| Plan Review Stops For Permit 00040884 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-07-25 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-07-25 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-01 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-06-01 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING COMMENTS | | | ------------------- | | | 1]SATISFY COUNTY IMPACT FEE REQUIREMENTS | | | 2]SUBMIT LIFE SAFETY PLAN FOR EGRESS TO | | | ENTIRE BUILDING. | | | 3]EXPLAIN SMALL STAGE AT 2ND FLOOR [MAY | | | BE REQUIRED TO BE HANDICAP ACCESSIBLE] | | | 4]PROVIDE CLEAR SCOPE OF WORK,PLANS SHOW | | | MAJOR RENOVATION. | | | 5]PROVIDE ACCURATE SQUARE FOOT COUNT. | | | 6]EXPLAIN FUTURE OPENING NOTES AT 2ND | | | FLOOR PLAN AND 4TH FLOOR RESIDENTIAL | | | NOTE. | | | 7]2 APPROVED EXITS ARE REQUIRED FROM | | | EACH FLOOR LEVEL. | | | 8]SUBMIT FIRE SPRINKLER PLAN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-14 |
Time |
22:31 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-14 |
Time |
22:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE ELECTRICAL | | | SHEETS THAT WERE SUBMITTED DID NOT HAVE | | | THE CHANGES CLOUDED OR OUTLINED. | | | ALSO THERE WAS NO INDICATION THAT THE | | | PLANS WERE COMPLETELY RE-DRAWN?? | | | | | | | | | PLEASE SEE NOTES FROM BLDG PLAN REVIEW. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-05-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-05-15 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-05-15 |
Time |
16:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2000-06-01 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-06-01 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-12-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-20 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-20 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) THE SECOND FLOOR PLAN ON PAGE E-1 | | | IS WHAT TYPE OF OCCUPANCY. WHAT IS | | | THE SQUARE FOOTAGE. | | | 2) DESCRIBE OPENING AT CURVED STAIR | | | AT OPENING INTO BUILDING TO THE WEST | | | AT THE SECOND LEVEL. | | | 3) NO FIRE SPRINKLERS SHOWN ON FOURTH | | | FLOOR. | | | 4) NO SMOKE DETECTION EQUIPMENT SHOWN | | | ON THE FOURTH FLOOR. | | | 5) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT | | | SHOWN ON THE PLANS. | | | 6) THE SINGLE MEANS OF EGRESS IS NOT | | | PERMITTED FROM THE LIVE WORK LOFT | | | PER BUILDING CODE REQUIREMENTS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-05-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-05-30 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISH IN EXITS SHALL BE | | | CLASS A OR B. | | | 2) PROVIDE COMPLETE SHOP DRAWINGS FOR | | | THE INSTALLATION OF THE FIRE ALARM | | | SYSTEM. CUT SHEETS REQUIRED ON ALL | | | DEVICES PLANNED. SYSTEM TO BE MONITORED | | | BY A LICENSED UL LISTED CENTRAL STATION. | | | 3) NEW STAIRS TO COMPLY WITH | | | REQUIREMENTS FOR NEW STAIRS, NFPA 101, | | | 1985 EDITION. | | | 4) CURVED STAIRS TO COMPLY WITH | | | NFPA 101, 1985 EDITION. | | | 5) SUBMIT DRAWINGS FOR FIRE SPRINKLER | | | SYSTEM NOTED ON PLANS. | | | 6) GUARDS AND HANDRAILS TO COMPLY | | | WITH NFPA 101, 1985 EDITION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-12-26 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-26 |
Time |
07:39 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-12-26 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. RE: NOTE ON SHAFT REMOVAL OR MODIFIC- | | | ATION, 1997 SMC 610.4 DUCTS EXTENDING | | | THROUGH MORE THAN ONE FLOOR TO BE PROTE- | | | CTED BY SHAFT ENCLOSURE HAVING A FIRE | | | RESITANCE NOT LESS THAN 2 HRS FOR A BUIL | | | DING 4 STORIES AND MORE IN HEIGHT. PLAN | | | UNCLEAR AS TO WHAT WILL BE CHANGED. THIS | | | CODE SHALL BE COMPLIED WITH FOR ANY | | | CHANGES. | | | 2. LOCAL AMENDMENTS REQUIRE MINIMUM 18" | | | CLEARANCE BETWEEN ROOF SURFACE AND | | | BOTTOM OF SUPPORT STRUCTURE OF STAND. | | | PLEASE UPDATE STAND PRODUCT APPROVAL, | | | PLAN INDICATES EXPIRED DADE CO. APPROVAL | | | 3. NOTE 5 AND 6 SHOW OUTSIDE AIR AND | | | EXHAUST AIR OUTLET NEXT TO EACH OTHER | | | NOTE 10 FT SEPARATION REQUIRED AS MIN- | | | IMUM. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-05-24 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-05-24 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
2000-05-24 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *****************PROVISO**************** | | | 18" HEIGHT MIN. FROM THE TOP OF FINISHED | | | ROOF TO THE BOTTOM OF UNIT ON THE UNIT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-12-15 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-15 |
Time |
14:53 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2000-12-15 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.HI-LOW DRINKING FOUNTAIN REQUIRED SPC | | | TABLE 407 AND MUST MEET FACBC 4.1.3 | | | (10). | | | | | | 2.SHOW MEASUREMENTS OF HANDICAP BATHROOM | | | STALLS.INCLUDE TURNING CIRCLES. | | | | | | 3.SHOW MEASUREMENTS FOR OTHER PARTITIONS | | | IN BATHROOMS. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2000-06-01 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-06-01 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2000-06-01 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-06-01 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|