Plan Review Details - Permit 00040056
Plan Review Stops For Permit 00040056
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-05-02 Cont ID  
Sent By cthirben Date 2000-05-02 Time 21:20 Rev Time 0.00
Received By dpalmer Date 2000-05-02 Time 21:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-15 Cont ID  
Sent By cthirben Date 2000-04-15 Time 10:46 Rev Time 1.00
Received By cthirben Date 2000-04-15 Time 10:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-04-18 Cont ID  
Sent By tlarge Date 2000-04-18 Time 20:43 Rev Time 0.33
Received By tlarge Date 2000-04-18 Time 20:43 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-08-03 Cont ID  
Sent By jgomez Date 2000-08-03 Time 10:22 Rev Time 0.50
Received By jgomez Date 2000-08-03 Time 10:22 Sent To  
Notes
2001-01-08 00:00:00ENTRY DOORS PRODUCT APPROVAL:
 1-PRODUCT APPROVAL CALLS FOR OUTSWING
 DOORS, WHILE ARCHITECTURAL DRAWING
 CALLS FOR INSWING DOORS. REVISE DWGS
 AS REQUIRED.
 2-PRODUCT APPROVAL FOR ENTRY DOORS
 REQUIRES A 2X BUCK. PROVIDE 2X
 STRUCTURAL BUCK DETAIL.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-05-22 Cont ID  
Sent By jgomez Date 2000-05-22 Time 21:04 Rev Time 2.00
Received By jgomez Date 2000-05-22 Time 21:04 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE ROOF FRAMING PLAN SHOWING THE
 CALCULATED UPLIFT LOADS AND ANCHOR
 SCHEDULE. SEC 104.2.2 CITY AMENDMENTS.
 2-REVISE THE DESIGN CERTIFICATION FOR
 BUILDIONG CODE COMPLIANCE FORM. THE
 MEAN ROOF HEIGHT IS 23'-0" PLUS OR
 MINUS, NOT 20'-0". MEAN ROOF HEIGHT IS
 TAKEN FROM GRADE, NOT FROM FINISH
 FLOOR, TO THE AVERAGE POINT OF THE
 HIGHEST ROOF.
 3-PRODUCT APPROVALS:
 -PROVIDE PRODUCT APPROVAL FOR GOLFCART
 GARAGE DOOR.
 -PROVIDE PRODUCT APPROVAL FOR "INSWING"
 ENTRY DOORS.
 4-CLARIFY SIZE OF FOOTING F-1. SHEET #1
 SPECIFIES 18"X18" FOOTING, BUT SHEET
 #6 (WALL SECTION) SPECIFIES A 20"X18"
 FOOTING.
 5-PROVIDE COMPLETE SETS OF ENGINEERED
 ROYAL WALL PANELS SHOWING THE CONCRETE
 THICKNESS AND REINFORCEMENT. SIGNED,
 SEALED AND DATED.
 SECTION 104.2.2 CITY AMENDMENTS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-05 Cont ID  
Sent By gjoyce Date 2000-04-05 Time 09:23 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***