Plan Review Details - Permit 00040985
Plan Review Stops For Permit 00040985
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-07-12 Cont ID  
Sent By bstaples Date 2000-07-12 Time 14:47 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-06-27 Cont ID  
Sent By bstaples Date 2000-06-27 Time 11:42 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. CHANGES TO EXTERIOR ELEVATION NOT
 APPROVED BY CITYPLACE.
 2. FLORIDA ENERGY SHEETSW NOT SIGNED BY
 OWNER. OK 7/5/00
 3. LETTER RELEASING SPACE FROM SPECIAL
 INSPECTOR OK 7/5/00, ORIGIONAL RECEIVED.
 4. FIRE SPRINKLER PERMIT REQUIRED
 PRIOR TO ISSUANCE OF BUILDING PERMIT.
 5. ELEVATION REVIEWED BY JOHN COLLIER RE
 TELEPHONE NO APPROVAL ISSUED 7/5/00.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-06-16 Cont ID  
Sent By bstaples Date 2000-06-16 Time 10:30 Rev Time 0.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. FLORIDA ENERGY SHEETS NOT SUBMITTED.
 2. LETTER FROM CITYPLACE ENGINEER NOT
 SUBMITTED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-05-24 Cont ID  
Sent By bstaples Date 2000-05-24 Time 11:34 Rev Time 3.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. FLORIDA ENERGY SHEETS 1997 CODE.
 2. LETTER FROM CITYPLACE ENG. RELEASING
 SPACE FOR BUILDOUT PERMIT.
 3. SHEET G-1 CODE REFERENCE REVISE NOTE1
 A.BUILDING CODE IS 1997 SBC AS AMENDED
 BY THE CITY OF WPB.
 B. MECHANICAL CODE IS 1997 SBC AS
 AMENDED BY THE CITY OF WPB.
 C. NOTE 21: ALL EXTERIOR GLSAZING SHALL
 COMPLY WITH THE 1997 SBC AND CITY OF WPB
 AMENDMENTS FOR LARGE MISSLE IMPACT
 PROTECTION.
 D. PLUMBING CODE IS 1994 SBC AS AMENDED
 BY THE CITY OF WPB.
 E. ELECTERICAL CODE IS THE 1997 NEC AS
 AMENDED BY THE CITY OF WPB.
 F. FLORIDA ENERGY CODE IS THE 1997
 EDITION.
 4. FIRE SPRINKLER CONTRACTOR TO APPLY
 FOR PERMIT.
 5. SHEET A-6 SECTION A, ALL FIRE
 SEPERATIONS ARE TO BE FINISHED ON BOTH
 SIDES.
 6. SIGNS REQUIRE SEPERATE PERMITS.
 7. BUILDING IS TYPE II CONSTRUCTION
 1997 SBC ALL WOOD PRODUCTS SHALL BE
 INSTALLED ACCORDING TO THE APPLICABLE
 CODE SECTIONS.
 8. GLAZING: PROVIDE PRODUCT APPROVAL
 INFORMATION INDICATING COMPLIANCE WITH
 THE 1997 SBC CHAPTER 16 AS AMENDED BY
 THE CITY OF WPB. METRO DADE COUNTY OF
 SBCCI PRODUCTS ARE ACCEPTABLE.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2000-11-27 Cont ID  
Sent By dpalmer Date 2000-11-27 Time 16:47 Rev Time 0.00
Received By dpalmer Date 2000-11-27 Time 16:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-07-13 Cont ID  
Sent By dpalmer Date 2000-07-13 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2000-07-13 Time 09:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-06-27 Cont ID  
Sent By dpalmer Date 2000-06-27 Time 21:29 Rev Time 0.00
Received By dpalmer Date 2000-06-27 Time 21:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2000-06-09 Cont ID  
Sent By dpalmer Date 2000-06-09 Time 14:13 Rev Time 0.00
Received By dpalmer Date 2000-06-09 Time 21:24 Sent To  
Notes
2001-01-08 00:00:00NO ELECTRICAL SHEETS SUBMITTED

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-04-27 Cont ID  
Sent By dpalmer Date 2000-04-27 Time 19:50 Rev Time 0.00
Received By dpalmer Date 2000-04-27 Time 19:50 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO **************
  
 1)NOTE: PLEASE CORRECT THE EQUIPMENT
 GROUNDING CONDUCTOR YOU SHOW ON E-4.
 AS PER 250-122 OF THE '99' NEC 400 AMP
 OC PROTECTION REQ`S #3.
  
 2)NOTE: ALSO FOR THE COLOR CODING ON E-5
 YOU SHOW FOR 277/480 GRAY AND WHITE WITH
 STRIPE. UNDER THE LOCAL AMENDMENTS ART;
 215, 277/480 REQ`S ONLY GRAY.
 PLEASE REMOVE THE WORDING FOR WHITE W/
 STRIPE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL (561)659-8096
 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-07-05 Cont ID  
Sent By bstaples Date 2000-07-05 Time 11:02 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO M. CARSILLO, PROVIDE EMERGENCY
 LIGHTING IN SALES AREA. 6/29/00.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-05-15 Cont ID  
Sent By bstaples Date 2000-05-15 Time 15:12 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE M. CARSILLO NOTES ATTACHED TO PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-08-07 Cont ID  
Sent By cthirben Date 2000-08-07 Time 08:02 Rev Time 1.00
Received By cthirben Date 2000-08-07 Time 07:54 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
 SAFE ROOM: PROVIDE MANUFACTURERDETAIL-
 ED INFORMATION TO INDICATE CODE COMPLI-
 ANCE WITH SMC SECTION 403 PRIOR TO INSU-
 LATION. SCHEDULE PRE-INSPECTION PRIOR TO
 INSTALLING
  
 ATTACH DIFFUSERS AS REQUIRED BY FLORIDA
 ENERGY CODE 1997 EDITION, SECTION 410.
 1ABCD.3.3. PROVIDE INFORMATION AND SCHE-
 DULE PRE-INSPECTION PRIOR TO INSTALLING
 SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-05 Cont ID  
Sent By bstaples Date 2000-07-05 Time 12:52 Rev Time 0.00
Received By cthirben Date 2000-08-07 Time 07:40 Sent To  
Notes
2001-01-08 00:00:001. SAFE ROOM: PROVIDE MANFACTURES
 DETAILED INFORMATION TO INDICATE CODE
 COMPLIANCE WITH SMC SECTION 403 PRIOR
 TO INSTULLATION. SCHEDULE PRE INSPECTION
 PRIOR TO INSTALLING.
 2. ATTACH DIFUSER AS REQUIRED BY FLORIDA
 ENERGY CODE 1997 EDITION, SECTION
 410.1ABCD.3.3. PROVIDE INFORMATION AND
 SEHEDULE PRE INSPECTION PRIOR TO
 INSTALLING SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-05-01 Cont ID  
Sent By ndenmark Date 2000-05-01 Time 07:08 Rev Time 1.00
Received By ndenmark Date 2000-05-01 Time 07:08 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
  
 1) EXHAUST FANS NOTE 2 SHOW VENT TO
 ABOVE CEILING SPACE. 1997 SMC 501.3
 REQUIRES ALL EXHAUST TO BE DISCHARGED
 OUTDOORS.
 2) SAFE ROOM SHOWS NO VENTILATION.
 1997 SMC 403 REQUIRES EVERY PORTION OF
 EVERY BUILDING TO BE VENTILATED IN
 ACCORDANCE WITH ASHRAE 62-89
 3) DIFFUSER DETAIL INDICATES FLEX
 ATTACHMENT METHOD. NOTE METHOD TO COMPLY
 WITH ENERGY EFFICIENCY CODE FOR BLDG
 CONSTRUCTION 1997 410.1ABCD.3.3

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-11-28 Cont ID  
Sent By jleech Date 2000-11-28 Time 16:36 Rev Time 0.33
Received By jleech Date 2000-11-28 Time 16:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-07-12 Cont ID  
Sent By tlarge Date 2000-07-12 Time 15:56 Rev Time 0.50
Received By tlarge Date 2000-07-12 Time 15:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-07-05 Cont ID  
Sent By tlarge Date 2000-07-05 Time 09:10 Rev Time 0.50
Received By tlarge Date 2000-07-05 Time 09:10 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY FIXED LADDER
 FOR ACCESS OR RELOCATE EWH TO FLOOR.
  
 PROVISIONS SHALL BE MADE AT DRINKING
 FOUNTAIN FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.FACBC SEC.4.1.3.(10)
 (A).
  
 SUBMIT MANUF.SHEETS FOR STEAMER UNITS.
 MAX.TEMPERATURE OF WASTE DISCHARGED TO
 SANITARY SHALL BE 140 DEGREES PER SPC
 SEC.717.8
  
 FLOOR SINKS SHALL BE INSTALLED IN LIEU
 OF HUB DRAINS AND SHALL BE OF A DESIGN
 THAT PREVENTS SPLASHING PER SPC SEC.
 807.1.3.
  
 SHOW LOCATION OF 2ND.DRINKING FOUNTAIN
 ON FLOOR PLAN.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE,PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-06-12 Cont ID  
Sent By tlarge Date 2000-06-12 Time 18:04 Rev Time 1.50
Received By tlarge Date 2000-06-12 Time 18:04 Sent To  
Notes
2001-01-08 00:00:00SINK AT KITCHEN AREA SHALL COMPLY
 W/FACBC SECS.4.24.1-4.24.7.
  
 CLEARLY SHOW LOCATION OF DRINKING
 FOUNTAIN AND COMPLIANCE W/FACBC SEC.
 4.1.3.(10)(A).
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.PROVIDE FIXED LADDER
 OR RELOCATE TO FLOOR.
  
 SHOW DRINKING FOUNTAIN ON SANITARY AND
 WATER RISER.DRINKING FOUNTAIN SHALL
 COMPLY W/FACBC SEC.4.1.3.(10)(A).
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLE BENDING OR STOOPING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-04-29 Cont ID  
Sent By tlarge Date 2000-04-29 Time 10:17 Rev Time 1.25
Received By tlarge Date 2000-04-29 Time 10:17 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SQ.FOOTAGE OF HABITABLE FLOOR
 SPACE TO ENSURE COMPLIANCE W/TABLE 407
 OF SPC 1994 EDITION.REFER TO SEC.407.1.3
 FOR ALLOWED DEDUCTIBLE AREAS.
  
 PLANS SHALL BEAR CITY PLACE LANDLORD
 APPROVAL STAMPS.
  
 SINK AT KITCHEN AREA SHALL COMPLY W/
 FACBC SECS.4.24.1-4.24.7.
  
 SANITARY FACILITIES AND DRINKING
 FOUNTAIN SHALL BE ACCESSIBLE TO THE
 PUBLIC PER SPC SEC.407.2.2.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A),4.15.PROVISIONS SHALL
 BE MADE FOR PERSONS WHO HAVE TROUBLE
 BENDING OR STOOPING.SUBMIT DETAIL.
  
 SHOW DIMENSIONS OF TOILET ROOMS.SIZE AND
 CLEAR FLOOR SPACE FOR FIXTURES SHALL
 COMPLY W/FACBC SEC.4.16,FIG.28.
  
 SHT.A-17-LENGTH OF GRAB BARS BEHIND AND
 ALONG SIDE WATER CLOSETS SHALL COMPLY
 W/FACBC SECS.4.16.4,FIG.#29.
  
 HEIGHT OF TOWEL DISPENSERS SHALL COMPLY
 W/FACBC SEC.4.2.5, 4.2.6.
  
 SHOW HEIGHT OF H.C.WATER CLOSET.COMPLY
 W/FACBC SEC.4.16.3.
  
 CLEAR FLOOR SPACE UNDER H.C.LAV.SHALL
 COMPLY W/FACBC SEC.4.19.2.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.PROVIDE FIXED LADDER
 OR RELOCATE TO FLOOR.
  
 SUBMIT MANUF.SHEETS FOR STEAMERS.MAX.
 TEMP.OF WATER TO SANITARY SHALL BE 140
 DEGREES PER SPC SEC.717.8.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-15 Cont ID  
Sent By gjoyce Date 2000-04-24 Time 11:40 Rev Time 1.00
Received By bstaples Date 2000-05-15 Time 15:14 Sent To  
Notes
***NONE***