Plan Review Details - Permit 00040002
Plan Review Stops For Permit 00040002
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-05-15 Cont ID  
Sent By hpiskura Date 2000-05-15 Time 07:27 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-15 Cont ID  
Sent By dpalmer Date 2000-05-15 Time 07:21 Rev Time 0.00
Received By dpalmer Date 2000-05-15 Time 07:21 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO ***************
  
 1)NOTE: YOU SHOW ON SHEET E-1 TWO SETS
 OF 350 MCIL. THIS IS CORRECT. YOU CANNOT
 USE THE TAP RULE. THESE ARE THE MAIN
 FEEDERS. PLEASE THE CONDUCTOR SIZES YOU
 SHOW ON E-1.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 X8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-04-17 Cont ID  
Sent By dpalmer Date 2000-04-17 Time 19:13 Rev Time 0.00
Received By dpalmer Date 2000-04-17 Time 19:13 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: SHEET E-2 YOU SHOW GROUNDING
 ELECTRODE GOING TO GROUND RING AROUND
 EQUIPMENT. THIS IS FINE BUT YOU ALSO
 NEED GROUNDING ELECTRODE CONDUCTOR
 GOING TOO BLDG. STEEL AND CONCRETE REBAR
 AS REQ`D BY 250-50 OF THE '99' NEC.
 PLEASE SHOW GOING TO THOSE LOCATIONS.
 215-5.
  
 2)NOTE: ALSO PLEASE INCLUDE ANY METERCAN
 OR METER CT`S ON PLANS.215-5
  
 3)NOTE: YOU SHOW A 600 AMP DISC WITH 600
 AMP OVERCURRENT PROTECTION FOR 500 MCM
 WIRE. OVERCURRENT PROTECTION NEEDS TO BE
 AT 400 AMPS. 310-16
  
 4)NOTE: YOU SHOW THE AIC RATING OF THE
 400 AMP CONTROL PANEL BUT NEED TO SUBMIT
 THE AIC RATINGOF MAIN DISC. 110-9
 215-5 MAIN MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS PLEASE
 CALL 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-05-09 Cont ID  
Sent By rturnque Date 2000-05-09 Time 15:02 Rev Time 0.45
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-13 Cont ID  
Sent By gjoyce Date 2000-04-13 Time 09:06 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved