Plan Review Details - Permit 00040884
Plan Review Stops For Permit 00040884
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-07-25 Cont ID  
Sent By lmartine Date 2000-07-25 Time 17:43 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-06-01 Cont ID  
Sent By lmartine Date 2000-06-01 Time 16:55 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING COMMENTS
 -------------------
 1]SATISFY COUNTY IMPACT FEE REQUIREMENTS
 2]SUBMIT LIFE SAFETY PLAN FOR EGRESS TO
 ENTIRE BUILDING.
 3]EXPLAIN SMALL STAGE AT 2ND FLOOR [MAY
 BE REQUIRED TO BE HANDICAP ACCESSIBLE]
 4]PROVIDE CLEAR SCOPE OF WORK,PLANS SHOW
 MAJOR RENOVATION.
 5]PROVIDE ACCURATE SQUARE FOOT COUNT.
 6]EXPLAIN FUTURE OPENING NOTES AT 2ND
 FLOOR PLAN AND 4TH FLOOR RESIDENTIAL
 NOTE.
 7]2 APPROVED EXITS ARE REQUIRED FROM
 EACH FLOOR LEVEL.
 8]SUBMIT FIRE SPRINKLER PLAN.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-12-14 Cont ID  
Sent By dpalmer Date 2000-12-14 Time 22:31 Rev Time 0.00
Received By dpalmer Date 2000-12-14 Time 22:31 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT THE ELECTRICAL
 SHEETS THAT WERE SUBMITTED DID NOT HAVE
 THE CHANGES CLOUDED OR OUTLINED.
 ALSO THERE WAS NO INDICATION THAT THE
 PLANS WERE COMPLETELY RE-DRAWN??
  
  
 PLEASE SEE NOTES FROM BLDG PLAN REVIEW.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-05-15 Cont ID  
Sent By dpalmer Date 2000-05-15 Time 16:45 Rev Time 0.00
Received By dpalmer Date 2000-05-15 Time 16:45 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2000-06-01 Cont ID  
Sent By lmartine Date 2000-06-01 Time 17:17 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-12-21 Cont ID  
Sent By mcarsill Date 2000-12-20 Time 13:49 Rev Time 0.00
Received By mcarsill Date 2000-12-20 Time 13:48 Sent To  
Notes
2001-01-08 00:00:001) THE SECOND FLOOR PLAN ON PAGE E-1
 IS WHAT TYPE OF OCCUPANCY. WHAT IS
 THE SQUARE FOOTAGE.
 2) DESCRIBE OPENING AT CURVED STAIR
 AT OPENING INTO BUILDING TO THE WEST
 AT THE SECOND LEVEL.
 3) NO FIRE SPRINKLERS SHOWN ON FOURTH
 FLOOR.
 4) NO SMOKE DETECTION EQUIPMENT SHOWN
 ON THE FOURTH FLOOR.
 5) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON THE PLANS.
 6) THE SINGLE MEANS OF EGRESS IS NOT
 PERMITTED FROM THE LIVE WORK LOFT
 PER BUILDING CODE REQUIREMENTS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-05-30 Cont ID  
Sent By mcarsill Date 2000-05-30 Time 16:40 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISH IN EXITS SHALL BE
 CLASS A OR B.
 2) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE INSTALLATION OF THE FIRE ALARM
 SYSTEM. CUT SHEETS REQUIRED ON ALL
 DEVICES PLANNED. SYSTEM TO BE MONITORED
 BY A LICENSED UL LISTED CENTRAL STATION.
 3) NEW STAIRS TO COMPLY WITH
 REQUIREMENTS FOR NEW STAIRS, NFPA 101,
 1985 EDITION.
 4) CURVED STAIRS TO COMPLY WITH
 NFPA 101, 1985 EDITION.
 5) SUBMIT DRAWINGS FOR FIRE SPRINKLER
 SYSTEM NOTED ON PLANS.
 6) GUARDS AND HANDRAILS TO COMPLY
 WITH NFPA 101, 1985 EDITION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-12-26 Cont ID  
Sent By ndenmark Date 2000-12-26 Time 07:39 Rev Time 0.33
Received By ndenmark Date 2000-12-26 Time 07:39 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1. RE: NOTE ON SHAFT REMOVAL OR MODIFIC-
 ATION, 1997 SMC 610.4 DUCTS EXTENDING
 THROUGH MORE THAN ONE FLOOR TO BE PROTE-
 CTED BY SHAFT ENCLOSURE HAVING A FIRE
 RESITANCE NOT LESS THAN 2 HRS FOR A BUIL
 DING 4 STORIES AND MORE IN HEIGHT. PLAN
 UNCLEAR AS TO WHAT WILL BE CHANGED. THIS
 CODE SHALL BE COMPLIED WITH FOR ANY
 CHANGES.
 2. LOCAL AMENDMENTS REQUIRE MINIMUM 18"
 CLEARANCE BETWEEN ROOF SURFACE AND
 BOTTOM OF SUPPORT STRUCTURE OF STAND.
 PLEASE UPDATE STAND PRODUCT APPROVAL,
 PLAN INDICATES EXPIRED DADE CO. APPROVAL
 3. NOTE 5 AND 6 SHOW OUTSIDE AIR AND
 EXHAUST AIR OUTLET NEXT TO EACH OTHER
 NOTE 10 FT SEPARATION REQUIRED AS MIN-
 IMUM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-05-24 Cont ID  
Sent By cthirben Date 2000-05-24 Time 14:03 Rev Time 0.00
Received By cthirben Date 2000-05-24 Time 14:09 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 18" HEIGHT MIN. FROM THE TOP OF FINISHED
 ROOF TO THE BOTTOM OF UNIT ON THE UNIT.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-12-15 Cont ID  
Sent By jleech Date 2000-12-15 Time 14:53 Rev Time 1.00
Received By jleech Date 2000-12-15 Time 14:53 Sent To  
Notes
2001-01-08 00:00:001.HI-LOW DRINKING FOUNTAIN REQUIRED SPC
 TABLE 407 AND MUST MEET FACBC 4.1.3
 (10).
  
 2.SHOW MEASUREMENTS OF HANDICAP BATHROOM
 STALLS.INCLUDE TURNING CIRCLES.
  
 3.SHOW MEASUREMENTS FOR OTHER PARTITIONS
 IN BATHROOMS.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-06-01 Cont ID  
Sent By lmartine Date 2000-06-01 Time 17:18 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2000-06-01 Cont ID  
Sent By lmartine Date 2000-06-01 Time 17:18 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***