Plan Review Details - Permit 00040494
Plan Review Stops For Permit 00040494
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-06-19 Cont ID  
Sent By lsmith Date 2000-06-19 Time 09:09 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO PER HHP 6/14/00

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-06-02 Cont ID  
Sent By hpiskura Date 2000-06-02 Time 09:37 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-01 Cont ID  
Sent By dpalmer Date 2000-09-01 Time 07:55 Rev Time 0.00
Received By dpalmer Date 2000-09-01 Time 07:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-24 Cont ID  
Sent By dpalmer Date 2000-08-24 Time 09:32 Rev Time 0.00
Received By dpalmer Date 2000-08-24 Time 09:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-05-03 Cont ID  
Sent By dpalmer Date 2000-05-03 Time 20:59 Rev Time 0.00
Received By dpalmer Date 2000-05-03 Time 20:59 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2000-08-18 Cont ID  
Sent By mgonzale Date 2000-08-18 Time 14:36 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PARKING LOT REFLECTS CHANGES THAT A PERM
 IT OR A REVIEW PANEL HAVE NOT APPROVED.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-05-10 Cont ID  
Sent By mgonzale Date 2000-05-10 Time 08:49 Rev Time 0.50
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED
 AS PER MY CONVERSATION WITH THE
 ARCHITECT, THERE WILL NOT BE ANY
 UTILITIES OR SITE CHANGES TO THIS
 PROPERTY ALL WORK IS PERFORMED INSIDE.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-05-10 Cont ID  
Sent By mgonzale Date 2000-05-05 Time 13:54 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00FAILED
 PLEASE PROVIDE PLANS FOR WATER, SEWER,
 STORM AND POLLUTION CONTROL.
 (SEE REVISION 2)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-05-30 Cont ID  
Sent By mcarsill Date 2000-05-30 Time 14:57 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) ADDRESS NOT SHOWN ON ELEVATION
 DRAWINGS.
 2) INTERIOR FINISHES ON WALLS AND
 CEILINGS SHALL BE CLASS A OR B.
 3) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE FIRE ALARM SYSTEM. PROVIDE CUT
 SHEETS FOR DUCT DETECTORS, HORN STROBES
 ETC.
 4) THE CANOPY SHOWN ON A.07.02 IS TO
 BE FIRE SPRINKLER PROTECTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-05-04 Cont ID  
Sent By cthirben Date 2000-05-04 Time 14:31 Rev Time 1.50
Received By cthirben Date 2000-05-04 Time 14:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-09-06 Cont ID  
Sent By tlarge Date 2000-09-06 Time 11:37 Rev Time 0.25
Received By tlarge Date 2000-09-06 Time 11:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-09-01 Cont ID  
Sent By tlarge Date 2000-09-01 Time 18:35 Rev Time 0.25
Received By tlarge Date 2000-09-01 Time 18:34 Sent To  
Notes
2001-01-08 00:00:00VENTING OF WATER CLOSETS SHALL COMPLY W/
 COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.3
 (WATER CLOSETS ARE ON WET VENTS AS
 DESIGNED-RELOCATE UPSTREAM FIXTURE
 BRANCH.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER
 561-659-8096,EXT.8377.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-01 Cont ID  
Sent By lsmith Date 2000-06-02 Time 09:45 Rev Time 0.10
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER PAUL SCHMITZ ON 6/19.00 SEE PLANS.
 TKL.8/1/00.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-20 Cont ID  
Sent By gjoyce Date 2000-04-20 Time 11:31 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***