Plan Review Details - Permit 00040867
Plan Review Stops For Permit 00040867
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-07-27 Cont ID  
Sent By lsmith Date 2000-07-27 Time 08:49 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00ADD'L WALLS IN BATHS TO ADD PLUMBING FIX

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-05-05 Cont ID  
Sent By hpiskura Date 2000-05-05 Time 15:00 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-06-28 Cont ID  
Sent By dpalmer Date 2000-06-28 Time 20:55 Rev Time 0.00
Received By dpalmer Date 2000-06-28 Time 20:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-06-05 Cont ID  
Sent By dpalmer Date 2000-06-05 Time 16:28 Rev Time 0.00
Received By dpalmer Date 2000-06-05 Time 16:27 Sent To  
Notes
2001-01-08 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT OUTLET SPACING
 TO MEET LOCAL CODE; 210-50 EVERY 20` OF
 UNENCUMBERED WALL.
  
 2)NOTE: YOUSHOW ON E-4 TWO DIFFERENT
 FEEDER SCHEDULES?? PLEASE SHOW CORRECT
 SCHEDULE. ONE SHOWS 2-SETS OF 500 AND
 THE OTHER SHOWS 3-SETS OF 600 MCM??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL. 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-03 Cont ID  
Sent By dpalmer Date 2000-05-03 Time 19:40 Rev Time 0.00
Received By dpalmer Date 2000-05-03 Time 19:40 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: NEED TO SHOW THE REQ`D OUTLETS
 FOR SHOW WINDOWS AS PER 210-62
 REVISE PANEL SCHEDULE.
  
 2)NOTE: NEED TO SUBMIT THE LOAD CALCS
 SHOWING ALL CONTINUOUS LOADS AT 125%
 THIS WOULD BE LIGHTING OR ANY OTHER LOAD
 EXPECTED TO RUN FOR 3 OR MORE HOURS PER
 ART;22-3-B-7 AND 210-20
  
 PLEASE SUBMIT THE ABOVE INFORMATIONFOR
 REVIEW. PLANS WOULD HAVE PASSED WITH
 PROVISO BUT THEY WERE COMING BACK FOR
 OTHER COMMENTS. IF THERE ARE ANY QUEST-
 -IONS PLEASE CALL 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-06-08 Cont ID  
Sent By rturnque Date 2000-06-08 Time 14:26 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-04-20 Cont ID  
Sent By rturnque Date 2000-04-20 Time 10:38 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE FIRE SPRINKLER DRAWINGS
 PROVIDE SHOP DRAWINGS FOR FIRE ALARM
 SYSTEM AND FIRE SPRINKLER SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-08-29 Cont ID  
Sent By ndenmark Date 2000-08-29 Time 15:27 Rev Time 0.25
Received By ndenmark Date 2000-08-29 Time 15:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-06-07 Cont ID  
Sent By cthirben Date 2000-06-07 Time 09:29 Rev Time 1.00
Received By cthirben Date 2000-06-07 Time 09:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-05-04 Cont ID  
Sent By ndenmark Date 2000-05-04 Time 11:34 Rev Time 1.00
Received By ndenmark Date 2000-05-04 Time 11:34 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
 1) OUTSIDE AIR PER ASHRAE 62-89 REQUIRED
 2) PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2
 3) OFFICE AREA SHOWS NO VENTILATION
 4) STOCKROOM SHOWS NO VENTILATION
 VENTILATION REQUIRED FOR ALL PORTIONS OF
 BUILDINGS REQUIRED PER 1997 SMC 403

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-07-13 Cont ID  
Sent By tlarge Date 2000-07-13 Time 10:00 Rev Time 0.50
Received By tlarge Date 2000-07-13 Time 10:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status N Date 2000-07-05 Cont ID  
Sent By tlarge Date 2000-07-05 Time 12:03 Rev Time 0.00
Received By tlarge Date 2000-07-05 Time 12:02 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 THERE ARE LESS THAN THE REQUIRED NUMBER
 OF SANITARY FACILITIES IN THE WOMEN'S
 RESTROOM.REVISED PLANS ARE REQUIRED AND
 PLUMBING PERMIT SHALL NOT BE ISSUED
 UNTIL PLUMBING PLANS ARE APPROVED.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-07-05 Cont ID  
Sent By tlarge Date 2000-07-03 Time 15:56 Rev Time 0.75
Received By pschmitz Date 2000-07-03 Time 15:56 Sent To  
Notes
2001-01-08 00:00:00THE MINIMUM NUMBER OF REQUIRED SANITARY
 FACILITIES SHALL COMPLY W/SPC TABLE 407
 OF SPC.THERE ARE NOT ENOUGH FIXTURES IN
 THE WOMEN'S RESTROOM.PLEASE COMPLY.THIS
 COMMENT IS NOT GOING AWAY.
  
 URINAL SHALL BE MOUNTED AT 17"MAX.TO THE
 RIM,NOT TO THE BOTTOM.FACBC SEC.4.18.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-07-05 Cont ID  
Sent By tlarge Date 2000-06-04 Time 07:38 Rev Time 1.00
Received By tlarge Date 2000-06-04 Time 07:38 Sent To  
Notes
2001-01-08 00:00:00THE MINIMUM REQUIRED PLUMBING FIXTURES
 SHALL COMPLY W/TABLE 407 OF THE SPC.THE
 NUMBER OF FIXTURES IN THE WOMEN'S REST-
 ROOM ARE INSUFFICIENT ACCORDING TO THE
 NOTED HABITABLE SQUARE FOOT AREA OF THE
 SPACE.
  
 THE SIZE OF THE HANDICAP TOILET STALLS
 DO NOT COMPLY W/FACBC SEC.4.17.3.SEE
 EXCEPTION:NEW CONSTRUCTION.THE LAVATORY
 CANNOT INFRINGE ON THE CLEAR FLOOR
 SPACE FOR THE WATER CLOSET.
  
 URINAL SHALL BE MOUNTED AT 17"MAX.TO THE
 RIM,NOT THE BOTTOM OF THE URINAL.FACBC
 4.18.
  
 A CLEANOUT IS REQD.IN THE UPSTREAM END
 OF THE BUILDING DRAIN PER SPC SEC.710.2
  
 NOTE:SHT.P-1-THE SQUARE FOOTAGE PER
 PERSON FOR THIS OCCUPANCY PER TABLE 407
 OF THE SPC IS 200 SQ.FT.THE CODE SEC.
 403.1 OF THE SPC YOU REFERENCED ON THE
 PLAN REFERS TO THE CLEANING OF PLUMBING
 FIXTURES,NOT THE OCCUPANT LOAD.MY
 CALCULATIONS SHOW 29,465 SQ.FT.WHICH
 EQUALS AN OCCUPANT LOAD OF 148 PERSONS.
 (CALCULATIONS ARE FROM HABITABLE FLOOR
 SPACE SHOWN ON A-2.)

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-05 Cont ID  
Sent By tlarge Date 2000-04-30 Time 10:06 Rev Time 1.00
Received By tlarge Date 2000-04-30 Time 10:06 Sent To  
Notes
2001-01-08 00:00:00SHOW SQ.FOOTAGE OF HABITABLE FLOOR SPACE
 ON PLANS TO ENSURE COMPLIANCE W/SPC
 TABLE 407 FOR MIN.PLUMBING FIXTURE REQS.
  
 LAVATORIES ARE REQUIRED IN THE
 ACCESSIBLE STALLS PER FLA.ACCESS.CODE
 FOR BUILDING CONSTRUCTION SEC.4.17.3.
 RESTROOMS SHALL FULLY COMPLY W/FACBC
 OCT.1997 EDITION.
  
 SHOW INSIDE CLEAR DIMENSIONS (LXW) OF
 ACCESSIBLE STALLS AND STANDARD STALLS.
 COMPLY W/FACBC 4.17.3.,FIG.#30, SPC SEC.
 403.4.
  
 SHT.A-4-ACCESSIBLE WATER CLOSET SHALL BE
 18"FROM WALL,NOT 36" AS SHOWN PER FACBC
 FIGURE 30.
  
 SHOW HEIGHT OF URINAL.COMPLY W/FACBC SEC
 4.18.
  
 MIN.CLEAR FLOOR SPACE UNDER DRINKING
 FOUNTAIN SHALL BE 27"PER FACBC SEC.4.15.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY FIXED LADDER
 OR RELOCATE WATER HEATER TO FLOOR.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1,610.4.2.
  
 SHOW REQD.WHEELCHAIR TURNING SPACE IN
 RESTROOMS PER FACBC SEC.4.2.3.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved