Plan Review Details - Permit 00031752
Plan Review Stops For Permit 00031752
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-18 Cont ID  
Sent By dpalmer Date 2000-07-18 Time 19:20 Rev Time 0.00
Received By dpalmer Date 2000-07-18 Time 19:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-04-21 Cont ID  
Sent By dpalmer Date 2000-04-21 Time 07:07 Rev Time 0.00
Received By dpalmer Date 2000-04-21 Time 07:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-10-18 Cont ID  
Sent By jleech Date 2000-10-18 Time 19:47 Rev Time 0.33
Received By jleech Date 2000-10-18 Time 19:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-17 Cont ID  
Sent By cthirben Date 2000-07-17 Time 11:41 Rev Time 1.00
Received By cthirben Date 2000-07-17 Time 11:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-17 Cont ID  
Sent By cthirben Date 2000-04-17 Time 08:50 Rev Time 1.00
Received By cthirben Date 2000-04-17 Time 08:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-31 Cont ID  
Sent By tlarge Date 2000-08-31 Time 09:06 Rev Time 0.25
Received By tlarge Date 2000-08-31 Time 09:06 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY RISER.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-07-12 Cont ID  
Sent By tlarge Date 2000-07-12 Time 18:23 Rev Time 0.30
Received By tlarge Date 2000-07-12 Time 18:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-04-18 Cont ID  
Sent By tlarge Date 2000-04-18 Time 06:29 Rev Time 0.33
Received By tlarge Date 2000-04-18 Time 06:29 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-08-01 Cont ID  
Sent By lhatten Date 2000-08-01 Time 18:37 Rev Time 2.50
Received By lhatten Date   Time   Sent To  
Notes
2001-01-08 00:00:00OK PER LOU HATTEN

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-05-23 Cont ID  
Sent By jcaloger Date 2000-05-23 Time 12:37 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLAN #1, DESIGN COMPLIANCE STATEMENT HAS
 THE INCORRECT BASIC VELOCITY PRESSURES
 FOR A MEAN ROOF HT OF 18 FEET. DO NOT
 WRITE IN CHANGES SUBMIT REVISED PLAN.
 *** INSERT NEWW PLAN IN SET***
  
  
 THE SOIL REPORTY NEEDS THE ORIGINAL
 SIGNATURE OF THE ENGINEER WITH DATE.
  
  
 THE REAR ELEVATION ILLUSTRATES A FIXED
 WINDOW IN THE MASTER BEDROOM.NOTE THAT
 THE WINDOWS IN ALL BEDROOM ARE REQUIRED
 TO PROVIDE A MEANS OF EGRESS ACCORDING
 TO SECT 1005.4 SBC 1997.CLARIFY
  
 PROVIDE THE ENGINEER CALCULATIONS USED
 FOR DETERMINING THE WIND PRESSURES FOR
 THE OVERHEAD GARAGE DOOR.NOTE THAT THE
 END ZONES ARE REQUIRED TO BE A MINIMUM
 OF 3 FEET WIDE.FOR THIS MODEL THE
 DOOR IS LOCATED IN THE END ZONE.
 SECT 1606.2C SBC 1997
  
  
 THE TRUSS ENGINEERINGNEEDS TO SPECIFY
 THE DESIGN CRITERIA, EX SBC 1997, ASCE 7
 95.ALSO THE MEAN ROOF HEIGHT DIFFERS
 FROM THE ENGINEERS DESIGNED ROOF HEIGHT
 OF 18 FEET.
  
 THE TRUSS ENGINEERING NEEDS THE RAISED
 SEAL AND ORIGINAL SIGNATURE OF THE
 ENGINEER,JUILUS LEE.
  
  
 THE TRUSS ENGINEERING AND LAYOUT NEEDS
 TO SPECIFY AND AND HAVE THE BUILDING
 ADDRESS.
  
 PROVIDE A ILLUSTRATION OF ATTACHING THE
 BEARING WOOD FRAME WALL TO THE SLAB.
 SPECIFY THE HARDWARE CONNECTORS FOR TOP
 AND BOTTOM ALSO STUD CONNECTIONS..

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-05 Cont ID  
Sent By gjoyce Date 2000-04-05 Time 10:07 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***