| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-FLOOD ZONE "AO". WILL NEED ELEVATION |
| | CERTIFICATE. |
| | -LOWEST FLOOR ELEVATION TO BE NO LESS |
| | THAN 18" ABOVE THE CROWN OF THE ROAD. |
| | SEC. 3107.1.1 CITY AMENDMENTS. |
| | 2-CLEARLY INDICATE AREAS TO HAVE SAFETY |
| | GLASS. SEE PLANS FOR COMMENTS. |
| | SECTION 2405.2 SBC 1997. |
| | 3-CLARIFY WINDOW SIZE FOR BEDROOMS #2 |
| | AND #3. WHAT IS A SH 34+4?. WINDOW TO |
| | HAVE MINIMUM 24" CLEAR HEIGHT OPENING. |
| | SECTION 1005.4 SBC 1997. |
| | 4-DESIGN CERTIFICATION FOR BUILDING CODE |
| | COMPLIANCE FORM: |
| | -ENGINEER WHO SEALED THIS FORM TO SEAL |
| | THE STRUCTURAL DRAWINGS TOO. |
| | -REVISE MEAN ROOF HEIGHT. 16'-0" PLUS |
| | OR MINUS. MEAN ROOF HEIGHT IS TAKEN |
| | FROM GRADE, NOT FROM FINISH FLOOR, TO |
| | THE AVERAGE POINT OF THE HIGHEST ROOF. |
| | 5-REVISE/UPDATE DRAWINGS. SEE COMMENTS |
| | ON PLANS. |
| | 6-SOIL TEST REPORT TO HAVE ORIGINAL |
| | SIGNATURE AND DATE WHEN THE DOCUMENT |
| | WAS SEALED BY THE ENGINEER. |
| | 7-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| | DOOR WITHOUT SIDELITES AND WITH |
| | LEGIBLE DRAWINGS. |
| | 8-PROVIDE COPIES OF TEST REPORTS FOR |
| | SLIDING GLASS DOORS AS PER ASTM E-330. |
| | SECTION 1706 SBC 1997. |
| | -PROFESSIONAL OF RECORD TO WRITE JOB |
| | LOCATION FOR SITE SPECIFIC PRODUCT |
| | APPROVAL FOR DOORS AND WINDOWS BY |
| | NORANDEX. ASLO, CLEARLY INDICATE WHICH |
| | WINDOW TYPE AND SIZE ARE GOING TO BE |
| | USED ON THIS PROJECT. |
| | -PROFESSIONAL OF RECORD TO CLEARLY |
| | PROVIDE NAME, ADDRESS, LICENSE NUMBER |
| | AND TELEPHONE NUMBER ON THIS PRODUCT |
| | APPROVAL. |
| | 9-STORM PANELS: |
| | -CLEARLY INDICATE FASTENING METHOD AND |
| | ANCHOR TYPE AND SPACING TO BE USED ON |
| | THIS PROJECT ACCORDING TO THE DESIGN |
| | PRESSURES, STORM PANEL SPAN, EDGE |
| | DISTANCE AND BUILDING CONSTRUCTION |
| | (MASONRY CONSTRUCTION). |