| 2001-01-08 00:00:00 | *************** UNSAT ****************** |
| | |
| | 1)NOTE:SMOKE DETECTORS ARE REQ`D INSIDE |
| | AND OUTSIDE ALL SLEEPING ROOMS. |
| | AS PER NFPA-72 2-2.1.1.1 |
| | |
| | 2)NOTE: AS PER 210-52E ONE GFI OUTLET IS |
| | REQ`D BACK OF DWELLING (NEW ADDITION) |
| | THE LOCATION OUTBACK IS YOUR CHOICE. |
| | |
| | 3)NOTE:AS PER 210-52 MISSING OUTLET IN |
| | MASTER BEDROOM. 2` OF WALL. |
| | |
| | 4)NOTE:AS REQ`D BY ART 250-52 C MIN GRND |
| | ROD LENGTH IS 8` FT. PLEASE CORRECT. |
| | |
| | 5)NOTE:PLEASE SHOW ON THE RISER DIAGRAM |
| | THE BLDG. STEEL AS PART OF THE GROUND- |
| | ING ELECTRODE SYSTEM. THIS IS THE STEEL |
| | IN THE NEW ADDITION. 250-50 |
| | |
| | 6)NOTE: NEED TO SUBMIT THE AIC RATING OF |
| | THE MAIN IN YOUR PANEL. AIC RATING FOR |
| | THE MIN AIC CAN BE FIGURED FROM THE |
| | FAULT CURRNET CALCULATIONS. 110-9/215-5 |
| | |
| | 7)NOTE; YOU SHOW ONCE AGAIN AN 18 POLE |
| | /CIRCUT PANEL? PLEASE COUNT UP THE |
| | NUMBER OF BRKRS AND CHANGE THE PANEL TO |
| | ACCOMADATE THE SPACES. 215-5 |
| | |
| | 8)NOTE: YOU SHOW 4500 KW FOR GEN LIGHTIN |
| | -G. THIS IS MORETHAN YOUR 3WATTS PER SQ. |
| | FT. THIS IS OK BUT PLEASE CORRECT TO |
| | REFLECT THE PROPER AMOUNT OF 3696.KW |
| | |
| | 9)NOTE:PLEASE INCLUDE ON PANEL SCHEDULE |
| | THE REQ`D DEDICATED BATH CIRCUT FOR |
| | THE NEW MASTER BATH. AS PER 210-11-C-3 |
| | #12 AWG AND 20 AMP. |
| | 10)NOTE:YOU ARE SHOWING 2500WATTS FOR |
| | THE PUMP ON A SINGLE POLE 20AMP BRKR.?? |
| | THIS LOAD IS TOO LARGE FOR BRKR. PLEASE |
| | DOUBLE CHECK THE LOAD OF PUMP AND IF IT |
| | IS GOING TO BE A 220V LOAD. 215-5 |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTION |
| | PLEASE DO NOT HESITATE TO CALL. |
| | MY # IS 659-8096 EXT 8372 |