Plan Review Details - Permit 00040162
Plan Review Stops For Permit 00040162
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-04-13 Cont ID  
Sent By dpalmer Date 2000-04-13 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2000-04-13 Time 14:47 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT******************
  
 1)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATION FOR EXISTING SERVICE.AS REQ`
 -D BY 220-3-C-1
  
 2)NOTE: PLEASE SUBMIT NEW PANEL SCHEDULE
 FOR MAIN PANEL. PLEASE INCLUDE THE DED-
 -ICATED CIRCUTS FOR BATH(S) AS PER
 210-11-C-3
  
 3)NOTE:PLEASE SHOW THE REQ`D OUTLET FOR
 REAR OF DWELLING AS PER 210-52E
  
 4)NOTE: MORE OUTLETS ARE REQ`D IN NEW
 ADDITION AREA PER 210-52 2`,6`,12` RULE
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-05-01 Cont ID  
Sent By cthirben Date 2000-05-01 Time 16:49 Rev Time 0.00
Received By cthirben Date 2000-05-01 Time 16:50 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 MECHANICAL PERMIT REQUIRED TO INSTALL
 A/C UNIT.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-04-17 Cont ID  
Sent By tlarge Date 2000-04-17 Time 10:57 Rev Time 0.33
Received By tlarge Date 2000-04-17 Time 10:57 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-05-01 Cont ID  
Sent By jgomez Date 2000-05-01 Time 20:43 Rev Time 2.50
Received By jgomez Date 2000-05-01 Time 20:43 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-DESIGNER, ARTHUR L PATTERSON, IS NOT
 AN ARCHITECT OR ENGINEER. THEREFORE,
 HE DOESN'T QUALIFY TO FILL OUT AND
 SIGN AND SEAL THE DESIGN CERTIFICATION
 FOR BUILDING CODE COMPLIANCE FORM
 (CHAPTER 471 AND 481 FLORIDA STATUTES)
 -CITY AMENDMENTS SECTION 104.2.3 ALLOWS
 OTHER PERSON OTHER THAN AN ARCHITECT
 OR ENGINEER TO PROVIDE DESIGN SERVICES
 PROVIDED THAT THE ENTIRE DWELLING
 CONFORMS TO A PRESCRIPTIVE STANDARD.
 THE CITY HAS ADOPTED THE STANDARD FOR
 HURRICANE RESISTANT RESIDENTIAL
 CONSTRUCTION, KNOWN AS SSTD 10-97, AS
 THE PRESCRIPTIVE STANDARD.
 -USE THE SSTD 10-97 GUIDELINES TO
 DESIGN THE FOUNDATION, SHOW THE
 ENDWALLS AND SIDEWALLS, SHEARWALLS,
 CALCULATE THE UPLIFT LOADS, SHOW THE
 CONTINUITY OF VERTICAL WALL REINFORCE-
 MENT, SPECIFY TIE BEAMS AND LINTELS,
 REINFORCEMENT AT ENDS OF OPENINGS AND
 CORNERS.
 NOTE: ALL THIS INFORMATION CAN BE
 IN CHAPTER 2 OF SSTD 10-97.
 2-EGRESS WINDOWS FROM MASTER BEDROOM AND
 BEDROOM BEHIND THE MASTER BATHROOM
 DON'T COMPLY WITH THE MINIMUM SIZE
 REQUIREMENTS OF SECTION 1005.4.4 OF
 SBC 1997.
 3-CLARIFY IF THE HOUSE HAS CENTRAL AIR
 CONDITIONING OR NOT. IF SO, CLARIFY
 HOW IS THE ADDITION GOING TO BE AIR
 CONDITIONED. PROVIDE PLANS AND SPECS.
 4-HOW IS THE MASTER BATHROOM GOING TO BE
 VENTILATED? SECTION 1203.4.2 SBC 1997.
 5-PROVIDE COMPLETE BUCK DETAILS FOR
 EXTERIOR DOOR AND WINDOWS. SECTION
 104.2.2 CITY AMENDMENTS TO SBC 1997.
 6-PROVIDE TYPICAL WALL SECTION SHOWING
 REINFORCEMENT AROUND WINDOW OPENINGS
 IN ORDER TO RECEIVE THE INSTALLATION
 OF STORM PANELS. SECTION 104.2.2 CITY
 AMENDMENTS TO SBC 1997.
 7-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS.
 8-CLARIFY CONNECTION OF NEW WOOD TRUSSES
 TO EXISTING TIE BEAM. HOW ARE THE TWO
 CONNECTORS SPECIFIED IN THE WALL
 SECTION GOING TO BE NAILED TO THE TIE
 BEAM. SEC 104.2.2 CITY AMENDMENTS.
 NOTE: THIS ARE WOOD TO WOOD CONNECTORS
 NOT WOOD TO CONCRETE.
 9-PROVIDE COMPLETE ROOF FRAMING PLAN
 INDICATING TRUSSES SIZE AND BLOCKING
 AND BRIDGING REQUIRED. SEC 104.2.2 OF
 CITY AMENDMENTS TO SBC 1997.
 10-SEE COMMENTS ON PLANS AND REVISE AND
 UPDATE DRAWINGS AS REQUIRED.
 NOTE: RETURN REVIEWED DRAWINGS TO
 EXPEDITE THE REVIEW PROCESS.
 11-PROVIDE PRODUCT APPROVAL FOR EXTERIOR
 DOOR AND WINDOWS, SINGLE PLY ROOFING
 SYSTEM.
  
  
 NOTE: SEE COMMENTS BY ELECTRICAL AND
 MECHANICAL PLAN REVIEWERS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-06 Cont ID  
Sent By gjoyce Date 2000-04-06 Time 15:41 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***