCATION TO SERVE
 AS AN ALARM THAT THE REGULAR DRAIN IS
 RESTRICTED
 14) PROVIDE INFORMATION ON LOCATION OF
 EXHAUST DUCT AND FAN LOCATION FOR FUTURE
 KITCHEN HOODS

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-08-04 Cont ID  
Sent By tlarge Date 2000-08-04 Time 12:39 Rev Time 0.00
Received By tlarge Date 2000-08-04 Time 12:39 Sent To  
Notes
2001-01-08 00:00:0023)WASTE STACKS CANNOT BE USED FOR VERT-
 ICAL COMBINATION WASTE AND VENT.911.4.
  
 24)HORIZONTAL BRANCH CONNECTIONS CANNOT
 CONNECT TO STACK WITHIN 2 FT.ABOVE OR
 BELOW THE OFFSET.
  
 25)THE FOLLOWING UNITS SHOW THE WATER
 CLOSET IN THE BATHROOM INFRINGING INTO
 REQUIRED CLEAR FLOOR SPACE WHICH IS IN
 VIOLATION OF THE FHA.
 SHT.A433-UNITS B2 & B2A
 SHT.A443-UNIT C6
 SHT.A445-UNIT D2
 SHT.A447-UNIT D4
 SHT.A449-UNIT D5B
 SHT.A450-UNIT D6
 SHT.A451-UNITS D7 & D7A
 SHT.A452-UNIT D8
 SHT.A453-UNIT D9
 THE FOLLOWING UNITS SHOW VIOLATIONS OF
 THE FHA IN THE KITCHEN AREA.
 SHT.A451-UNIT D7A-THE REFRIGERATOR
 INFRINGES ON THE 5'-0"TURNING SPACE.
 COMPLY W/FHA REQ.#7(1)(A)(B)(C).
 SHT.A456-UNIT D13-KITCHEN IS NOT WIDE
 ENOUGH TO COMPLY W/FHA REQ.#7(1)(C).
  
 IF YOU HAVE ANY QUESTIONS CALL
 561-659-8096,EXT.8377
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-08-04 Cont ID  
Sent By tlarge Date 2000-08-04 Time 09:03 Rev Time 32.00
Received By tlarge Date 2000-07-27 Time 20:19 Sent To  
Notes
2001-01-08 00:00:001)SHT.C-6 AND P401-GREASE INTERCEPTORS
 SHALL COMPLY W/CITY OF WPB BLDG.DEPT.
 REQS.SEE ATTACHED.SPC 1004.2
  
 2)SHT.A110-THE NUMBER OF OCCUPANTS FOR
 THE POOL CLUB HOUSE SHALL BE BASED ON
 SQUARE FEET OF HABITABLE FLOOR SPACE
 PER SPC TABLE 407.SEE SPC SEC.407.1.3
 FOR ALLOWED DEDUCTIBLE FLOOR SPACE.
 SHOW OCCUPANT LOAD ON PLANS. A MIN.OF 2
 TOILET ROOMS SHALL BE REQD.
  
 3)SHT.A601-BACKING FOR GRAB BARS FOR TUB
 AT BACK WALLSHALL COMPLY W/FHA REQ.#6,
 FIG.#4.(SEE ATTACHED.)
  
 4)SHT.A601-HEIGHT OF HANDICAP URINAL
 SHALL COMPLY W/FACBC SEC.4.18.2.(MAX.OF
 17"TO TOP OF RIM.)
  
 5)SUBMIT HABITABLE SQUARE FOOT AREA OF
 EACH PUBLIC AND COMMON USE AREA TO
 DETERMINE OCCUPANT LOAD FOR MINIMUM
 SANITARY FACILITY REQS..COMPLY W/SPC
 TABLE 407.RE:EXERCISE AREA,RETAIL,ETC.
  
 6)CLEAR FLOOR SPACE FOR THE SINKS IN THE
 KITCHENS OF THE DWELLING UNITS SHALL BE
 CENTERED ON THE FIXTURE PER FHA 24 CFR
 100.205 REQ.#7(USABLE KITCHENS)AND FAIR
 HOUSING ACT.REFER TO SHEETS A453 UNIT D9
 SHT.A457,UNITS E1 & E1A,SHT.A460,UNIT
 D4A.
  
 7)SHT.A801-DETAIL SHOWS 4" DIA.SCUPPER.
 SUBMIT CALCULATIONS FOR OVERFLOW
 DRAINAGE.COMPLY W/SPC SEC.1109.3 &
 APPENDIX"A".
  
 8)SUBMIT DETAIL OF OIL INTERCEPTOR.SPC
 1004.4.
  
 9)VERTICAL COMBINATION WASTE AND VENTS
 FOR THE KITCHEN SINK SHALL REMAIN
 VERTICAL FROM WASTE STACK OR BRANCH
 BEGINNING AT THE BLDG.DRAIN.SPC SEC.
 911.4.SEE SHTS.P303-308.
  
 10)SOIL AND WASTE STACKS SHALL REMAIN
 UNDIMINISHED IN SIZE FROM THE BUILDING
 DRAIN TO IT'S CONNECTION W/THE STACK
 VENT PER SPC SEC.714.2.
  
 11)SANITARY RISERS SHALL COMPLY W/SPC
 SEC.715.2.(THIS CODE SECTION APPLIES TO
 ALL RISERS DESIGNED IN THE SAME MANNER.
  
 12)RISERS SHALL COMPLY W/SPC SEC.911.3,
 TABLE 911.3.SEE SHT.P304,RISER# S/14.
  
 13)RISERS SHALL COMPLY W/SPC 714.2.
  
 14)FIXTURES ON STACKS ABOVE THE HIGHEST
 WATER CLOSET OR BATHTUB SHALL COMPLY W/
 SPC SEC.913.2.SEE RISER #6 ET.AL.
  
 15)SOIL AND WASTE STACKS IN BUILDINGS
 HAVING MORE THAN TEN BRANCH INTERVALS
 SHALL BE PROVIDED W/RELIEF VENTS AT EACH
 TENTH INTERVAL PER SPC SEC.916.
  
 16)OFFSET VENTS SHALL BE INSTALLED PER
 SPC SEC.715.4,917.1-917.3.SEE SPC SEC.
 715.5 FOR OMISSION OF VENTS.
  
 17)SHT.P315-SHOW SQ.FOOTAGE FOR DRAINS
 FOR PARKING GARAGE.SUBMIT CALCULATIONS
 FOR SECONDARY DRAINAGE.COMPLY W/SPC SEC.
 1109.2,1109.3.& APPENDIX "A".
  
 18)A PERMIT MAY BE REQD.FROM THE DEPT.OF
 ENVIRONMENTAL PROTECTION FOR THE WATER
 MAIN INSTALLATION.COUNTYWIDE AMENDMENTS
 TO SPC SEC.101.4.7.
  
 19)SHT.P101-ITEM#12-CLARIFY IF LINE IS
 3"OR 4".SEE SHT.P301.
  
 20)SHT.P301-5TH.FLR.RISER-CIRCUIT AND
 LOOP SHALL COMPLY W/SPC SEC.914.
  
 21)RISER DIAGRAMS SHOW STACKS W/2 HORIZ.
 BRANCHES AT BASE AND SHT.P301 SHOWS 1
 CONNECTION.CLARIFY.
  
 22)MAX.VERTICAL DISTANCE OF COMBINATION
 WASTE AND VENT SHALL COMPLY W/TABLE
 911.4.
  
 SEE PLBG.REVIEW STEP #4 FOR CONTINUATION

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-05-20 Cont ID  
Sent By tlarge Date 2000-05-20 Time 12:27 Rev Time 25.00
Received By tlarge Date 2000-05-20 Time 12:27 Sent To  
Notes
2001-01-08 00:00:00**********PLBG.STEP#2-CONTINUATION OF
 PLUMBING COMMENTS FOR #00041269.
  
 23)SHT.P305-RISER S/3-SHALL COMPLY W/SPC
 SEC.911.3 & TABLE 911.3.(THIS CODE SEC.
 APPLIES TO ALL RISERS DESIGNED IN THE
 SAME MANNER.)
  
 24)SHT,P305-RISERSS/5 & S/20-SHALL
 COMPLY W/SPC SEC.714.2.(APPLIES TO ALL
 RISERS OF THIS DESIGN.)
  
 25)FIXTURES LOCATED ON STACKS ABOVE THE
 HIGHEST WATER CLOSET OR BATHTUB SHALL
 COMPLY W/SPC SEC.913.2.(SEE SHT.P306-
 RISER #S/6 AND ALL OTHERS OF THE SAME
 DESIGN.)
  
 26)RELIEF VENTS ARE REQD.IN SOIL OR
 WASTE STACKS MORE THAN 10 BRANCH INTER-
 VALS PER SPC SEC.916
  
 27)OFFSET VENTS SHALL BE INSTALLED PER
 SPC 917.1,917.2,917.3.(SEE SHT.P306,
 RISERS S/11,S/25, AND ALL OTHER STACKS
 OF THE SAME DESIGN.)
  
 28)SHT.P310-SHOW PIPE SIZES FOR THE
 GREASE WASTE AND SANITARY COLLECTION
 SYSTEMS.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 29)SHT.P401-MIN.1"INSULATION IS REQD.ON
 C.W.PIPE AT WATER HEATER PER F.E.C.
 TABLE 4-11.(SEE NOTE #15.)
  
 30)SUBMIT COMPLETE STORM DRAINAGE RISER
 FOR REVIEW.SHOW SQ.FT.AREA DRAINED BY
 EACH DRAIN,PIPE SIZES,SLOPE OF PIPE.
 INCLUDE ALL AREA DRAINS AND DECK DRAINS
 IN THE DRAWING.COUNTYWIDE AMENDMENTS TO
 SPC 104.2.1.
  
 31)SUBMIT PROVISIONS,CALCULATIONS,AND
 DRAWINGS FOR SECONDARY DRAINAGE FOR THE
 ROOF.COMPLY W/SPC SECS.1109.1,1109.2,
 1109.3 AND APPENDIX "A".
  
 32)LAYOUT OF GREASY WASTE SYSTEM ON P310
 DOESN'T CORRELATE W/P102.CLARIFY.
  
 33)SHT.P310 NOTES 8"TO SANITARY AND
 P102 NOTES 6".CLARIFY.(SEE GREASE WASTE)
  
 34)A PERMIT MAY BE REQD.FROM THE DEPT.OF
 ENVIRONMENTAL PROTECTION FOR THE WATER
 MAIN INSTALLATION.COUNTYWIDE AMENDMENTS
 TO SPC SEC.101.4.7.
  
 35)REQUIRED NUMBER OF SANITARY FIXTURES
 FOR THE POOL SHALL COMPLY W/FLA.DEPT.OF
 HEALTH CHAPTER 64E-9.APPROVAL REQD.FROM
 HEALTH DEPT.
  
 36)A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE FOUNTAIN.
  
 37)SHT.P312-NOTES ALL P&T LINES AND DP
 LINES AS 1 1/2" AND P101 CALLS OUT
 1 1/4".SHT.P101 ALSO NOTES 1 1/2" LINES
 DISCHARGING INTO A 1 1/4" LINE U/G AND
 A/G.CLARIFY.LINES SHALL NOT BE REDUCED
 IN SIZE PER VALVE MANUF.RECOMMENDATIONS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-19 Cont ID  
Sent By tlarge Date 2000-05-19 Time 17:22 Rev Time 0.00
Received By tlarge Date 2000-05-19 Time 17:22 Sent To  
Notes
2001-01-08 00:00:001)SHT.A110-THE NUMBER OF OCCUPANTS SHALL
 BE BASED ON HABITABLE FLOOR SPACE PER
 SPC TABLE 407.SEE SPC SEC.407.1.3.FOR
 ALLOWED DEDUCTIBLE FLOOR SPACE AND NOTE
 OCCUPANT LOAD ON PLANS.
  
 2)PLANS FOR POOL HOUSE SHALL BE REVIEWED
 BY PALM BEACH COUNTY HEALTH DEPT.PRIOR
 TO REVIEW BY THIS DEPT.SPC SEC.101.4.7.
  
 3)BATHROOMS IN THE DWELLING UNITS SHALL
 COMPLY W/THE FEDERAL FAIR HOUSING ACT 24
 CFR 100.205(C)(3)(I-IV).SUBMIT DETAILS
 OF REINFORCED WALLS FOR FUTURE INSTALL-
 ATION OF GRAB BARS.COMPLY W/FHA REQ.#6,
 FIGURES #3,4,& 5.
  
 4)CLEAR FLOOR SPACE FOR FIXTURES SHALL
 BE SHOWN ON THE PLAN AND DESIGNATE WHICH
 DESIGN SPECIFICATION("A"OR "B")OF THE
 FAIR HOUSING ACT IS BEING USED.
  
 5)SUBMIT HABITABLE SQUARE FOOT AREA OF
 EACH PUBLIC AND COMMON USE AREA TO
 DETERMINE OCCUPANT LOAD FOR MINIMUM
 SANITARY FACILITY REQS.COMPLY W/SPC
 TABLE 407.(RETAIL,EXERCISE,ETC.)
  
 6)SHT.A422-RESTROOM #R104 SHALL BE FULLY
 ACCESSIBLE PER FACBC SEC.4.1.3.(10)(A).
  
 7)SANITARY FACILITIES FOR THE RESTAURANT
 SHALL COMPLY W/FLA.STATUTE 553.141(3).
 (POTTY PARITY)
  
 8)CLEAR FLOOR SPACE FOR FIXTURES IN THE
 KITCHEN SHALL BE CENTERED ON THE FIXTURE
 PER FHA 24 CFR 100.205 REQ.#7(USABLE
 KITCHENS) AND FAIR HOUSING DESIGN MANUAL
  
 9)CLOSETS HOUSING WASHER/DRYER UNITS
 WHICH ARE INTENDED FOR PASSAGE SHALL
 HAVE 32" NOMINAL CLEAR OPENING PER FHA
 24 CFR 100.205 REQ.#7 & FHA DESIGN
 MANUAL.(SEE SHTS.A434 UNIT B3 AND SHT.
 A444 UNIT C7.)
  
 10)SHOW THE REQUIRED FIXTURE CLEARANCE
 DIMENSION OF THE WATER CLOSETS FROM
 FINISHED SURFACE OF ADJOINING WALLS,
 VANITIES,EDGE OF LAVATORY,OR ANY OTHER
 OBSTACLE PER FHA 24 CFR 100.205 REQ.#7.
  
 11)PUBLIC AND COMMON AREA TOILET ROOM
 SHALL HAVE WALLS AND FLOORS OF NONABSORB
 ENT MATERIAL TO HEIGHT OF 4'ABOVE THE
 FLOOR PER SBC 1204.2.NOTE ON SHT.A501.
  
 13)SHT-A601-SHOW MOUNTING HEIGHTS OF ALL
 HANDICAP FIXTURES AND CLEAR FLOOR SPACE
 BENEATH FIXTURES.COMPLY W/FACBC 1997 ED.
  
 14)SHT. A801-DETAIL#3 SHOWS 4"DIA.
 SCUPPER.SUBMIT CALCULATIONS FOR OVERFLOW
 DRAINAGE.COMPLY W/APPENDIX"A" OF SPC.
  
 15)SHT.FP101 ET.AL.-SHOWS DISCHARGE OF
 DRAINRISER TO STORM DRAINAGE SYSTEM.
 DISCHARGE SHALL BE TO EXTERIOR PER NFPA
 13 SEC.4-14.3.4.3.
  
 16)SHT.P101-CHECK KEYNOTES #10,11.
 LINE IS NOTED AS SANITARY AND CALLED OUT
 AS CONDENSATE AND RWL.
  
 17)SHT.P103-KEYNOTES #6 & 7 ARE
 MISLABELED.
  
 18)SUBMIT DETAIL OF OIL INTERCEPTOR.
 COMPLY W/CITY OF WEST PALM BEACH ENG.
 STANDARDS.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 19)P200 DRAWINGS-CLEARLY LABEL RISERS
 FOR IDENTIFICATION AND REVIEW.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 20)VERTICAL COMBINATION WASTE AND VENT
 STACKS FOR KIT.SINKS SHALL COMPLY W/SPC
 SEC.911.4.(MAX.HEIGHT FOR 4"IS 100').
  
 21)SOIL AND WASTE STACKS SHALL REMAIN
 UNDIMINISHED IN SIZE FROM BUILDING DRAIN
 TO CONNECTION W/THE STACK VENT PER SPC
 SEC.714.2.
  
 22)SHT.P305-RISER #S/3-COMPLY W/SPC SEC.
 715.4.(THIS CODE SECTION APPLIES TO ALL
 RISERS DESIGNED IN THE SAME MANNER.)
 **SEE PLBG.STEP #2 FOR CONTINUATION*****

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***