| Plan Review Stops For Permit 00040172 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-07-29 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-07-29 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-04-20 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-04-20 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1]TENANT SEPERATION REQUIRED. | | | 2]SUBMIT SITE PLAN FOR EGRESS APPROVAL. | | | 3]PROVIDE SECOND APPROVED EXIT FOR | | | ALTERED AREA. | | | 4]SECTION 4.1.6[2.2.A]1997 FL.ACC.CODE | | | REQUIRES ALTERED AREA ACCESSIBILITY | | | TO BE IMPROVED BY UPTO 20%OF THE TOTAL | | | CONSTRUCTION VALUE. | | | 5]SUBMIT ENERGY CALCULATIONS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-08-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-09 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-09 |
Time |
07:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-07-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-20 |
Time |
17:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-20 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** PROVISO ***************** | | | | | | 1)NOTE: STILL NEED TO ADDRESS THE LOAD | | | CALCULATION REQUEST FOR THE LOAD BEING | | | ADDED ON EXISTING PANEL. | | | PLEASE NOTE THAT ALL CONTINUOUS LOADS | | | ARE TO BE SHOWN AT 125% (LIGHTING) ETC. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-04-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-04-12 |
Time |
18:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-04-12 |
Time |
18:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUT | | | #`S ON PLANS FOR ALL LIGHTING AND OUTLET | | | -S. | | | | | | 2)NOTE: SHOW LIGHTING THAT PERMIT APPL. | | | SAYS THAT YOU ARE INSTALLING. | | | | | | 3)NOTE: PROVIDE LOAD CALCULATION ON | | | EXISTING MAIN TO BLDG.? BEFORE YOU CAN | | | ADD NEW MAIN. ALSO SHOW WIRE SIZE FOR | | | NEW PANEL/ MAIN, CONDUIT SIZE ETC. | | | | | | 4)NOTE:PLEASE SUBMIT NEW LOAD CALC ON | | | NEW PANEL AND PANEL SCHEDULE. | | | | | | 5)NOTE: PLEASE PROVIDE AIC RATING OF | | | EQUIPMENT MAINS. MAINS MUST BE RATED TO | | | HANDLE THE AVAILABLE FAULT CURRENT. | | | 110-9/215-5 | | | | | | 6)NOTE: PLEASE SHOW A MORE DETAIL LAYOUT | | | OF THE SERVICE AND THE TENANT SPACES | | | AND WHERE EACH SERVICE FOR EACH TENANT - | | | IS BEING SEPARATED BY FIRE WALLS. | | | MAINS MUST BE GROUPED AND LABELED 1OF3, | | | 2OF 3,ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2000-07-20 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2000-07-20 |
Time |
15:21 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO CIVIL PLANS TO REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-04-12 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-04-12 |
Time |
11:11 |
Rev Time |
0.20 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2000-12-08 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-08 |
Time |
15:12 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2000-12-08 |
Time |
15:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2000-11-30 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-30 |
Time |
08:17 |
Rev Time |
0.75 |
| Received By |
jleech |
Date |
2000-11-30 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED; | | | 1.ONE 3" VENT STACK IS REQUIRED IN | | | BUILDING. SPC 904.3.1. SHOW COMPLETE | | | PLUMBING ON SANITARY RISER DIAGRAM. | | | | | | 2.DRINKING FOUNTAIN TO BE HIGH LOW | | | TO ACCOMMODATEWHEELCHAIRS AND PEOPLE | | | WHO HAVE TROUBLE BENDING AND STOOPING. | | | FACBC 4.15. | | | | | | 3.BATHROOM FACILITIES MUST MEET HANDICAP | | | REQUIREMENTS SINCE BUILDING HAS BEEN | | | DIVIDED. | | | | | | PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-11-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-17 |
Time |
14:14 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-11-17 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-11-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-14 |
Time |
08:03 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2000-11-14 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED; | | | 1.INFORMATION ON D.I. SYSTEM NOT | | | SUBMITED. | | | 2.WATER DRAIN NOT SHOWN ON PLUMBING | | | DIAGRAM.[DRAIN FOR D.I. SYSTEM] | | | 3.WATER RISER NOT CORRECT. RISER SHOWS | | | TWO EYE WASH STATIONS BEFORE D.I. | | | SYSTEM. | | | 4.HC ELEVATION W/C MEASUREMENT SHOULD | | | BE 1'6" OF WALL NOT 2'. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-10-29 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-29 |
Time |
15:42 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-10-29 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SUBMIT SANITARY AND WATER RISER | | | DIAGRAMS FOR REVIEW THAT REFLECT ALL | | | CHANGES TO THE PLUMBING SYSTEM.COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.104.2.1. | | | | | | 2)SUBMIT DETAILS ON "WATER DRAIN", | | | "WATER INTAKE",AND WATER D.I. SYSTEM. | | | | | | CALL IF YOU HAVE QUESTIONS. | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|