Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-06-23 Cont ID  
Sent By dpalmer Date 2000-06-23 Time 13:01 Rev Time 0.00
Received By dpalmer Date 2000-06-23 Time 13:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-16 Cont ID  
Sent By dpalmer Date 2000-05-16 Time 19:17 Rev Time 0.00
Received By dpalmer Date 2000-05-16 Time 19:16 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: YOU HAVE NOTED ON RISER DIAGRAM
 TO USE CURRENT LIMITING FUSES?? BUT YOU
 ARE SHOWING A MAIN BRKR PANEL? PLEASE
 CORRECT.IF THERE IS GOING TO BE A FUSED
 DISCONNECT THEN PLEASE SHOW.
 PLEASE PROVIDE THE AIC RATING OF PANELS,
 MAIN DISC, OR FUSES. 215-5 AND 110-9
  
 2)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. AS REQ`D BY 210-8-A-6.
  
 3)NOTE; PLEAS EINCLUDE BLDG. STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM
 AS PER 250-50./215-5
  
 4)NOTE: PLEASE INCLUDE THE REQ`D DEDICAT
 -ED BATH(S) CIRCUIT(S) ON PANEL SCHEDULE
 ASPER 210-11-C-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
 -E CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-18 Cont ID  
Sent By cthirben Date 2000-04-18 Time 13:29 Rev Time 1.00
Received By cthirben Date 2000-04-18 Time 13:26 Sent To  
Notes
2001-01-08 00:00:00 
 ****************PROVISO*****************
 REQUIRE TO INDICATE ON PLANS THE
 LOCATION OF EXHAUST FANS IN BATHROOMS
 AND VENTS FOR DRYER

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-06-26 Cont ID  
Sent By tlarge Date 2000-06-26 Time 09:14 Rev Time 0.33
Received By tlarge Date 2000-06-26 Time 09:14 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY RISER THAT CORRELATES W/
 FLOOR PLAN PRIOR TO PLBG.INSPECTION.
  
 GAS WATER HEATER SHALL BE PROTECTED PER
 SGC SEC.402.7.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-04-18 Cont ID  
Sent By tlarge Date 2000-04-18 Time 11:48 Rev Time 0.33
Received By tlarge Date 2000-04-18 Time 11:43 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 SUBMIT REVISED SANITARY RISER DIAGRAM
 PRIOR TO ROUGH INSPECTION.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-07-03 Cont ID  
Sent By jgomez Date 2000-07-03 Time 09:12 Rev Time 2.00
Received By jgomez Date 2000-07-03 Time 09:12 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE PRODUCT APPROVAL FOR BUTT
 GLAZING SYSTEM AT MASTER BATHROOM.
 2-PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS THAT MATCHES SIZE SHOWN ON
 ARCHITECTURAL DRAWINGS.
 3-PROVIDE COMPLETE INSTALLATION DETAIL
 FOR AHU IN ATTIC. SPECIFY ALL
 FASTENERS. (LETTER FROM ENGINEER WILL
 BE ACCEPTABLE. PROVIDE INFORMATION ON
 DRAWINGS FOR FUTURE SUBMITTALS).
 4-PROVIDE COPIES OF SOIL TESTS DONE AS
 PER SECTION 1804.2.7.3 CITY AMENDMENTS
 5-INSWING ENTRY DOOR PRODUCT APPROVAL
 SUBMITTED IS FOR SINGLE DOOR ONLY.
 PROVIDE PRODUCT APPROVAL FOR INSWING
 DOUBLE DOORS AS SHOWN ON FLOOR PLAN.
 6-PROVIDE STRUCTURAL BUCK DETAIL WITH A
 2X BUCK AS REQUIRED ON DOORS PRODUCT
 APPROVAL.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-06-26 Cont ID  
Sent By jgomez Date 2000-06-26 Time 18:44 Rev Time 2.00
Received By jgomez Date 2000-06-26 Time 18:44 Sent To  
Notes
2001-01-08 00:00:00SECOND CHECKLIST:
 1-SURVEY:
 -PROFESSIONAL ENGINEER SHOULD NOT SEAL
 ORIGINAL DOCUMENTS. SEC 61G15-23.002.
 2-PROVIDE PRODUCT APPROVAL FOR BUTT
 GLAZING ASSEMBLY, FIREPLACE, INSWING
 ENTRY DOORS.
 -SLIDING GLASS DOORS PRODUCT APPROVAL
 DOESN'T QUALIFY FOR THE SIZE OF DOORS
 SHOWN ON PLANS AND ELEVATIONS.
 3-ENGINEER TO SIGN, SEAL AND DATE DWGS
 WITH THE EXTERIOR ELEVATIONS. THEY
 SHOW THE DESIGN PRESSURES AT EXTERIOR
 OPENINGS CALCULATED FOR THIS BUILDING.
 4-PROVIDE COMPLETE INSTALLATION DETAIL
 FOR AHU IN ATTIC. SPECIFY ALL
 FASTENERS. SEC 104.2.2 CITY AMENDMENTS
 5-PROVIDE SAFETY GLASS AT BEDROOM #2.
 SECTION 2405.2 SBC 1997.
 6-REVISE SIZE OF CEILING FANS. SEE TABLE
 6-6 OF FLORIDA ENERGY EFICIENCY CODE
 FOR BUILDING CONSTRUCTION, 1997 ED.
 7-PROVIDE COPIES OF THE SOIL TESTS
 RESULTS DONE AS PER SECTION 1804.2.7.3
 OF CITY AMENDMENTS TO SBC 1997.
 8-OWES $669.73 FOR LOW VALUATION AND
 RADON FEES.(RECEIPT TO PAY ATTACHED).
 9-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 10-CLARIFY WHY ORIGINAL DRAWING A-1 WAS
 NOT REVISED. INSTEAD, ANOTHER REVERSED
 PLAN WAS SUBMITTED, THEREFORE NOT
 MATCHING THE OTHER PLANS.
 11-SEE COMMENTS ON PLANS AND UPDATE/
 REVISE AS REQUIRED.
 -SEE ROOF TRUSS LAYOUT FOR COMMENTS.
  
 NOTES:
 1-SEE COMMENTS BY OTHER TRADES.
 2-PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-06 Cont ID  
Sent By jgomez Date 2000-06-06 Time 11:37 Rev Time 3.00
Received By jgomez Date 2000-06-06 Time 11:37 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-SURVEY;
 -PROFESSIONAL ENGINEER SHOULD NOT SEAL
 ORIGINAL DOCUMENTS. SEC 61G15-23.002
 FLORIDA BOARD OF PROFESSIONAL ENGINEER
 2-PROVIDE PRODUCT APPROVAL FOR BUTT
 GLAZING ASSEMBLY, FIREPLACE, ENTRY-
 DOORS ("INSWING").
 -SLIDING GLASS DOORS PRODUCT APPROVAL
 DOESN'T WORK FOR THIS HOUSE. SEE DWG 1
 OF 6 OF SGD PRODUCT APPROVAL AND SIZE
 OF DOORS IN ARCHITECTURAL DRAWINGS.
 3-ENGINEER TO SIGN, SEAL AND DATE DWGS
 WITH THE EXTERIOR ELEVATIONS ALSO.
 ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. SECTION 104.2.1 OF
 CITY AMENDMENTS.
 4-PROVIDE COMPLETE INSTALLATION DETAIL
 FOR AHU IN ATTIC. SPECIFY FASTENERS.
 SECTION 104.2.2 CITY AMENDMENTS.
 5-PROVIDE ATTIC ACCESS AT MAIN ROOF AND
 SPECIFY SIZE OF ATTIC ACCESS AT GARAGE
 SECTION 2309.6 SBC 1997.
 6-PROVIDE SAFETY GLASS. SEE PLANS FOR
 COMMENTS. SECTION 2405.2 SBC 1997.
 7-REVISE SIZE OF CEILING FANS. SEE TABLE
 6-6 OF FLORIDA ENERGY CODE, 1997 ED.
 8-PROVIDE COPIES OF THE SOIL TESTS
 RESULTS DONE AS PER SECTION 1804.2.7.3
 CITY AMENDMENTS.
 9-OWES $669.73 FOR LOW VALUATION FOR
 CONSTRUCTION AND RADON FEES.
 10-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
  
 NOTES:
 1-SEE COMMENTS BY OTHER TRADES.
 2-REVISE ALL PLANS AS REQUIRED AND BRING
 THIS SET OF MARKED DRAWINGS IN ORDER
 TO EXPEDITE THE REVIEW PROCESS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-13 Cont ID  
Sent By gjoyce Date 2000-04-13 Time 10:21 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved