| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-DESIGNER, ARTHUR L PATTERSON, IS NOT |
| | AN ARCHITECT OR ENGINEER. THEREFORE, |
| | HE DOESN'T QUALIFY TO FILL OUT AND |
| | SIGN AND SEAL THE DESIGN CERTIFICATION |
| | FOR BUILDING CODE COMPLIANCE FORM |
| | (CHAPTER 471 AND 481 FLORIDA STATUTES) |
| | -CITY AMENDMENTS SECTION 104.2.3 ALLOWS |
| | OTHER PERSON OTHER THAN AN ARCHITECT |
| | OR ENGINEER TO PROVIDE DESIGN SERVICES |
| | PROVIDED THAT THE ENTIRE DWELLING |
| | CONFORMS TO A PRESCRIPTIVE STANDARD. |
| | THE CITY HAS ADOPTED THE STANDARD FOR |
| | HURRICANE RESISTANT RESIDENTIAL |
| | CONSTRUCTION, KNOWN AS SSTD 10-97, AS |
| | THE PRESCRIPTIVE STANDARD. |
| | -USE THE SSTD 10-97 GUIDELINES TO |
| | DESIGN THE FOUNDATION, SHOW THE |
| | ENDWALLS AND SIDEWALLS, SHEARWALLS, |
| | CALCULATE THE UPLIFT LOADS, SHOW THE |
| | CONTINUITY OF VERTICAL WALL REINFORCE- |
| | MENT, SPECIFY TIE BEAMS AND LINTELS, |
| | REINFORCEMENT AT ENDS OF OPENINGS AND |
| | CORNERS. |
| | NOTE: ALL THIS INFORMATION CAN BE |
| | IN CHAPTER 2 OF SSTD 10-97. |
| | 2-EGRESS WINDOWS FROM MASTER BEDROOM AND |
| | BEDROOM BEHIND THE MASTER BATHROOM |
| | DON'T COMPLY WITH THE MINIMUM SIZE |
| | REQUIREMENTS OF SECTION 1005.4.4 OF |
| | SBC 1997. |
| | 3-CLARIFY IF THE HOUSE HAS CENTRAL AIR |
| | CONDITIONING OR NOT. IF SO, CLARIFY |
| | HOW IS THE ADDITION GOING TO BE AIR |
| | CONDITIONED. PROVIDE PLANS AND SPECS. |
| | 4-HOW IS THE MASTER BATHROOM GOING TO BE |
| | VENTILATED? SECTION 1203.4.2 SBC 1997. |
| | 5-PROVIDE COMPLETE BUCK DETAILS FOR |
| | EXTERIOR DOOR AND WINDOWS. SECTION |
| | 104.2.2 CITY AMENDMENTS TO SBC 1997. |
| | 6-PROVIDE TYPICAL WALL SECTION SHOWING |
| | REINFORCEMENT AROUND WINDOW OPENINGS |
| | IN ORDER TO RECEIVE THE INSTALLATION |
| | OF STORM PANELS. SECTION 104.2.2 CITY |
| | AMENDMENTS TO SBC 1997. |
| | 7-PROVIDE COMPLETE INFORMATION FOR |
| | STORM PANELS. |
| | 8-CLARIFY CONNECTION OF NEW WOOD TRUSSES |
| | TO EXISTING TIE BEAM. HOW ARE THE TWO |
| | CONNECTORS SPECIFIED IN THE WALL |
| | SECTION GOING TO BE NAILED TO THE TIE |
| | BEAM. SEC 104.2.2 CITY AMENDMENTS. |
| | NOTE: THIS ARE WOOD TO WOOD CONNECTORS |
| | NOT WOOD TO CONCRETE. |
| | 9-PROVIDE COMPLETE ROOF FRAMING PLAN |
| | INDICATING TRUSSES SIZE AND BLOCKING |
| | AND BRIDGING REQUIRED. SEC 104.2.2 OF |
| | CITY AMENDMENTS TO SBC 1997. |
| | 10-SEE COMMENTS ON PLANS AND REVISE AND |
| | UPDATE DRAWINGS AS REQUIRED. |
| | NOTE: RETURN REVIEWED DRAWINGS TO |
| | EXPEDITE THE REVIEW PROCESS. |
| | 11-PROVIDE PRODUCT APPROVAL FOR EXTERIOR |
| | DOOR AND WINDOWS, SINGLE PLY ROOFING |
| | SYSTEM. |
| | |
| | |
| | NOTE: SEE COMMENTS BY ELECTRICAL AND |
| | MECHANICAL PLAN REVIEWERS. |