Plan Review Details - Permit 00031708
Plan Review Stops For Permit 00031708
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-17 Cont ID  
Sent By dpalmer Date 2000-05-17 Time 18:31 Rev Time 0.00
Received By dpalmer Date 2000-05-17 Time 18:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-04-21 Cont ID  
Sent By dpalmer Date 2000-04-21 Time 07:15 Rev Time 0.00
Received By dpalmer Date 2000-04-21 Time 07:15 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLANS SHOW THE SMOKE DETECTORS
 ON THE SAM E CIRCUT WITH THE BATH GFI`S?
 THIS IS NOT PERMITTED BY ART 210-11-C-3
 OF THE NEC.
  
 2)NOTE: PLEASE SHOW THE REQ`D SMOKE
 DETECTOR OUTSIDE BEDROOM #2? ALSO IF THE
 PLEASE NOTE IF THE DEN IS MADE INTO A
 SLEEPING ROOM THIS WILL REQ` SD ALSO.
  
 3)NOTE: PLEASE SUBMIT THE AIC RATING
 OF THE MAIN. THE MAIN MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9
  
 4)NOTE:PLEASE SHOW ON PLANS THE COLD
 WATER PIPE AS PART OF THE GROUNDING
 ELECTRODE SYSTEM PER 250-50/215-5
  
 YOU ARE REFERENCING THE CODES FOR GROUND
 -ING UNDER THE 96 NEC. WE ARE UNDER THE
 99' NEC AND THOSE CODE #`S HAVE CHANGED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS PLEASE
 CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-14 Cont ID  
Sent By cthirben Date 2000-08-14 Time 09:30 Rev Time 1.00
Received By cthirben Date 2000-08-14 Time 09:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-12 Cont ID  
Sent By cthirben Date 2000-04-12 Time 15:07 Rev Time 1.00
Received By cthirben Date 2000-04-12 Time 15:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-16 Cont ID  
Sent By jleech Date 2000-08-16 Time 17:21 Rev Time 0.25
Received By jleech Date 2000-08-16 Time 17:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-04-18 Cont ID  
Sent By tlarge Date 2000-04-18 Time 06:43 Rev Time 0.33
Received By tlarge Date 2000-04-18 Time 06:40 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-05-17 Cont ID  
Sent By rmcdouga Date 2000-05-17 Time 14:03 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
  
 1)PROVIDE FLOOD ELEVATION CERTIFICATE
  
 2)SPECIFY SPECIFIC TYPE OF ANCHORS TO BE
 USED WITH STORM PANELS
  
 3)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO-DADE COUNTY PRODUCT APPROVALS FOR
 HORIZONTAL SLIDING WINDOWS AS SPECIFIED
 ON PLANS

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-05 Cont ID  
Sent By gjoyce Date 2000-04-05 Time 10:19 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***