Plan Review Details - Permit 00040468
Plan Review Stops For Permit 00040468
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-06-08 Cont ID  
Sent By lmartine Date 2000-06-08 Time 07:48 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-05-10 Cont ID  
Sent By lmartine Date 2000-05-10 Time 07:39 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-04-26 Cont ID  
Sent By lmartine Date 2000-04-26 Time 07:20 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING2ND REVIEW
  
 1]ENERGY CODE COMPLIANCE IS REQUIRED,SEE
 USE FORMS 400D-97 PROVIDED.
 2]FL.ACC.CODE SECT.4.1.6,ALTERATION OF
 EXISTING SPACE REQUIRES ACCESSIBILITY
 IMPROVEMENTS.FOLLOWING THE LIST OF
 PRIORITY ON PAGE 28,SEE #3 ACCESSIBLE
 RESTROOMS.
 3]FL.STATE STATUE 481.229,REQUIRES A
 LICENSED ARCHITECT TO PROVIDE DRAWINGS
 WHEN COST OF CONSTRUCTION EXCEEDS
 $25,000.
 4]PLEASE INCLUDE ELECTRICAL,MECHANICAL
 AND PLUMBING SPECIFICATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-04-17 Cont ID  
Sent By lmartine Date 2000-04-17 Time 11:37 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:001]COMMERCIAL RENOVATIONS REQUIRE FLA.
 ENERGY CODE CALCULATIONS.
 2]PROVIDE BUILDING DATA,TYPE OF CONSTR.
 AND FIRE PROTECTION CLASSIFICATION.
 3]SPECIFY STOREFRONTS AND DOORS.DETAIL
 RECEPTION AREA.
 4]PROVIDE SITE PLAN.SUBMIT EGRESS PLAN.
 5]CLERIFY STAIR AT EXISTING FIRE DOOR.
 6]RENOVATION OF SPACE MUST COMPLY WITH
 4.1.6 FL.ACC.CODE FOR ALTERATIONS.
 7]CONSTRUCTION VALUE IS LOW,SUBMIT COPY
 OF SIGNED CONTRACT FOR COMPLETE SCOPE
 OF WORK.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-06-06 Cont ID  
Sent By dpalmer Date 2000-06-06 Time 21:38 Rev Time 0.00
Received By dpalmer Date 2000-06-06 Time 21:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-05-30 Cont ID  
Sent By dpalmer Date 2000-05-30 Time 20:16 Rev Time 0.00
Received By dpalmer Date 2000-05-30 Time 20:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-05-18 Cont ID  
Sent By dpalmer Date 2000-05-18 Time 20:42 Rev Time 0.00
Received By dpalmer Date 2000-05-18 Time 20:42 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
  
 1)NOTE: SET #1, CHANGES ARE MADE IN
 PENCIL? THIS IS NOT ACCEPTED. PLEASE
 HAVE THE SHEET RE-DONE.
  
 2)NOTE: ALSO ALL CHANGES MUST BE MADE BY
 THE ARCHITECT/OR ENGINEER OF RECORD.
  
  
 3)NOTE: THE SECOND SET OF PLANS MUST
 ALSO BE SIGNED AND SEALED BY PERSON OF
 RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS PLEASE
 CALL 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-03 Cont ID  
Sent By dpalmer Date 2000-05-03 Time 21:04 Rev Time 0.00
Received By dpalmer Date 2000-05-03 Time 21:04 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT PLANS SHOWING ALL
 BRANCH CIRCUIT #`S ON PLANS.
  
 2)NOTE: SUBMIT REVISED PANEL SCHEDULE.
  
 3)NOTE:OUTLET SPACING TO MEET LOCAL
 AMENDMENTS. SEE 210-50 OF THE LOCAL CODE
  
 4)NOTE: SUBMIT LOAD CALCULATION AND SHOW
 EXISTING SERVICE SIZE. 215-5
 NOTE:LIGHTING IS CONTINUOUS FIG.@125%
 5)NOTEL PLEASE GIVE MORE DETAIL ON WHATS
 EXISTING AND WHAT IS NEW?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS CALL
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2000-06-02 Cont ID  
Sent By rturnque Date 2000-06-02 Time 10:08 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2000-05-18 Cont ID  
Sent By rturnque Date 2000-05-18 Time 09:49 Rev Time 0.25
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-04-25 Cont ID  
Sent By lmartine Date 2000-04-25 Time 16:44 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-04-11 Cont ID  
Sent By rturnque Date 2000-04-11 Time 10:02 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE FIRE SPRINKLER DRAWINGS.
 PROVIDE EXIT LIGHT ILLUMINATION OR
 INDICATE EXISTING EXIT LIGHT ILLUMINATIO
 N.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-06-07 Cont ID  
Sent By cthirben Date 2000-06-07 Time 14:54 Rev Time 1.00
Received By cthirben Date 2000-06-07 Time 14:54 Sent To  
Notes
2001-01-08 00:00:00PROVISO*********************************
 INDICATE ON PLANS WHERE THE EXHAUST FAN
 IS VENTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-06-02 Cont ID  
Sent By lsmith Date 2000-06-02 Time 09:06 Rev Time 0.10
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEPARATE PERMIT PER CONTRACTOR

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-06-06 Cont ID  
Sent By tlarge Date 2000-06-06 Time 07:28 Rev Time 0.50
Received By tlarge Date 2000-06-06 Time 07:28 Sent To  
Notes
2001-01-08 00:00:00RELOCATE H.C.BATH.
 PROVISO:SUBMIT SIGNED AND SEALED WATER
 RISER FOR REVIEW PRIOR TO PLBG.INSP.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-06-01 Cont ID  
Sent By tlarge Date 2000-06-01 Time 16:50 Rev Time 0.33
Received By tlarge Date 2000-06-01 Time 16:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-05-20 Cont ID  
Sent By tlarge Date 2000-05-20 Time 05:16 Rev Time 0.50
Received By tlarge Date 2000-05-20 Time 05:16 Sent To  
Notes
2001-01-08 00:00:00ALL PLANS AND ADDENDUMS SHALL BE SIGNED
 AND SEALED BY DESIGN PROFESSIONAL OF
 RECORD PER FLA.STATUTE.(INCLUDES WATER
 AND SANITARY RISER SHEETS.)
  
 WALLS IN TOILET ROOM SHALL BE NONABSORB-
 ENT TO HEIGHT OF 4' PER SBC 1204.2.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-06 Cont ID  
Sent By tlarge Date 2000-05-06 Time 09:19 Rev Time 0.65
Received By tlarge Date 2000-05-06 Time 09:19 Sent To  
Notes
2001-01-08 00:00:00DIMENSION FROM F.F.TO BOTTOM OF H.C.LAV.
 APRON SHALL BE 29"PER FACBC SEC.4.19.2.
  
 SUBMIT WATER SUPPLY RISER DIAGRAM FOR
 REVIEW.
  
 SIZE THE WASTE STACKS AND VENTS ON
 SANITARY RISER.COMPLY W/SPC SEC.920.2,
 920.4.
  
 WALLS IN TOILET ROOM SHALL BE NONABSORB-
 ENT TO A HEIGHT OF 4" PER SBC SEC.1204.2
  
 ARRANGE PLANS IN ORDER AND SUBMIT 2
 COMPLETE SETS.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.