Plan Review Details - Permit 00040810
Plan Review Stops For Permit 00040810
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-10-25 Cont ID  
Sent By jwitmer Date 2001-10-25 Time 07:27 Rev Time 1.50
Received By jwitmer Date 2001-10-25 Time 07:27 Sent To  
Notes
2001-10-25 00:00:00PROVISO PRODUCT APPROVAL FOR OVERHEAD,
 DOORS BEFORE FRAMING INSPECTION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-07-03 Cont ID  
Sent By jwitmer Date 2001-07-03 Time 16:33 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-03 00:00:00BUILDING PLAN REVIEW
 PERMIT # 00040810
 1156 CLARE AVENUE
 PHONE 659-0019
  
 1)- IMPACT FEES TO BE PAID TO THE
 COUNTY BEFORE THE PERMIT CAN BE ISSUED.
  
 2)- THESE PLANS SHOW IN THE TITLE BLOCK
 THAT THEY WERE PREPARED BY ARCH. M.
 CORBITT, THEY NEED THE ARCH. OF RECORD
 TO SIGN & SEAL PLANS, THAT ARE TO BE FOR
 PUBLIC RECORD.
  
 3)- MISSING ARE THEPRODUCT REPORTS FOR
 DOORS, WINDOWS & ROOFING MATERIALS. DADE
 COUNTY OR SBCCI REPORT ARE ACCEPTED.
 SBC 1606.4.1 AMEND/ 1707.4.1.
  
 4)_ SBC 104.2 SHOW AN INTERIOR PARTITION
 CONSTRUCTION DETAIL.
  
 5)- THE PROPOSED BUILDING IS LOCATED IN
 A FIRE ZONE, SHOW THE FIRE DESIGN NUMBER
 FOR THE EXTERIOR WALLS, WALLS WILL
 REQUIRE A 2 HR RATING.
  
 6)- SBC 1503.1.2.3. SHOW HOW ROOF DRAIN-
 AGE WILL OCCUR?
  
 7)- SBC 1804.2 AMEND. SOILS REPORT RE-
 QUIRED.
  
 8)- HANDICAPPED RAMP DOESN'T COMPLY WITH
 THE RAMP RISE & RUN. CHECK THE FINISH
 FLOOR HEIGTH OF 15.8' FLOOR ELEVATION
 TO THE 10.10' AT THE ACCESS RAMP. ALSO
 HOW DO WE ACCOMPLISH GETTING TO THE LIFT
 ? DETAILS ON THE LIFT AS WELL AS THE
 SECOND FLOOR LANDING.
  
 9)- SBC 1606.2.4 (MWFRS) INDICATE ON THE
 PLAN THE WIND PRESSURE ZONES FOR THE
 OPENINGS, WALLS & ROOF.
  
 JIM WITMER
 BUILDING PLAN REVIEW
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-27 Cont ID  
Sent By hpiskura Date 2001-03-27 Time 10:02 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-03-27 00:00:00PROPERTY IS IN FLOOD ZONE A9 BFE 13.0
 PROVIDE CERTIFICATION ON APPROPRIATE
 FEMA FORM
  
 PROVIDE ENERGY CODE CALCULATIONS.
  
 IMPACT FEES MUST BE PAID TO THE COUNTY,
 CALL 233-5025 FOR MORE INFORMATION.
  
 PLANS ARE REQUIRED TO BE SIGNED, SEALED
 AND DATED BY THE ARCHITECT.
  
 PROVIDE PRODUCT APPROVALS FORE THE
 DOORSAND ROOF COVERING.
  
 SHOW AN INTERIOR PARTITION DETAIL.
  
 SHOW THE FIRE DESIGN NUMBER FOR THE
 REQUIRED 2 HR RATED EXTERIOR WALLS.
  
 SHOW THE METHOD OF ROOF DRAINAGE.SEE
 SBC 1503.1.2.3.
  
 A SOIL INVESTIGATIION IS REQUIRED.SEE
 SBC 1804..2 AS AMENDED BY THE CITY.
  
 SHOW THE HC CURB CUTS TO COMPLY WITH 4.7
 OF THE FACBC.
  
 SHOW HOW THE C AND D COLUMNS PENETRATE
 THE SECOND FLOOR.
  
 SHOW HOW THE HC LIFT WILL TERMINATE AT
 THE SECOND FLOOR.
  
 SHOW THE CODES AND STANDARDS USED FOR
 THE DESIGN.INCLUDING EDITION.
  
 PROVIDE A SKETCH OF THE WIND ZONES AND
 THEIR PRESSURES FOR THE WALLS AND ROOF.

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2001-10-26 Cont ID  
Sent By dpalmer Date 2001-10-26 Time 09:51 Rev Time 0.00
Received By dpalmer Date 2001-10-26 Time 09:51 Sent To  
Notes
2001-10-26 00:00:00PULLED FROM REVIEW PER CONTRACTOR

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-10-22 Cont ID  
Sent By dpalmer Date 2001-10-22 Time 22:48 Rev Time 0.00
Received By dpalmer Date 2001-10-22 Time 22:48 Sent To  
Notes
2001-10-22 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE SAME NOTES
 FROM PREVIOUS REVIEW ON 6/13/01 WERE
 NOT ADDRESSED? ALSO SOME NOTES FROM
 4/2/01?
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW
 AND SUBMIT THE INFORMAITON FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-06-13 Cont ID  
Sent By dpalmer Date 2001-06-13 Time 20:38 Rev Time 0.00
Received By dpalmer Date 2001-06-13 Time 20:38 Sent To  
Notes
2001-06-13 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT THERE ARE NO
 CONDUCTOR SIZES /OR CONDUIT FROM METER
 CAN TO MAIN AND FROM MAIN TO PANEL.
  
 2) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 3)NOTE: PLEASE NOTE THAT LOCATION OF
 SERVICE EQUIPMENT IS NOT SHOWN ON PLANS
 PLEASE SHOW.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATING WAS SHOWN
 FOR PANEL BUT NOT FOR MAIN?
 PLEASE SHOW. IF FUSED, PLEASE GIVE AIC
 OF FUSES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-02 Cont ID  
Sent By dpalmer Date 2001-04-02 Time 22:18 Rev Time 0.00
Received By dpalmer Date 2001-04-02 Time 22:16 Sent To  
Notes
2001-04-02 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT PER LOCAL CODE
 OUTLET SPACINGTO MEET COUNTYWIDE AND C
 ITY WIDE ART;210-50. FOR STORAGE AND/OR
 OFFICE.
  
 2)NOTE: PLEASE PLACE ALL BRANCH CIRCUIT
 #`S ON PLANS AND CORRLATE WITH PANEL
 SCHEDULES. PLEASE SUBMIT PANEL SCHEDULES
 215-5
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 5)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-10-15 Cont ID  
Sent By mamini Date 2001-10-15 Time 09:37 Rev Time 3.00
Received By mamini Date 2001-10-15 Time 09:37 Sent To  
Notes
2001-10-15 00:00:00PASSED WITH PROVISOS :
 1. PLEASE CONTACT PUBLIC UTILITIES
 ENGINEERING SERVICES MR. MANNY GONZALEZ
 659-8040 FOR INSTALLATION / LOCATIONS
 OF THE PROPOSED METERS.
 2. A CLEAN-OUT WILL NEED TO BE INSTALLED
 IN SANITARY LATERAL, ON THE PROPERTY,
 AT BACK OF THE SIDEWALK, IF NOT ALREADY
 INSTALLED.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-03-22 Cont ID  
Sent By mamini Date 2001-03-22 Time 09:40 Rev Time 2.00
Received By mamini Date 2001-03-22 Time 09:01 Sent To  
Notes
2001-03-22 00:00:00FAILED:
 1. PLEASE SHOW THE EXACT LOCATION OF
 CONNECTIONS TO THE SERVICE LINES.ALSO
 SHOW THE LOCATION OF METERS.
 2. A CLEAN OUT WILL NEED TO BE INSTALLED
 IN SANITARY LATERAL, ON THE PROPERTY,
 AT BACK OF THE SIDEWALK,IF NOT ALREADY
 INSTALLED.
 3. A SEPARATE IRRIGATION METER IS
 SUGGESTED TO SAVE ON MONTHLY BILL. A
 PROPER BACKFLOW PREVENTER WILL NEED TO
 BE INSTALLED ON THIS LINE.
 4. ALL BACKFLOW PREVENTERS SHOULD BE
 HIDDEN FROM VIEW WITH SHRUBS PRIOR TO
 ACTIVATION.
 5. PLEASE PROVIDE POLLUTION PREVENTION
 PLAN.THE PLAN SHALL BE INSTALLED IN
 FIELD PRIOR TO ANY EARTHWORK. THE
 POLLUTION PREVENTION PLAN SHALL BE KEPTH
 ON SITE AT ALL TIME DURING CONSTRUCTION.
 6. PROVIDE PERVIOUS & IMPERVIOUS
 CALCULATIONS ON A 8 1/2 X 11 SHEET AND
 INCLUDE PROPERTY NAME , ADDRESS,
 PROPERTY CONTROL NUMBER.THIS SHOULD
 BE SIGNED AND SEALED BY THE ENGINEER OF
 RECORD.IF ANY QUESTION PLEASE CONTACT
 561- 659-8096 EXT. 8492

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-04-05 Cont ID  
Sent By mcarsill Date 2001-04-05 Time 14:13 Rev Time 0.00
Received By mcarsill Date 2001-04-05 Time 14:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-04-20 Cont ID  
Sent By rturnque Date 2000-04-20 Time 11:02 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-03-22 Cont ID  
Sent By ndenmark Date 2001-03-22 Time 14:05 Rev Time 0.25
Received By ndenmark Date 2001-03-22 Time 14:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-04-02 Cont ID  
Sent By jleech Date 2001-04-02 Time 12:40 Rev Time 0.50
Received By jleech Date 2001-04-02 Time 12:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2001-10-11 Cont ID  
Sent By sgraham Date 2001-10-11 Time 11:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2000-04-24 Cont ID  
Sent By gjoyce Date 2000-04-24 Time 09:46 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS LEVEL 1 SITE PLAN REVIEW