Plan Review Details - Permit 00031607
Plan Review Stops For Permit 00031607
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-11 Cont ID  
Sent By dpalmer Date 2000-09-11 Time 10:31 Rev Time 0.00
Received By dpalmer Date 2000-09-11 Time 10:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-17 Cont ID  
Sent By dpalmer Date 2000-05-17 Time 17:32 Rev Time 0.00
Received By dpalmer Date 2000-05-17 Time 17:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-01 Cont ID  
Sent By dpalmer Date 2000-05-01 Time 06:58 Rev Time 0.00
Received By dpalmer Date 2000-05-01 Time 06:58 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING OF
 EQUIPMENT MAIN. MAINS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT. 110-9/215-5
  
 2)NOTE: YOU SHOW KITCHEN LIGHTING ON THE
 SMALL APPLIANCE CIRUCIT? PLEASE CORRECT.
  
 3)NOTE;AS PER 210-11-C-3 BATHS ARE TO BE
 ON THEIR OWN! THE SMOKE DETECTORS ARE
 NOT TO BE ON THE CIRCUIT.210-52D
  
 4)NOTE: AS PER 250-50 GROUNDING ELECTROD
 -E TO COLD WATER ASLO IF METAL.
  
 5)NOTE: IN YOUR NOTES YOU ARE REF. '96'
 NEC. PLEASE CHANGE TO REFLECTTHE
 CODE TABLES OF THE '99' NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-14 Cont ID  
Sent By cthirben Date 2000-08-14 Time 09:27 Rev Time 1.00
Received By cthirben Date 2000-08-14 Time 09:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-17 Cont ID  
Sent By cthirben Date 2000-04-17 Time 08:15 Rev Time 1.00
Received By cthirben Date 2000-04-17 Time 08:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-16 Cont ID  
Sent By jleech Date 2000-08-16 Time 17:28 Rev Time 0.25
Received By jleech Date 2000-08-16 Time 17:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-04-18 Cont ID  
Sent By tlarge Date 2000-04-18 Time 08:29 Rev Time 0.33
Received By tlarge Date 2000-04-18 Time 08:29 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-08-01 Cont ID  
Sent By rmcdouga Date 2000-08-01 Time 07:48 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-06-26 Cont ID  
Sent By rmcdouga Date 2000-06-26 Time 11:42 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED
  
 2)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR SLIDING
 GLASS DOORS AND HORIZONTAL SLIDING
 WINDOWS. SITE SPECIFIC ENGINEERING THAT
 WAS SUBMITTED IS NOT ACCEPTABLE.IT DOES
 NOT COVER HORIZONTAL SLIDING WINDOWS AND
 THE SLIDING GLASS DOORS TEST SUMMARIES
 DO NOT SHOW THAT A UNIFORM STATIC AIR
 PRESSURE TEST WAS PREFORMED (ASTM E-330)
 THIS TEST IS FOR WINDLOADS.
 THE SUBMITTAL FOR MUST HAVE THE SITE
 LOCATION LISTED AND BE SIGNED,SEALED AND
 DATED BY THE DESIGN PROFESSIONAL OF
 RECORD.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-05-17 Cont ID  
Sent By rmcdouga Date 2000-05-17 Time 16:38 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)PROVIDE FLOOD ELEVATION CERTIFICATE
  
 2)SPECIFY SPECIFIC TYPE OF ANCHORS TO BE
 USED TO SECURE STORM PANELS PRIOR TO
 INSTALLATION
  
 3)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO-DADE PRODUCT APPROVALS FOR
 HORIZONTAL SLIDING WINDOWS AS SPECIFIED
 ON PLANS
  
 4)SHEETS S-1B AND S-2 NEED TO BE SIGNED
 AND SEALED BY THE DESIGN PROFESSIONAL OF
 RECORD

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-05 Cont ID  
Sent By gjoyce Date 2000-04-05 Time 10:04 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***