Plan Review Details - Permit 00041268
Plan Review Stops For Permit 00041268
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-06-28 Cont ID  
Sent By dpalmer Date 2000-06-28 Time 15:55 Rev Time 0.00
Received By dpalmer Date 2000-06-28 Time 15:55 Sent To  
Notes
2001-01-08 00:00:00PLANS REDLINED AND TO BE REVISED BEFORE
 FINAL..

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-05-24 Cont ID  
Sent By dpalmer Date 2000-05-24 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2000-05-24 Time 18:26 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE:NEED TO SHOW THE REQ`D SMOKE
 DETECTORS OUTSIDE BEDROOMS IN THE IMMED-
 IATE VICINITY. THEY ARE ALSO REQ`D ON
 EACH LEVEL IN COMMON AREAS. AS REQ`D BY
 NFPA-72 2-2.1.1.1
  
 2)NOTE:MISSING THE REQ`D OUTLET FOR
 FRONT OF DWELLING PER 210-52E
  
 3)NOTE:MISSING OUTLET FOR DOWNSTAIRS
 BEDROOM PER 210-52 2` OF WALL
  
 4)NOTE; OUTLET FOR GARAGE MUST BE GFI
 AS PER 210-8
  
 5)NOTE:PLEASE SHOW THE REQ`D BATH(S)
 CIRCUIT(S) AS PER 210-11-C-3.MUST BE
 20AMP AND #12 AWG.
  
 6)NOTE:PLEASE SHOW THE GROUNDING ELEC-
 -TRODE CONDUCTOR GOING TO COLD WATER
 PIPE AND AND BLDG. STEEL AS REQ`D BY
 250-50
  
 7)NOTE:PLEASE PROVIDE THE AIC RATING OF
 MAIN ON PANEL AND BRKRS. MAIN MUST BE
 RATED FOR THE AVAILABLE FAULT CURRENT
 AS PER 110-9.
  
 PLEASE NOTE THAT PLANS WOULD HAVE PASSED
 WITH A PROVISO BUT WERE COMING BACK FOR
 MECHANICAL BEING DENIED ANYWAY. PLEASE
 MAKE THE ABOVE CHANGESAND SUBMIT FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-09 Cont ID  
Sent By jleech Date 2000-12-09 Time 09:55 Rev Time 0.33
Received By jleech Date 2000-12-09 Time 09:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2000-06-23 Cont ID  
Sent By cthirben Date 2000-06-23 Time 10:10 Rev Time 0.00
Received By cthirben Date 2000-06-23 Time 11:06 Sent To  
Notes
2001-01-08 00:00:00DENIED:******************************
 A/C DEMAND SUBMITTED ON THEPLANS IS 1935
 CFM'S, THE A/C UNIT IS A FOUR TON UNIT
 TOTAL SUPPLY IS 1600 CFM'S.
 THE UNIT IS TOO SMALL.
 SEPERATE PERMIT REQUIRED FOR MECHANICAL/
 A/C INSTALLATION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-06-28 Cont ID  
Sent By cthirben Date 2000-06-28 Time 16:39 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2001-01-08 00:00:00***************DENIED*******************
 1. ENERGY CALCULATIONS SHEETS REQUIRED.
 2.EXHAUST FAN REQUIRED IN BATHROOMS
 3.DRYER VENT TO BE INDICATED AND INSTALL
 4.INFORMATION ON A/C UNIT REQUIRED
 CUSTOMER WAS INFORMED (STEVE SMITH).
 5.RETURN AIR TO BE SHOWN ON PLANS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-05-05 Cont ID  
Sent By tlarge Date 2000-05-05 Time 06:27 Rev Time 0.33
Received By tlarge Date 2000-05-05 Time 06:27 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-06-28 Cont ID  
Sent By sgraham Date 2000-06-28 Time 16:40 Rev Time 5.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-01 Cont ID  
Sent By gjoyce Date 2000-05-01 Time 09:51 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***