Plan Review Details - Permit 00040172
Plan Review Stops For Permit 00040172
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-07-29 Cont ID  
Sent By lmartine Date 2000-07-29 Time 11:49 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-04-20 Cont ID  
Sent By lmartine Date 2000-04-20 Time 15:04 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:001]TENANT SEPERATION REQUIRED.
 2]SUBMIT SITE PLAN FOR EGRESS APPROVAL.
 3]PROVIDE SECOND APPROVED EXIT FOR
 ALTERED AREA.
 4]SECTION 4.1.6[2.2.A]1997 FL.ACC.CODE
 REQUIRES ALTERED AREA ACCESSIBILITY
 TO BE IMPROVED BY UPTO 20%OF THE TOTAL
 CONSTRUCTION VALUE.
 5]SUBMIT ENERGY CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-09 Cont ID  
Sent By dpalmer Date 2000-08-09 Time 07:25 Rev Time 0.00
Received By dpalmer Date 2000-08-09 Time 07:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-20 Cont ID  
Sent By dpalmer Date 2000-07-20 Time 17:54 Rev Time 0.00
Received By dpalmer Date 2000-07-20 Time 07:22 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE: STILL NEED TO ADDRESS THE LOAD
 CALCULATION REQUEST FOR THE LOAD BEING
 ADDED ON EXISTING PANEL.
 PLEASE NOTE THAT ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125% (LIGHTING) ETC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-04-12 Cont ID  
Sent By dpalmer Date 2000-04-12 Time 18:46 Rev Time 0.00
Received By dpalmer Date 2000-04-12 Time 18:46 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUT
 #`S ON PLANS FOR ALL LIGHTING AND OUTLET
 -S.
  
 2)NOTE: SHOW LIGHTING THAT PERMIT APPL.
 SAYS THAT YOU ARE INSTALLING.
  
 3)NOTE: PROVIDE LOAD CALCULATION ON
 EXISTING MAIN TO BLDG.? BEFORE YOU CAN
 ADD NEW MAIN. ALSO SHOW WIRE SIZE FOR
 NEW PANEL/ MAIN, CONDUIT SIZE ETC.
  
 4)NOTE:PLEASE SUBMIT NEW LOAD CALC ON
 NEW PANEL AND PANEL SCHEDULE.
  
 5)NOTE: PLEASE PROVIDE AIC RATING OF
 EQUIPMENT MAINS. MAINS MUST BE RATED TO
 HANDLE THE AVAILABLE FAULT CURRENT.
 110-9/215-5
  
 6)NOTE: PLEASE SHOW A MORE DETAIL LAYOUT
 OF THE SERVICE AND THE TENANT SPACES
 AND WHERE EACH SERVICE FOR EACH TENANT -
 IS BEING SEPARATED BY FIRE WALLS.
 MAINS MUST BE GROUPED AND LABELED 1OF3,
 2OF 3,ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2000-07-20 Cont ID  
Sent By mgonzale Date 2000-07-20 Time 15:21 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00NO CIVIL PLANS TO REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-04-12 Cont ID  
Sent By rturnque Date 2000-04-12 Time 11:11 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-12-08 Cont ID  
Sent By jleech Date 2000-12-08 Time 15:12 Rev Time 0.50
Received By jleech Date 2000-12-08 Time 15:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-11-30 Cont ID  
Sent By jleech Date 2000-11-30 Time 08:17 Rev Time 0.75
Received By jleech Date 2000-11-30 Time 08:17 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1.ONE 3" VENT STACK IS REQUIRED IN
 BUILDING. SPC 904.3.1. SHOW COMPLETE
 PLUMBING ON SANITARY RISER DIAGRAM.
  
 2.DRINKING FOUNTAIN TO BE HIGH LOW
 TO ACCOMMODATEWHEELCHAIRS AND PEOPLE
 WHO HAVE TROUBLE BENDING AND STOOPING.
 FACBC 4.15.
  
 3.BATHROOM FACILITIES MUST MEET HANDICAP
 REQUIREMENTS SINCE BUILDING HAS BEEN
 DIVIDED.
  
 PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-11-17 Cont ID  
Sent By jleech Date 2000-11-17 Time 14:14 Rev Time 0.33
Received By jleech Date 2000-11-17 Time 14:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-11-14 Cont ID  
Sent By jleech Date 2000-11-14 Time 08:03 Rev Time 0.50
Received By jleech Date 2000-11-14 Time 08:03 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1.INFORMATION ON D.I. SYSTEM NOT
 SUBMITED.
 2.WATER DRAIN NOT SHOWN ON PLUMBING
 DIAGRAM.[DRAIN FOR D.I. SYSTEM]
 3.WATER RISER NOT CORRECT. RISER SHOWS
 TWO EYE WASH STATIONS BEFORE D.I.
 SYSTEM.
 4.HC ELEVATION W/C MEASUREMENT SHOULD
 BE 1'6" OF WALL NOT 2'.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-29 Cont ID  
Sent By tlarge Date 2000-10-29 Time 15:42 Rev Time 0.33
Received By tlarge Date 2000-10-29 Time 15:42 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT SANITARY AND WATER RISER
 DIAGRAMS FOR REVIEW THAT REFLECT ALL
 CHANGES TO THE PLUMBING SYSTEM.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 2)SUBMIT DETAILS ON "WATER DRAIN",
 "WATER INTAKE",AND WATER D.I. SYSTEM.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.