Plan Review Details - Permit 00040838
Plan Review Stops For Permit 00040838
Review Stop E ELECTRICAL
Rev No 2 Status N Date 2000-08-01 Cont ID  
Sent By dpalmer Date 2000-08-01 Time 20:03 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE PERMIT #00040835

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-17 Cont ID  
Sent By jleahy Date 2000-05-17 Time 10:01 Rev Time 2.30
Received By jleahy Date 2000-05-17 Time 09:56 Sent To  
Notes
2001-01-08 00:00:001- PER ARTICLE 500-3A, AND B YOU NEED TO
 LAYOUT THE CLASS LOCATIONS ON THIS
 JOB.SHOW ALL HAZARDOUS LOCATIONS!!!
  
 2- NO AIC RATINGS FOR CIRCUIT BREAKERS
 SHOWN ON PANEL SCHEDULES

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-05-08 Cont ID  
Sent By mgonzale Date 2000-05-08 Time 13:11 Rev Time 3.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISO
 ON SHEET C-4 ON THE PARTIAL SITE PLAN
 THE NOTES UNDER THE NORTH ARROW ARE CUT
 OFF PLEASE MAKE VIEWPORT LARGER
 PLEASE BE AWARE THAT SOME AREAS WHERE
 PIPING IS BEING INSTALLED THERE ARE
 EXISTING WATERMAINS THAT MUST STAY
 ACTIVE SINCE THEY SERVICE FIRE HYDRANTS.
  
 PLANS ON BOARD 6/26/00 (PASSED WITH
 PROVISO)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status A Date 2000-07-11 Cont ID  
Sent By ndenmark Date 2000-07-11 Time 13:34 Rev Time 0.50
Received By ndenmark Date 2000-07-11 Time 13:33 Sent To  
Notes
2001-01-08 00:00:00ACCEPTED BY LETTER OF AFFIDAVIT
 SEE ORIGINAL ATTACHED TO OFFICE SET OF
 PLANS
 REPORTS ON MECHANICAL INSPECTIONS TO BE
 SUBMITTED TO BUILDING DIVISION
 CONTACT THIS OFFICE (659-8096 EXT 8221)
 FOR INFORMATION ON SUBMITTING REPORTS

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-06-20 Cont ID  
Sent By tlarge Date 2000-06-20 Time 09:05 Rev Time 1.00
Received By tlarge Date 2000-06-20 Time 09:05 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
 SIZE OF SCUPPERS SHALL COMPLY W/APPENDIX
 "A" OF SPC.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-08 Cont ID  
Sent By tlarge Date 2000-05-08 Time 11:32 Rev Time 3.50
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00SHT.A-5-SUBMIT DETAIL OF SCUPPERS.SHOW
 DIMENSIONS(LXW) AND CALCULATIONS.COMPLY
 W/APPENDIX "A" OF SPC.
  
 SHT.S-4-SHOW TERMINATION PT.OF 4"DRAIN
 FROM OZONE CONTACT POINT.
  
 SHT.M-9-SHOW TERMINATION POINT OF FLOOR
 DRAINS IN POTASSIUM PERMANGANATE AREA.
  
 A BACKFLOW PREVENTION DEVICE SHALL BE
 INSTALLED ON EACH POTABLE WATER SUPPLY
 TO EACH BUILDING PER SPC SEC.606.1.601.6
  
 INDICATE BUILDING OCCUPANCY ON PLAN PER
 SBC AMENDED COUNTY CODE SEC,301.2,301.3.
  
 INDICATE OCCUPANT LOAD ON PLANS FOR THE
 PLANT.SHOW LOCATION,TYPE AND NUMBER OF
 SANITARY FACILITIES FOR PLANT PERSONNEL.
 SPC 407.1.3.