Plan Review Details - Permit 00040275
Plan Review Stops For Permit 00040275
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-05-03 Cont ID  
Sent By dpalmer Date 2000-05-03 Time 09:03 Rev Time 0.00
Received By dpalmer Date 2000-05-03 Time 09:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-10-14 Cont ID  
Sent By jleech Date 2000-10-14 Time 10:37 Rev Time 0.33
Received By jleech Date 2000-10-14 Time 10:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-24 Cont ID  
Sent By cthirben Date 2000-04-24 Time 08:31 Rev Time 1.00
Received By cthirben Date 2000-04-24 Time 08:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-04-20 Cont ID  
Sent By tlarge Date 2000-04-20 Time 06:52 Rev Time 0.33
Received By tlarge Date 2000-04-20 Time 06:52 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-09-22 Cont ID  
Sent By jgomez Date 2000-09-22 Time 17:42 Rev Time 0.50
Received By jgomez Date 2000-09-22 Time 17:42 Sent To  
Notes
2001-01-08 00:00:00REVISION:
 -EXTENSION OF REAR PORCH.
  
  
  
  
 NOTE:
  
 -REMEMBER TO PROVIDE ALL INFORMATION
 REQUESTED ON PROVISO DATED 6-4-00 PRIOR
 TO INSTALLATION OR CONSTRUCTION IN
 ORDER TO AVOID DELAYS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-06-04 Cont ID  
Sent By jgomez Date 2000-06-04 Time 14:14 Rev Time 3.00
Received By jgomez Date 2000-06-04 Time 14:14 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE CURRENT PRODUCT APPROVAL FOR
 MASONRY.
 2-MULLION PRODUCT APPROVAL IS TO BE USED
 WITH SERIES 7500 SINGLE HUNG WINDOWS
 MULLED TOGETHER ONLY. PROVIDE MULLION
 PRODUCT APPROVAL FOR HORIZONTAL
 APPLICATIONS.
 -CLEARLY INDICATE MULLION SIZES AND
 FASTENERS TO BE USED IN THIS PROJECT.
 -PROVIDE UPDATED PRODUCT APPROVAL.
 3-PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS WITH TRANSOM ABOVE AS A
 SINGLE ASSEMBLY. SEE ARCHITECT'S PLANS
 4-PROVIDE STORM PANELS PRODUCT APPROVAL.
 -INDICATE SPECIFIC MOUNTING CONDITIONS
 AND ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES,
 MEAN ROOF HEIGHT, EDGE DISTANCE, PANEL
 SPAN AND STRUCTURE TO BE ANCHORED TO.
 5-UPDATE/REVISE ALL DRAWINGS AS REQUIRED
 SEE COMMENTS ON PLANS.
 6-PROVIDE COMPLETE FRAMING DETAILS AT
 ARCHED OPENINGS. SECTION 104.2.2 OF
 CITY AMENDMENTS.
 7-PROVIDE SOIL TEST REPORT WITH THE
 MINIMUM INFORMATION AS REQUESTED IN
 SECTION 1804.2.7.2 CITY AMENDMENTS.
 8-ATTIC ACCESS TO BE 22"X36" MIN. SEC.
 2309.6 SBC 1997. REVISE NOTE #7 ON A-2
 9-PROVIDE CURRENT PRODUCT APPROVAL FOR
 "LA PORTE" FRENCH DOORS.
 10-CLEARLY INDICATE ON PLANS AREAS TO
 HAVE SAFETY GLASS. SEC. 2405.2 SBC/97.
 11-ENERGY CALCULATIONS:
 -REVISE CEILING AREA CALCULATIONS. SEE
 SECTION 604.1.A.1 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.
 12-UPDATE NOTE #3 ON SHEET S-3. USE
 ASCE 7-95 AT 145 MPH.
 13-CLEARLY INDICATE ON ROOF FRAMING PLAN
 THE DETAILS SHOWN ON S-1 THAT APPLY TO
 THIS PROJECT.
 14-SPECIFY WHICH PRODUCT APPROVAL IS
 REFERRING TO IN DETAIL 3 OF SHEET A-5.
 GARAGE BUCK DETAIL.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-11 Cont ID  
Sent By gjoyce Date 2000-04-11 Time 10:44 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***