Plan Review Details - Permit 00040022
Plan Review Stops For Permit 00040022
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2000-07-12 Cont ID  
Sent By bstaples Date 2000-07-12 Time 12:18 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2000-07-11 Cont ID  
Sent By bstaples Date 2000-07-11 Time 09:17 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. LETTER FROM SPECIAL INSPECTOR IN FILE
  
 2. ITEMS TWO THREE AND FOUR NOT
 ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-06-22 Cont ID  
Sent By bstaples Date 2000-06-22 Time 13:42 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. LETTER FORM SPECIAL INSPECTOR IS A
 COPY ORIGIONAL REQUIRED.
 2. STATE OF FLORIDA LICENSED CONTRACTOR
 TO SECURE PERMIT.
 3. ORIGIONAL FLORIDA ENERGY SHEETS WITH
 SEAL AND SIGNATURE OF FLORIDA ENG. OR
 ARC. REQUIRED COPY SUBMITTED.
 4. SHEET S-2 REVISE PLYWOOD NOTE TO
 REQUIRE FIRE RETARDANT TREATED
 PLYWOOD.
  
 ITEMS LISTED HAVE BEEN REQUESTED ON
 PRIOR REVIEWS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-06-01 Cont ID  
Sent By bstaples Date 2000-06-01 Time 13:42 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SECOND REVIEW
 1. STATE OF FLORIDA LICENSED CONTRACTOR
 TO MAKE APPLICATION FOR PERMIT AND PAY
 ALL FEES DUE.
 2. FLORIDA ENERGY SHEETS REQUIRED MUST
 BE ORIGIONAL WITH SEAL AND SIGNATURE OF
 A LICENSED FLORIDA ARC. OR ENG.
 3. EXTER GLAZING SHALL MEET THE LARGE
 MISSLE IMPACT STANDARD SHUTTERS ARE NOT
 PERMITTED. SEE SHEETS A-1.1 & A-4 ECT.
 PROVIDE METRO DADE OR SBCCI PRODUCT
 APPROVALS FOR ALL EXTERIOR GLAZING.
 4. SHEET S-2 REVISE PLYWOOD TO FIRE
 RETARDANT TREATED. SEE 1997 SBC,
 SECTION 707.1.3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-04-04 Cont ID  
Sent By bstaples Date 2000-04-04 Time 12:07 Rev Time 0.00
Received By bstaples Date 2000-04-04 Time 12:54 Sent To  
Notes
2001-01-08 00:00:001. CONTRACTOR MUST BE CERTIFIED TO WORK
 IN THE STATE AND THE CITY.
  
 2. DRAWINGS ARE NOT SIGNED AND SEALED BY
 A STATE OF FLORIDA LICENSED ARCHITECT OR
 ENGINEER.
  
 3. FLORIDA ENERGY SHEETS SEE FLORIDA
 ENERGY CODE 1997 EDITION.
  
 4. EXTERIOR GLAZING SHALL BE IMPACT
 RESISTANT SEE 1997 STANDARD BUILDING
 CODE CHAPTER 16 AND CITY OF WEST PALM
 BEACH AMENDMENTS FOR SSTD 12-97, 110MPH.
  
 5. SHEET S-2, PLYWOOD SEE 1997 STANDARD
 BUILDING CODE CHAPTER 6, TABLE 600,
 SECTION 704.2 AND 707.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-10-16 Cont ID  
Sent By dpalmer Date 2000-10-16 Time 18:03 Rev Time 0.00
Received By dpalmer Date 2000-10-16 Time 17:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-06-27 Cont ID  
Sent By dpalmer Date 2000-06-27 Time 21:04 Rev Time 0.00
Received By dpalmer Date 2000-06-27 Time 21:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-04-05 Cont ID  
Sent By jleahy Date 2000-04-05 Time 13:54 Rev Time 0.45
Received By jleahy Date 2000-04-05 Time 13:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-07-12 Cont ID  
Sent By bstaples Date 2000-07-12 Time 12:18 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00M. CARSILLO RELEASED BY TELEPHONE 7/12.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-06-29 Cont ID  
Sent By bstaples Date 2000-06-29 Time 08:53 Rev Time 0.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED NO REVISIONS RECEIVED SEE PRIOR
 NOTES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-04-26 Cont ID  
Sent By bstaples Date 2000-04-26 Time 07:38 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE REVIEW NOTES ATTACHED TO PLANS
 M. CARSILLO DATED 4/17/00

Review Stop FS  
Rev No 1 Status P Date 2000-06-29 Cont ID  
Sent By mcarsill Date 2000-06-29 Time 14:53 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) FIRE SPRINKLER SYSTEM TO COMPLY WITH
 NFPA 13.
 2) ENTIRE SPACE IS TO BE PROTECTED BY
 FIRE SPRINKLERS.
 3) NO FIRE SPRINKLER HEAD SHOWN IN
 BOTTOM OF ELEVATOR SHAFT.
 4) UNDERSIDE OF ROTUNDA IS TO BE
 PROTECTED BY FIRE SPRINKLERS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-10-17 Cont ID  
Sent By ndenmark Date 2000-10-17 Time 18:08 Rev Time 0.25
Received By ndenmark Date 2000-10-17 Time 18:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-06-30 Cont ID  
Sent By cthirben Date 2000-06-30 Time 12:09 Rev Time 1.00
Received By cthirben Date 2000-06-30 Time 12:04 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
  
 ROOF MOUNTED CONDENSER UNIT NEEDS DETAIL
 OF STANDS AND MOUNTING METHOD.
 NOTE:
  
 LOCAL CODE REQUIRES MIN. OF 18" OF CLEAR
 ANCE BETWEEN ROOF SURFACE AND BOTTOM OF
 SUPPORT BEAM OF STAND.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-06-08 Cont ID  
Sent By cthirben Date 2000-06-08 Time 13:15 Rev Time 1.00
Received By cthirben Date 2000-06-08 Time 13:13 Sent To  
Notes
2001-01-08 00:00:00NOTES***********************************
 NO CHANGES WERE MADE ON SUBMITTED REVI-
 SION DATED 0N 06.01.00.
 CHECK ATTACHED MECHANICAL NOTES 04.07.00
 FOR REVISED NOTES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-04-07 Cont ID  
Sent By ndenmark Date 2000-04-07 Time 13:12 Rev Time 1.50
Received By ndenmark Date 2000-04-07 Time 13:12 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
  
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 UNIT PER ASHRAE 62-89
 2) PROVIDE AIR BALANCE CALCULATIONS TO
 SHOW COMPLIANCE WITH 1997 SMC 501.2
 3) AHU #5 SUPPY AIR OVER DESIGN AMOUNT
 4) AHU #1 SHOWS ONE DIFFUSER WITH NO
 AMOUNT CFM DESIGNED
 5) AHU #3 AND FC-1 SHOWS NO RETURN AIR
 6) ROOF MOUNTED CONDENSING UNIT NEEDS
 DETAIL OF STANDS AND MOUNTING METHOD.
 NOTE: LOCAL CODE REQUIRES MIN. 18" OF
 CLEARANCE BETWEEN ROOF SURFACE AND
 BOTTOM OF SUPPORT BEAM OF STAND
  
 PROVIDE ABOVE INFROMATION FOR REVIEW OF
 THIS PROJECT

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-06-28 Cont ID  
Sent By tlarge Date 2000-06-28 Time 10:25 Rev Time 0.50
Received By tlarge Date 2000-06-28 Time 10:25 Sent To  
Notes
2001-01-08 00:00:00COMPLY W/ALL PREVIOUS COMMENTS DATED
 6/1/00.
  
 SIZE THE SECTION OF THE WATER RISER FOR
 THE RESTROOMS.
  
 SUBMIT THE OCCUPANT LOAD BASED ON THE
 SQUARE FOOT AREA OF HABITABLE FLOOR
 SPACE.SEE SPC SEC.407.1.3.FOR ALLOWED
 DEDUCTIBLE AREAS.THE MINIMUM NUMBER OF
 SANITARY FACILITIES SHALL BE BASED UPON
 THIS OCCUPANT LOAD.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT 561-659-8096,EXT.8377.
 TIMOTHY LARGE,PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-06-01 Cont ID  
Sent By tlarge Date 2000-06-01 Time 17:37 Rev Time 1.00
Received By tlarge Date 2000-06-01 Time 17:37 Sent To  
Notes
2001-01-08 00:00:00THE MINIMUM REQUIRED NUMBER OFSANITARY
 FACILITIES SHALL COMPLY W/TABLE 407 OF
 1994 EDITION OF SPC.PRESENTLY THERE ARE
 INSUFFICIENT FACILITIES.SEE SPC SECTION
 407.1.3.FOR ALLOWED DEDUCTIBLE AREAS.
  
 SINK IN LOUNGE SHALL BE HANDICAP ACCESS-
 IBLE AND COMPLY W/FACBC SEC.4.24.1-
 4.24.7.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY A PERMANENT
 FIXED LADDER OR RELOCATE TO FLOOR.
  
 INSTALLATION OF VENTS ON FLOOR DRAINS
 AND MOP SINK SHALL COMPLY W/SPC SEC.
 906.2.1.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 FLOOR DRAINS SHALL BE EQUIPPED W/TRAP
 PRIMERS PER SPC SEC.409.4.1.1.
  
 WIDTH OF H.C. STALL SHALL COMPLY W/FACBC
 SEC/4.17.3.FIXTURE CLEARANCE OF LAV.
 SHALL COMPLY W/SPC SEC.403.1,403.4.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-16 Cont ID  
Sent By tlarge Date 2000-05-16 Time 20:14 Rev Time 1.50
Received By tlarge Date 2000-05-16 Time 20:09 Sent To  
Notes
2001-01-08 00:00:00THE MINIMUM REQUIRED NUMBER OF SANITARY
 FACILITIES SHALL COMPLY W/TABLE 407 OF
 1994 EDITION OF SPC.PRESENTLY THERE ARE
 INSUFFICIENT FACILITIES.SEE SPC SECTION
 407.1.3 FOR ALLOWED DEDUCTIBLE AREAS.
  
 SINK IN LOUNGE SHALL BE HANDICAP
 ACCESSIBLE AND COMPLY W/FACBC SEC.4.24.1
 THRU 4.24.7.
  
 SHT.A-8-HEIGHT OF HANDICAP WATER CLOSET
 SHALL COMPLY W/FACBC SEC.4.16.3.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY A PERMANENT
 FIXED LADDER OR RELOCATE TO FLOOR.
  
 INSTALLATION OF VENTS ON FLOOR DRAINS
 SHALL COMPLY W/SPC SEC.906.2.1.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.