Plan Review Details - Permit 00040910
Plan Review Stops For Permit 00040910
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-05-12 Cont ID  
Sent By lmartine Date 2000-05-12 Time 07:55 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-26 Cont ID  
Sent By dpalmer Date 2000-05-26 Time 15:19 Rev Time 0.00
Received By dpalmer Date 2000-05-26 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-03 Cont ID  
Sent By dpalmer Date 2000-05-03 Time 19:13 Rev Time 0.00
Received By dpalmer Date 2000-05-03 Time 19:13 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: YOU ARE SUBMITTING PLANS FOR THE
 ELECTRICAL SERVICE AND SHELL?? 274-E-4.1
 IF THE ONLY WORK BEING DONE IS THE FRONT
 THEN PLEASE SUBMIT ONLY THE SHEETS FOR
 WORK. IF THE SHELL IS BEING DONE THEN
 PLEASE CALL FOR NOTES. YOU NEED TO SHOW
 MORE DETAIL ON SERVICE FOR SHELL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS CALL
 561-659-896 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-05-05 Cont ID  
Sent By mgonzale Date 2000-05-05 Time 13:27 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED
 NO NEW WATER AND SEWER SERVICES
 ALL WORK IS BEING PERFORMED ON SITE
 AND TIED TO EXISTING LINES.
 ENGINEER WILL BE RESPONSIBLE FOR
 CALCULATING ALL FLOWS IN REFERENCE
 TO EXISTING SERVICES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-05-12 Cont ID  
Sent By rturnque Date 2000-05-12 Time 13:58 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status A Date 2000-05-05 Cont ID  
Sent By ndenmark Date 2000-05-05 Time 11:08 Rev Time 1.00
Received By ndenmark Date 2000-05-05 Time 11:08 Sent To  
Notes
2001-01-08 00:00:00INFORMATION PROVIDED ACCEPTED FOR SHELL
 ONLY. BUILDOUT OF STORE WILL REQUIRE
 ADDITIONAL PERMIT AND PLANS SUBMITTED
 FOR REVIEW. NOMECHANICAL WORK OTHER
 THAN SHOWN ON PLANS TO BE DONE PRIOR TO
 ADDITIONAL PLANS AS REQUIRED ABOVE.
 PROVIDE INFORMATION FOR CONDENSATE DRAIN
 TERMINATION. AS SHOWN ON PLAM M-1 NOT
 ACCEPTABLE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-05-27 Cont ID  
Sent By tlarge Date 2000-05-27 Time 11:22 Rev Time 0.65
Received By tlarge Date 2000-05-27 Time 11:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-04-30 Cont ID  
Sent By tlarge Date 2000-04-30 Time 12:37 Rev Time 0.65
Received By tlarge Date 2000-04-30 Time 12:37 Sent To  
Notes
2001-01-08 00:00:00PLAN REFERS TO SHT.274A-3.THIS SHEET IS
 NOT INCLUDED IN SET.
  
 A CLEANOUT IS REQD.ON THE INLET AND OUT-
 LET OF THE OIL INTERCEPTOR PER SPC
 1004.2.
  
 CONDENSATE DRAINS CANNOT DISCHARGE TO
 STORM SYSTEM INSIDE BUILDING.DRAINS
 SHALL INDIRECTLY CONNECT TO SYSTEM ON
 EXTERIOR OF BUILDING OR RUN INDEPENDENT
 TO APPROVED POINT OF DISPOSAL.SMC SEC.
 304.8.3.
  
 8"STORM DRAIN CANNOT DRAIN 18000 SQ.FT.
 OF ROOF AREA AT 2% PER SPC TABLE 1108.2.
 REVISE SLOPE OR INCREASE PIPE SIZE.

Review Stop Z ZONING
Rev No 1 Status N Date 2000-05-12 Cont ID  
Sent By lmartine Date 2000-05-12 Time 07:55 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***